1. Introduction
Series capacitor compensation used in long-distance transmission systems can enhance the transfer capability and transient stability. However, it is well-known that capacitors in series with transmission lines can cause subsynchronous resonance (SSR) in power systems. Self-excitation or dynamic instability due to SSR produces very high amplitude mechanical torques in the turbogenerator shaft that could lead to shaft damage [1,2]. The first reported case of SSR in the world occurred at Mohave Power Station in Arizona, where the generator shafting was subjected to a continuously increasing torque, which led to the shafting fracture. After that, several cases of shaft damage caused by SSR have happened. For example: In 2004, the generator rotors of 2# and 3# turbogenerators set cracked due to SSR in Dresden nuclear power plant. In 2008, several SSR events occurred at Yimin power plant in China, which led to the shaft fracture of 3# turbogenerator set. In recent years, wind power has been developing rapidly worldwide, and there have been many incidents of damage to the wind farm equipment caused by SSR [3,4,5,6,7]. For example: In 2009, SSR occurred at the Zorillo-Gulf wind farms. This incident caused multiple transmission devices to trip and many crowbar circuits to fail. During the year 2013, dozens of SSRs occurred in the Guyuan wind power system in Hebei Province, China. More than one thousand wind turbine generators tripped due to overcurrent caused by SSR, and the power of the wind farm dropped sharply in a short time. SSR seriously affects the safe and reliable operation of power systems, which has attracted great attention of countries all over the world.
There are many methods to study SSR in the power system. Amongst these, the eigenvalue analysis, electromagnetic transient analysis, complex torque coefficient analysis, and frequency scanning are the most used methods [8,9,10,11]. A summary of several major analysis methods is shown in Table 1.
The purpose of this paper was to study the SSR characteristics and influence factors of a series compensated transmission system. It can be seen from Table 1 that the combination of eigenvalue analysis method and time domain simulation method can well meet the requirements of accurate analysis. SSR system model, including a variety of electromechanical network modules, is the established. The eigenvalues under 70% series compensation level are analyzed by eigenvalue analysis method for the institute of electrical and electronics engineers (IEEE) first benchmark model (FBM). At the same time, power systems computer-aided design (PSCAD) is used to model and analyze the example, which proves the validity of eigenvalue analysis method. After that, the effects of series compensation levels, synchronous generator parameters, speed governing system parameters, and excitation system parameters on SSR characteristics of the system are studied in detail.
2. Eigenvalue Analysis and System Modeling 2.1. Eigenvalue Analysis
Eigenvalue analysis is a strict and accurate method based on linear theory. In order to analyze SSR characteristics by eigenvalue analysis method, it is necessary to establish the detailed mathematical model of each system component. Then, the linear state-space model is obtained by linearizing the system at the stable operating points.
X˙=AX
whereXis the system state variables of the incremental form, andA is the state matrix of the system. The corresponding eigenvalue equation of the system is [8]
|λI−A|=0
where I is identity matrix. λ is the eigenvalues of matrixA, and it can be expressed as
λi=σi±jωi
In summary, the steps of eigenvalue analysis are as follows:
- A detailed mathematical model is established for various components of the SSR system and the power network, and the differential equations describing the transient process is obtained.
-
By linearizing the differential equations near stable values and writing out the standard formX˙=AX, the state-space representation is acquired, which is suitable for eigenvalue analysis.
- The initial values of the studied system under stable operation are calculated.
- The eigenvalues of characteristic equations are solved, and the stability and damping characteristics of the system are analyzed based on the results.
2.2. System Modeling
The IEEE FBM, which was created by the IEEE Working Group in 1977, is used for SSR studies [12]. The system is shown in Figure 1.
The system consists of a turbogenerator shaft system, which includes high pressure turbine (HP), intermediate pressure turbine (IP), low pressure turbine A (LP-A), low pressure turbine B (LP-B), generator (GEN), and exciter (EXC), and an infinite bus with a series compensated transmission line. The system models include turbogenerator shaft system, turbine speed governing system, turbine prime mover system, generator electromagnetic circuits, exciter system, transmission lines, and series compensation circuit system. The models of the turbine speed governing system and turbine prime mover system are as follows. Other models are given in [13].
2.2.1. Turbine Speed Governing System
The main function of the speed governing system of a modern large turbogenerator is to adjust the speed and load of the system. The state characteristic equations of the speed governing system at an operating point are established as follows [8].
{pΔα=-KGTSRΔω−1TSRΔαpΔμ=1TSMΔα−1TSMΔμ
whereTSMis the integral time constant of the oil motive,KGandTSRare the amplification factor and time constant of the speed regulator, respectively.αandμare the position of the speed relay and the opening of the turbine inlet valve, respectively.
2.2.2. Turbine Prime Mover Model
Figure 2 is a typical turbine prime mover system model. WherePGVis the valve opening signal output from electro-hydraulic servomechanism of the speed governing system.Tcssis the steam volume time constant of the high pressure turbine.Trhsis the steam volume time constant of the reheater.Tcosis the steam volume time constant of the connected pipe. FHP, FIP and FLP are the power ratios of high pressure turbine, medium pressure turbine, and low pressure turbine, respectively.
According to mathematical models of turbine prime mover, the state-space model can be established, and the state characteristic equations at the operating point can be obtained as follows [9]:
{PΔT1=−1TCSSΔT1+FHP+FHP⋅λhTCSSΔPGVPΔT2=−1TrhsΔT2+1Trhs⋅FIP+FIP⋅λm−FHP⋅λhFHP+FHP⋅λhΔT1pΔT3=−1TcosΔT3+1Tcos⋅FLP−FIP⋅λmFIP+FIP⋅λm−FHP⋅λhΔT2ΔT4=ΔT3
whereT1,T2andT3are the mechanical torques of the high pressure turbine, the intermediate pressure turbine, and the low pressure turbine, respectively.
All the above equations consist of the system characteristic equations, including 27 first-order linear differential equations and 27 state variables, which includes 12 state variables of turbogenerator shaft,Xs=[Δω1,Δω2,Δω3,Δω4,Δω5,Δω6,Δδ1,Δδ2,Δδ3,Δδ4,Δδ5,Δδ6 ]T, whereωiis the angular velocity, andδiis the angular displacement of mass i. Two state variables of turbine speed governing system,Xg=[Δα,Δμ]T; three state variables of turbogenerator prime movers,Xy=[ΔT1,ΔT2,ΔT3]T; six state variables of generator electromagnetic voltage circuit,XG=[Δid,Δif,ΔiD,Δiq,Δig]T, whereid,if,iD,iq,igandiQare the currents through six windings of the generator, which are stator equivalent d-axis winding, excitation winding, d-axis damper winding D, stator equivalent q-axis winding, q-axis damping winding g and Q, respectively; two state variables of excitation system,Xe=[ΔuR,ΔEfd]T, whereuRandEfdare an intermediate variable of the excitation system and the output voltage of the exciter, respectively; two state variables of series compensation capacitors,XA=[Δucd,Δucq]T, whereucdanducqare the components of the voltage across the series compensation capacitor at the d-axis and the q-axis, respectively.
3. Case Analysis 3.1. Model Parameters
The IEEE FBM model shown in Figure 1 is used for SSR studies. The system specific parameters and initial state variables are as follows [12].
A. Turbogenerator shaft parameters:
The shaft system of the turbogenerator is modeled as a multi-mass system, including four turbine sections, a generator, and an exciter. Turbogenerator shaft parameters are shown in Table 2.
The natural frequencies of the torsional vibration of the turbogenerator shaft are 15.78, 20.22, 25.56, 32.31, and 47.46 Hz, respectively. The following parameters are given in p.u., unless stated otherwise. B. Turbine prime mover parameters:
FHP= 0.3,FIP= 0.26,FLP= 0.44,Tcss= 0.3,Trhs= 7.0,Tcos= 0.2.
C. Transformer, series compensated transmission lines, and infinite power grid parameters
Pbase=892.4MVA,XT=0.14,RT=0.01,XL=0.56,RL=0.02,XS=0.06.
D. Synchronous generator parameters:
Xd= 1.79,Xq= 1.71,Xad= 1.66,Xaq= 1.58,Xf= 0.001,XD= 1.666,Xg= 1.825,XQ= 1.695,Ra= 0.0015,Rf= 0.001,RD= 0.0037,Rg= 0.0182,RQ= 0.0053.
E. Control system parameters of unit side:
KG=25,TSR= 0.2,TSM= 0.3,KA= 50,TE= 0.002,TA= 0.1.
F. System initial operating condition parameters:
Pe=0.9,Vt= 1.05,cosφ= 0.9(lag).
3.2. Eigenvalue Calculation Results Based on the above system parameters and initial state variables, the eigenvalue analysis method can be used to calculate all 27 eigenvalues of the system, which consists of nine pairs of conjugate complex numbers and nine real numbers. In this model, eigenvalues 1 to 12 (six pairs of conjugate complex numbers) represent the torsional dynamics of the turbogenerator shaft system. Eigenvalues 1 and 2 correspond to the low frequency oscillation mode (TM0). Eigenvalues 3 to 12 correspond to the torsional modes (TM1 to TM5). Eigenvalues 17 to 18 and 19 to 20 represent the supersynchronous and subsynchronous electric network modes, respectively.
The series capacitor compensation level of transmission lines is the dominant factor influencing the electrical damping of subsynchronous oscillations. The definition of compensation levelkCfor series capacitors given by
kC=XCXL
whereXCandXLare the transmission lines capacitive reactance and inductive reactance, respectively.
WhenkC is 0.7, the calculation results are shown in Table 3 (only 12 eigenvalues representing the low frequency and torsional modes of shaft are written in the table). As can be seen from Table 3, the real parts of TM1 and TM2 are greater than zero, which means TM1 and TM2 are unstable, and their corresponding frequencies are 15.96 Hz and 20.38 Hz, respectively. The system is in multimode subsynchronous resonance state. The real part of TM2 is the largest, indicating that the main oscillation frequency of the system is 20.38 Hz.
To verify the validity of the eigenvalue analysis method, PSCAD time domain simulation method was used to analyze the above examples. For the case ofkC is 0.7, a disturbance was set on the electrical side. A three-phase short-circuit fault happened at 1.5 s and was released after 75 ms. The simulation results are shown in Figure 3.
From Figure 3a, it can be noticed that when a three-phase short-circuit fault occurs, the electromagnetic torque of the generator produces a relatively large fluctuation and the amplitude continuously increases with time. From Figure 3b, it can be seen that the fluctuating electromagnetic torque excites the torsional vibration of the shaft, which is manifested by the amplitude oscillation of the shaft torque and divergence with time. It indicates that the system is no longer stable and develops subsynchronous oscillations after a three-phase short-circuit fault occurs. The torque between LP-A and B was analyzed by the fast Fourier transform (FFT). The results are shown in Figure 3c. It can be seen that the torsional vibration frequencies are mainly 15.96 Hz and 20.38 Hz, and the amplitude of 20.38 Hz is the largest, which corresponds to TM1 and TM2. The result is in accordance with that of the eigenvalue analysis method.
4. Analysis of Influence Factors of SSR 4.1. Influence of Compensation Level
The eigenvalue analysis method was used to calculate the system eigenvalues with different compensation levelskC , and the results are shown in Table 4 and Figure 4.
Table 4 shows the system eigenvalues whenkC is 0.1, 0.3, 0.5, 0.7 and 0.9, respectively. Figure 4a describes the variation of the torsional mode frequency and the electrical resonance complementary frequency withkC. In the figure,fSUB corresponds to the electrical resonance complementary frequency, and its calculation formula given by [11]
fSUB=f0(1−XCX″+XT+XL)
wheref0is the synchronous frequency,XTis the leakage reactance of the transformer,X″is the subtransient reactance of the generator, andXCandXL are the transmission line inductive and capacitive reactance, respectively. Figure 4b depicts the variation of the real part of eigenvalue withkC.
It can be seen from Table 4 that eigenvalues are different in the case of differentkC, but all the sums of the eigenvalues are constant and the absolute value is about 696.1, which indicates that the total damping of the system is conserved, that is, the changes ofkCdo not affect the total system damping. ChangingkCwill cause various part damping of the system to be transferred and distributed between different locations, but the total system damping remains unchanged. WhenkCis small, the real part of TM0 is positive, the corresponding damping is negative, and the system is prone to low-frequency oscillations. This is because the total reactance of transmission lines is larger whenkCis low. The electric distance of transmission lines is longer, and low frequency oscillations can occur if a power system stabilizer is not installed in the system. With the increase ofkC, it is equivalent to shortening the electrical distance of the transmission lines and enhancing the connection between generators and the system, and the risk of low frequency oscillations is reduced. WhenkCis greater than 0.3, the real part of the TM0 eigenvalue is negative, which indicates that low-frequency oscillations do not occur in the system.
From Table 4, it can be seen that whenkCis equal to 0.3, the real part of TM4 is positive (0.3233), and the oscillation frequency is 32.27 Hz; whenkCis equal to 0.5, the real part of TM3 is positive (0.4564), and the oscillation frequency is 25.56 Hz; WhenkCis equal to 0.7, the real parts of TM2 and TM1 are positive, and the oscillation frequencies are 20.22 Hz and 15.78 Hz, respectively; whenkCis equal to 0.9, the real part of TM1 is positive (3.9947) and the oscillation frequency is 15.78 Hz. This shows that whenkCis greater than 0.3, at least one eigenvalue of the system is positive, that is, there is always a negative damping of a torsional mode. Then, the system is likely to cause SSR. With the increase ofkC, the dominant oscillation frequency decreases.
From Figure 4a, it can be noticed that the imaginary parts of TM1 to TM5’s eigenvalues change very little in the process ofkCbeing changed from zero to one, that is, the torsional mode frequencies (fTMx) of the turbogenerator shaft remain basically unchanged. The reason is that the torsional natural frequencies are mainly determined by the turbogenerator shaft structure parameters, and the torsional natural frequencies will be determined after the turbogenerator is manufactured. The electrical resonance complementary frequency (fSUB) decreases with the increase ofkC. The changed amplitude is relatively large, and it will generate intersections with different torsional resonant frequencies. At these intersections, the torsional frequency and the electrical resonant frequency are complementary.
From Figure 4b, it can be noticed that the damping of TM1 to TM5 vary greatly. The closerfTMis tofSUB, the larger the real part of the eigenvalue is. WhenfTMis equal tofSUB, the real part of the eigenvalue reaches the maximum, which means that the risk of torsional vibration is maximum. The real part of TM5 eigenvalue (47.46 Hz) is negative in the process ofkCbeing changed from 0 to 1, and it will not cause instability. The other four SSR modes will cause instability, andkCof instability areas are as follows: For TM4 (32.31 Hz),kCof instability areas is between 0.21 and 0.447, and instability is the most serious whenkCis 0.35. For TM3 (25.56 Hz),kCof instability areas is between 0.43 and 0.64, and instability is the most serious whenkCis 0.53. For TM2 (20.22 Hz),kCof instability areas is between 0.67 and 0.72, and instability is the most serious whenkCis 0.71. For TM1 (15.78 Hz),kCof instability areas is between 0.62 and 1.0, and instability is the most serious whenkCis 0.86. Due to the overlapping of instability intervals, the turbogenerator may generate multimode SSR instability problems, for example, whenkCis 0.7, both TM2 and TM1 are in a instability state.
4.2. Influence of Synchronous Generator Parameters
The parameters of synchronous generators include reactance and resistance parameters. The reactance parameters mainly include stator leakage reactanceXl, d-axis synchronous reactanceXd, q-axis synchronous reactanceXq, d-axis armature reaction reactanceXad, q-axis armature reaction reactanceXaq, excitation winding reactanceXf, d-axis damper winding D reactanceXD, q-axis damper winding g reactanceXg, and q-axis damper winding Q reactanceXQ. The resistance parameters mainly include armature winding resistanceRa, excitation winding resistanceRf, d-axis damper winding D resistanceRD, q-axis damper winding g resistanceRg, and q-axis damper winding Q resistanceRQ. Among them, the study of parametersXdandXqfor SSR can be converted into the analysis of parameterXl. TakingkC as 0.5, the generator parameters vary from 50% to 150% of nominal value. The eigenvalue analysis method was used to calculate the eigenvalues of five torsional modes, and the results are shown in Figure 5.
It can be seen from Figure 5a that the frequency of each torsional mode remains basically unchanged whenXl increases, and the other electrical parameters have the same effect on the torsional frequency, which means that the torsional frequency of the turbogenerator shaft is basically irrelevant to the reactance parameters. It can be seen from Figure 5b that the real part of TM3 eigenvalue decreases slightly whenXlincreases, and the corresponding negative damping decreases, which is beneficial to the stability of TM3.
The real part of TM4 eigenvalue increases, which means positive damping decreases and negative damping increases. WhenXlis greater than 1.2, the real part of TM4 eigenvalue changes from negative to positive and TM4 oscillation is excited. The system presents a multimode resonance state in which TM3 and TM4 coexist. The reason is that thefSUBincreases continuously whenXlincreases, which transitions from near fTM3 to near fTM4.
The influence of reactance parametersXf,XD,XgandXQ on the eigenvalues is similar, so Figure 5c shows only the influence ofXf . It can be seen from the Figure 5c, the influence of reactance parametersXfon the eigenvalues is similar toXl, but their influence on the real parts of the eigenvalues is less thanXl.
Figure 5d describes the effect of the generator resistance parameterRaon the eigenvalues, and it can be seen thatRahas little effect on the real parts of the eigenvalues, becauseRais much smaller than the line resistance and has very little effect on the torsional modes. The effect of other resistance parameters is similar to that ofRa.
In conclusion, neither the generator reactance parameters nor the resistance parameters will affect the torsional frequencies of the shaft system. When the reactance parameters of the generator change, which makesfSUBandfTMxclose to each other, the SSR instability may occur. However, it will increase the damping of the adjacent torsional modes, which is beneficial to its stability. The resistance parameters of synchronous generator have little effect on each torsional mode and it can be ignored.
4.3. Influence of Speed Governing System Parameters
4.3.1. With or Without Speed Governing System
The system models with and without a speed governing system were established, respectively. The eigenvalue analysis method was used to calculate the eigenvalues whenkC is 0.5. The results are shown in Table 5. It can be seen from the Table that when there is a speed governing system, the real part of each eigenvalue is slightly increased, which indicates that the existence of the speed governing system reduces the system damping and results in poor system stability. The speed governing system has a significant impact on the TM0, reducing the TM0 damping and frequency.
4.3.2. Influence of Speed Governing System Parameters
The parameters of the speed governing system mainly includeKG,TSRandTSM. WhenkCis 0.5,KGchanges from 20 to 30,TSRandTSM changes from 50% to 150% of nominal value. The eigenvalue analysis method was used to calculate system eigenvalues. The results are shown in Figure 6. It can be noticed thatKG,TSRandTSMhave little effect on the imaginary part of each eigenvalue, and the real part increases slightly. With the increase ofKGand the decrease ofTSRandTSM, TMx damping is slightly reduced, which increases the risk of SSR in the system. The reason is that the smallerTSRandTSMare, the shorter the reaction time of the speed governing system is and the faster the response of the shaft system to the electrical resonance is, which is beneficial to the transmission of SSR energy.
KG,TSRandTSMhave a large influence on TM0. With the increase ofKGand the decrease ofTSRandTSM, the real part of TM0 eigenvalue increases significantly, that is, TM0 damping decreases more, which means that the risk of low frequency oscillations in the system is increased.
4.4. Influence of Excitation System Parameters
In the excitation regulator, the magnification of the excitation regulatorKAis an important parameter. TakingkCas 0.5 and changingKA from 25 to 75, the eigenvalue analysis method was used to calculate eigenvalues of the system, and the result is shown in Figure 7.
As can be seen from Figure 7, with the increase ofKA, the real part of TM3 eigenvalue decreases. That is to say, the negative damping of TM3 in the divergence mode decreases, which means that increasingKAcan reduce the instability of SSR and reduce the risk of SSR. With the increase ofKA, the real part of TM0 eigenvalue increases significantly, that is, the damping value of TM0 is obviously reduced. WhenKAis greater than 58, the real part of TM0 eigenvalue even changes from negative to positive, and the system has the risk of generating divergent low-frequency oscillations.
5. Conclusions The purpose of this paper was to study the SSR characteristics and influence factors of the series compensation transmission system. By using the eigenvalue analysis method and time domain simulation method, the eigenvalues of a series compensated transmission system were calculated, and the following conclusions can be drawn:
-
The series compensation levelkChas the greatest influence on the torsional mode damping of the system. With the increase ofkC, one or more torsional mode damping will appear negative, indicating that the system may have a single mode or multimode SSR, and the greaterkCis, the lower the torsional mode frequency is, but the change ofkCdoes not affect total damping of the system, that is, the total damping of the system is conserved.
-
The parameters of the synchronous generator will not affect torsional mode frequencies of the turbogenerator shaft, and the reactance parameters of generators have a certain influence on torsional mode damping of the system. The variation of the reactance parameters may lead to instability of the torsional mode whenfSUBandfTMxbecome close. However, the damping of adjacent torsional modes will be increased, which is beneficial to its stability. In addition, the resistance parameters of synchronous generator have little effect on the damping of each torsional mode, which can be ignored.
-
Speed governing system parametersKG,TSRandTSMhave a great influence on TM0 damping, and slightly affect other torsional modes damping. Excitation system parameterKAsignificantly affects TM0 damping, and has little effect on other torsional modes damping.
SSR Analysis Methods | Features | Advantages | Disadvantages |
---|---|---|---|
Eigenvalue analysis | It is also called state-space analysis method, which is a quantitative analysis method based on the small disturbance linearization model and obtains SSR-related information by solving eigenvalues. |
| Higher order model parameters are required for the entire system, which is difficult to analyze. |
Electromagnetic transient analysis | Using a step-by-step numerical integration method, a set of differential equations of the system are solved. The mathematical model can be linear or nonlinear. |
| Only time domain response results can be given. It is difficult to directly give SSR reasons and the mechanism of instability. |
Complex torque coefficient analysis | Frequency scanning of the mechanical and electrical complex torque coefficients of the shaft system in the subsynchronous frequency range to determine whether the system will undergo subsynchronous oscillation. |
|
|
Frequency scanning | It is an approximate linear method to calculate the equivalent impedance for a specific frequency and filter out the system conditions with potential SSR. |
|
|
Mass Block | Inertia Constant,TJ(s) | Shaft Segment | Elastic Constant, K (p.u.) |
---|---|---|---|
HP | 0.185794 | - | - |
IP | 0.311178 | HP-IP | 19.303 |
LPA | 1.717340 | IP-LPA | 34.929 |
LPB | 1.768430 | LPA-LPB | 52.038 |
GEN | 1.736990 | LPB-GEN | 70.858 |
EXC | 0.068433 | GEN-EXC | 2.822 |
Eigenvalue | Torsional Mode | Real Part (1/s) | Imaginary Part (rad/s) | Frequency (Hz) |
---|---|---|---|---|
1,2 | TM0 | −0.5073 | ±11.66 | 1.86 |
3,4 | TM1 | 0.0931 | ±100.28 | 15.96 |
5,6 | TM2 | 0.2034 | ±128.08 | 20.38 |
7,8 | TM3 | −0.1352 | ±160.34 | 25.52 |
9,10 | TM4 | −0.0404 | ±202.78 | 32.27 |
11,12 | TM5 | −0.1818 | ±298.17 | 47.46 |
Eigenvalue | Torsional Mode | KC = 0.1 | KC = 0.3 | KC = 0.5 | KC = 0.7 | KC = 0.9 |
---|---|---|---|---|---|---|
1,2 | TM0 | 0.0693 ± j8.46 | −0.0748 ± j9.31 | −0.2597 ± j10.35 | −0.5073 ± j11.66 | −0.8623 ± j13.41 |
3,4 | TM1 | −0.1487 ± j99.13 | −0.1422 ± j99.27 | −0.1106 ± j99.52 | 0.0931 ± j100.28 | 3.9947 ± j98.05 |
5,6 | TM2 | −0.6549 ± j127.02 | −0.6525 ± j127.03 | −0.6423 ± j127.07 | 0.2034 ± j128.08 | −0.6522 ± j126.92 |
7,8 | TM3 | −0.1627 ± j160.62 | −0.1479 ± j160.69 | 0.4564 ± j161.08 | −0.1351 ± j160.34 | −0.1644 ± j160.46 |
9,10 | TM4 | −0.0301 ± j203.01 | 0.3233 ± j203.43 | −0.0125 ± j202.68 | −0.0404 ± j202.78 | −0.0449 ± j202.84 |
11,12 | TM5 | −0.1819 ± j298.17 | −0.1819 ± j298.17 | −0.1819 ± j298.17 | −0.1819 ± j298.17 | −0.1819 ± j298.17 |
13,14 | SUB | −7.1191 ± j283.35 | −7.1702 ± j213.94 | −7.0882 ± j166.68 | −6.5888 ± j128.06 | −9.1422 ± j96.86 |
15,16 | SUPER | −7.5026 ± j470.47 | −7.5806 ± j539.24 | −7.6238 ± j586.55 | −7.6543 ± j624.99 | −7.6778 ± j658.22 |
17,18 | −4.6872 ± j0.6335 | −4.7382 ± j0.3856 | −4.8737 ± j0.2566 | −4.9573 ± j0.1521 | −3.4114 ± j0.5459 | |
19 | −1.8966 | −1.8446 | −1.7833 | −1.6996 | −1.5619 | |
20 | −24.7628 | −24.7842 | −24.8113 | −24.8466 | −24.8939 | |
21 | −30.8793 | −31.5042 | −32.3627 | −33.6064 | −35.5306 | |
22 | −8.5726 | −8.3123 | −7.9786 | −7.5383 | −6.9382 | |
23 | −101.8931 | −101.7953 | −101.648 | −101.4514 | −101.1882 | |
24 | −499.9582 | −499.9821 | −499.9783 | −499.9742 | −499.9713 | |
25 | −2.9453 | −3.1215 | −3.4887 | −3.4828 | −3.9244 | |
26 | −0.1417 | −0.1417 | −0.1418 | −0.1419 | −0.1419 | |
27 | −4.6223 | −4.3293 | −3.6731 | −3.5842 | −4.1051 | |
sum | −696.0893 | −696.1123 | −696.1281 | −696.0932 | −696.1024 |
Torsional Mode | With Speed Governing System | Without Speed Governing System | ||
---|---|---|---|---|
Real Part (1/s) | Imaginary Part (rad/s) | Real Part (1/s) | Imaginary Part (rad/s) | |
TM0 | −0.2597 | 10.35 | −0.3099 | 10.56 |
TM1 | −0.1818 | 298.17 | −0.1828 | 298.17 |
TM2 | −0.0125 | 202.68 | −0.0153 | 202.68 |
TM3 | 0.4564 | 161.08 | 0.4453 | 161.08 |
TM4 | −0.6423 | 127.07 | −0.6505 | 127.07 |
TM5 | −0.1106 | 99.52 | −0.1224 | 99.52 |
Author Contributions
All the authors were involved in the data collection, model constructing, software simulation, results analysis and discussion, and manuscript preparation. All authors have approved the submitted manuscript.
Funding
This work is supported by the Open Research Fund of Key Laboratory of Space Utilization, Chinese Academy of Sciences (No. LSU-2016-04-02) and the Natural Science Foundation of Beijing, China (Grant No. 3132015).
Conflicts of Interest
The authors declare no conflict of interest.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
© 2019. This work is licensed under http://creativecommons.org/licenses/by/3.0/ (the “License”). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.
Abstract
Series capacitor compensation is used to improve the utilization of existing power systems. Subsynchronous resonance (SSR) can be caused by series compensated lines, which would lead to turbogenerator shaft breakdown. A novel approach was presented in this paper to analyze the characteristics and influence factors of SSR in a series compensated transmission system. The system model of SSR, including the various modules of the electromechanical network, was established, and the eigenvalue results under 70% series compensation level were analyzed by eigenvalue analysis method for the the institute of electrical and electronics engineers (IEEE) first benchmark model (FBM). Compared with the results of the power systems computer-aided design (PSCAD) modeling and simulation, the effectiveness of eigenvalue analysis method was proven. After that, the eigenvalue analysis method was used to study, in detail, the effects of system series compensation levels, synchronous generator parameters, speed governing system parameters, and excitation system parameters on SSR characteristics. The research results show that the series compensation level has the greatest influence on the torsional mode damping of the system. The parameters of generator reactance, speed governing system, and excitation system have some effect on the torsional mode damping. The parameters of excitation system significantly affect the low-frequency oscillation damping.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer