1. Introduction
The Energy Performance of Buildings Directive (EPBD) [1] requires that all new buildings constructed in the European Union (EU) from 2021 (in the case of public utility buildings from 2019) are buildings with nearly zero energy consumption (NZEB). According to the revised EPBD [2] by 2050 we should decarbonise the building stock, which is currently responsible for about 36 % of all CO2 emissions in the EU. The Member States, including Poland, have set out the country requirements for standard NZEB [3]. These requirements include, among others, thermal insulation of buildings elements and maximum non-renewable primary energy consumption (in Poland only the part of the energy that is coming from fossil fuels is included in the calculations). Abundant research indicates how to optimize single-family residential buildings to meet the requirements [4,5] or how to renovate to NZEB standard [6,7]. Reaching the aforementioned European goals, related to the building stock by 2050, can be complicated without more ambitious solutions. Meanwhile, new research show that the future will belong to plus energy buildings. The study of Gustafsson [8] concentrates on building energy systems in the context of renovation. This is especially important when aiming towards the 100% share of the renewable system in the future. To reach the plus energy standard a combination of photovoltaics, heat pumps, balanced ventilation with heat recovery and improved building envelopes is needed [9]. Therefore, a whole design process is to be optimized from the architectural and economic perspective [10]. One of the solutions can be the use of building integrated photovoltaics [11]. Examples of already-built plus energy houses can be found e.g., in Germany [12] where the Federal Ministry of the Interior for Building and Homeland is already promoting such a standard.
The question is how feasible requirements for the plus energy building definition should be formulated in central Poland. In order to find an answer, various energy efficiency standards of the model house were analysed, including different types of heat pumps, photovoltaic and ventilation systems. For each variant the global cost was calculated over a 30-year period. The used calculation period was based on the methodology framework established by the Commission with the Delegated Act No. 244/2012. According to the regulation for residential and public buildings 30 years of calculation period should be taken into account, and for commercial, non-residential buildings at least 20 years. The minimal cost was used as an optimizing criterion. The general definition states that building is plus energy when it produces more energy from renewable energy sources, over the course of a year, than it needs for heating, ventilation, domestic hot water (DHW) and auxiliary systems [13]. According to the concept [13] generated electricity, which is not consumed in place, is sent to the electricity grid. The power grid plays the role of energy storage in such a solution. Additionally, reaching of plus energy standard is only possible for buildings with a very high energy efficiency level, what confirms the study of Melgar, Bohórquez and Márquez [14]. What precise solutions in terms of construction and systems should be used are not always clear. Taking in consideration that the aim of the research was to check what is more cost-effective; the reduction of energy demand (e.g., thanks to better insulation of building elements) or the increase of production from renewable energy sources. At one point there has to be an optimum combination of those two measures, in combination with the minimal global cost. Research results were used to define possible requirements for plus energy building in the cold climate of central Poland.
The capital Warsaw was chosen as the location of the building, representing an average climate of central Poland. The city has a humid continental climate with long cold winters and short warm summers. The average length of the heating season is 222 days with the average outdoor air temperature of 3.4 °C. Yearly in-plane irradiation is 1100 kWh/m2 [15]. For the determination of the plus energy standard a single-family building model was used. It well represents typical new single-family buildings constructed in Poland and does not include any special solutions referring to its construction or architecture.
The whole paper has following structure:
- materials and method—description of the calculation methodology, used building model and analysed variants,
- systems dimensioning—selection of air and ground source heat pumps for different building variants, selection of photovoltaic panels on a basis of total final energy consumption for heating, hot water and auxiliary systems,
- cost calculation—calculations of investment costs including construction and systems, calculation of annual costs related to energy consumption, systems replacement and maintenance,
- results and discussion—global cost comparison and selection of cost-optimal variant,
- conclusions—proposition of requirements for plus energy single-family residential buildings in central Poland.
2. Material and Method 2.1. Calculation Methodology The process of determining requirements for the plus energy building definition was divided into the following stages:
- calculation of energy performance of the house,
- systems dimensioning,
- global cost calculation.
The first stage was defining the energy performance of a single-family house used as the model building. The calculations were made for three different energy efficiency standards. Energy data were the basis for the dimensioning of building systems. Adequate heat pumps, PV systems and balanced ventilation were selected. Based on them it was possible to determine six main variants of plus energy house using either an air or ground source heat pump.
The aim of the global cost calculation was to determine the cost-optimal variant. The results depended on the energy efficiency standard and energy systems in the building. As an optimizing criterion, the minimal global cost (including investment + running costs) was used, calculated over a 30-year period. The calculations were based on the standard EN 15459-1 Energy performance of buildings, Economic evaluation procedure for energy systems in buildings, Part 1: Calculation procedures [16] and literature review [17,18]. The global cost for the 30-year period for the purpose of the study was calculated on basis of the following formula:
CG=CI+∑i=130(Ca(i)·fpv(i))−∑j=1 V30_f(j),
where:
- CI—initial investment cost including additional constructions and systems costs, EUR;
- Ca(i)—annual costs of the year i represent the sum of maintenance costs and energy costs or replacement costs paid in the year i, EUR;
- fpv(i)—present value factor;
- V30_f(j)—final value of the component j at the end of the calculation period, EUR.
The present value factor is the factor by which any annual costs are to be multiplied in order to be comparable with the initial investment at the time of installation. It was calculated for the year i with the use of the following formula:
fpv(i)=(1+s)i·(1+e)i(1+d)i,
where:
- s—annual inflation rate;
- d—discount rate;
- e—evolution of energy prices (electrical energy) over the inflation rate in the analysed period.
The annual costs of the year i represent the sum of energy consumption, systems maintenance and replacement costs paid in specific years. It was calculated with the use of the following formula:
Ca(i)=CRj,Tn+Ce+Cm
where:
- CRj,Tn—replacement costs for component or system j at time Tn and 2Tn if the calculation period is longer or equal to 2Tn;
- Tn—lifetime expectancy for a component j (or system) normally specified in years;
- Ce—cost of energy consumption for heating, ventilation, DHW and auxiliary systems;
- Cm—maintenance costs.
The final value of the component j (V30_f(j)) at the end of the calculation period was calculated if its lifespan was longer than the calculation period of 30 years. For example, if the component had to be replaced in year 30 the full replacement cost was multiplied by present value factor and subtracted from the annual costs. But if the lifespan of the component was 15 years and it was replaced for the first time in year 15 the final value of the component at the end of the calculation period will be 0 (zero). 2.2. Building Variants The calculations were made for three different building energy efficiency standards referring to envelope performance, ventilation system and energy demand:
-
WT2021—This is the term for the requirements for new buildings designed according to the building code [3] that will be built in Poland from 2021. The requirements apply to the maximum heat transfer coefficients (U-values) of building elements and the coefficient of maximum annual demand for non-renewable primary energy (QP) for heating, ventilation, cooling, domestic hot water preparation and lighting. From 2021, it will be reduced to a maximum of 70 kWh/(m² year).
-
NF40—This is the term for a low-energy house, characterized by the energy need for heating (QH) no higher than 40 kWh/(m² year). The standard was defined by the National Fund for Environmental Protection and Water Management (NFEP and WM) in Poland as part of a program supporting the energy-efficient buildings [19]. The energy demand for heating of new houses is typically about 100 kWh/(m² year).
-
NF15—This is the term for a passive house, characterized by the energy need for heating (QH) no higher than 15 kWh/(m² year). The standard was also defined by the NFEP and WM [19]. To achieve such a low energy demand, the building must be properly designed, constructed and equipped with very efficient ventilation system.
It is worth noting that the WT2021 concentrates on demand for non-renewable primary energy while NF40 and NF15 on energy demand for heating. Specific requirements for the given standards are shown later in the paper. In order to reach plus energy level systems, components have to be used which reduce the house final energy consumption and maximize renewable energy production on the site. In the scope of the research the following systems were included:
- PV—Photovoltaic solar panels were used to produce electrical energy. Depending on the situation monocrystalline or polycrystalline solar panels were applied. The surface of the roof of the house on which the panels can be installed is usually limited, e.g., to 35 m² in the case of the used model house.
-
ASHP—Air source heat pump using energy stored in ambient air. Split system consists of one unit inside and one outside the building. The heat is distributed through the surface, water central heating system and used for the heating of DHW. The ASHP type has to be appropriate to work in cold climate. The key element of such a construction is the electronically controlled compressor with EVI (enhanced vapour injection) technology [20].
-
GSHP—Ground source heat pump with vertical exchanger using energy accumulated in the ground for heating and domestic hot water preparation. The pipes run in vertical holes bored in the ground with a diameter of 10–15 cm deep at 15–200 m. The minimum distance between holes is 5 to 6 m [21,22]. Stable ground temperature at a lower depth allows for higher efficiency of the heat pump, shorter loops reduce pumping costs and the exchanger takes up less space.
The house model has been subjected to six variants differing in the energy efficiency standards and the systems. In order to reduce the energy needs for heating balanced ventilation with heat recovery was introduced in the NF40 and NF15 standards. All the variants are presented in Table 1.
The research included two different heat pump types in order to check how they influenced the results. Currently in Poland air source heat pumps are becoming very popular because they are cheaper than pumps with a ground exchanger [23]. Unfortunately, their energy efficiency is lower compared to ground source heat pumps [24], what is especially important in a cold climate of Poland. One of the research tasks was to check if the investment in higher efficiency is cost effective in the case of plus energy buildings.
2.3. Building Model and Energy Performance
A single-family building model was used to determine the requirements for plus energy standard (Figure 1). It was a two-storey, detached house without basement, with a heated, usable attic. The building has compact shape, designed on a rectangular plan. It has traditional brick construction. The heated attic was covered with a gable roof with a wooden structure. The visible lucarne was oriented towards the south. The area of the roof, oriented on the south, on which the PV panels could be installed, was limited to 35 m². The basic geometric data of the house are shown in Table 2. The used model well represents typical new single-family buildings constructed in Poland.
The 3D model of the house and the energy performance was created in software Audytor OZC (energy need calculation) version 6.8 Pro (Sankom, Warsaw, Poland). The axonometric projections can be seen in Figure 2.
The precise requirements for individual energy efficiency standard are shown in Table 3 and Table 4. The comparison concerns the maximum values of heat transfer coefficients (U-value) and linear heat loss coefficients (Ψ-value), ventilation type and efficiency, air-tightness and energy demand.
For each variant the energy need for heating was calculated with use of software Audytor OZC in accordance with ISO 13790 standard [26]. The Audytor OZC software is used to assist in the calculation of the design heating load of rooms and buildings, determination of the seasonal energy need for heating and cooling and performance of Energy Certificates for buildings and their parts. The program can also carry out moisture analysis of building elements. Design heating load was calculated in accordance with EN 12831-1 standard [27] and used for the systems dimensioning. It was assumed that the house is located in Warsaw representing a typical Polish climate. The number of heating degree days (HDD) for Warsaw is 3686 Kd. The energy need for hot water heating was calculated on basis of Polish regulation [28]. All the assumptions used for the calculations were summarized in Table 5. The energy needs for heating and DHW preparation is given in Table 6.
Change of envelope and ventilation system parameters had visible influence on energy performance. Energy need for heating and design heating load decreased with the increase of requirements. The energy need for DHW preparation was the same for all standards. In all the energy efficiency standards the parameters of inside comfort were at the same level as shown in Table 5.
3. Systems Dimensioning In order to reach the plus energy level it was necessary to properly select the buildings systems for each variant. As part of the work, heat pumps, PV panels and ventilation with heat recovery were selected. Selection of exact model made it possible to precisely determine the price and efficiency of the devices. 3.1. Heat Pumps Selection
Two types of heat pumps were chosen for each energy efficiency standard of the house—ASHP or GSHP. The ground source heat pump works with a vertical exchanger. To make the comparison more reliable (to eliminate the influence of the brand) only one supplier was selected namely the company NIBE. The design heating load of the house included the transmission and ventilation losses and was calculated in accordance with EN 12831-1 standard [27]. On the basis of the results obtained, heat pumps were selected together with all the fittings necessary for the proper functioning of the entire system. The heating capacity of the heat pumps was always higher than the design heating load. From the manufacturer’s catalogue the first device in the order was always chosen with the capacity higher than the designed one. It was assumed that heat pumps will work with low temperature (35 °C—design supply temperature), under floor, water heating.
Using the NIBE catalogue, the Standard 12 Monoblok and Standard 6 Monoblok air source heat pumps were chosen. They are designed for central and water heating, even by an outdoor temperature of –20 °C. The set included: heat pump F2040 12 kW or 6 kW, internal unit HK 200 M with hot water heater of a 180 L capacity, heat exchanger and control module SMO 20. Table 7 shows the basic parameters of the pump.
In all cases the heating capacity of the ASHP was higher than the designing heating load. In the case of NF15 it was even twice higher because the F2040 6 kW was the smallest device produced by the company. During the research process a lot of effort was made to find a suitable heat pump (with very low heating capacity) for NF15 standard. For example, Samsung offers a heat pump EHS SPLIT 4.4 kW but it is only for heating and not for hot water preparation. Daikin offers Altherma III Bluevolution with 4.3 kW but it is only suitable for average climate and not for cold climate conditions. A suitable heat pump e.g., iTec from Thermia has a capacity of 5.0 kW so is very similar to the selected type. The additional capacity was used for DHW heating which especially important during the cold winters.
According to the literature [30] the influence of over-sizing on the energy efficiency of the heat pump is smaller than influence of under-sizing in the cold climate. By over-sizing the heat pumps work more often in the on–off mode. As a result the efficiency decreases by 3%–6%. By under-sizing the heat pumps, they work more often with full speed of the compressor and the amount of energy consumed by the auxiliary electric heater increases. As a result the efficiency decreases by 3%–18%. For the ground source heat pump the dual-function NIBE F1226 device was chosen with heating capacity 12 kW or 6 kW. The pumps have integrated hot water heater of 180 L capacity. Table 8 shows the basic parameters of the devices.
In all cases the heating capacity of the GSHP was higher than the designing heating load. In case of NF15 it was even twice higher because the F2040 6 kW was the smallest device produced by the company. In regard to the ASHP seasonal space heating energy efficiency was visibly higher but the water heating energy efficiency was very similar. The technical parameters of the heat pumps were the basis for the calculation of annual final energy demand. 3.2. Photovoltaic Panels Selection
In order to properly select the peak power of the PV system it was necessary to calculate the annual final energy demand of the house and compare it with electrical energy production of the system. In order to reach the plus energy level, the final, annual energy consumption for heating, ventilation, domestic hot water and auxiliary systems should be smaller than the annual production of the PV system. The annual energy consumption in kWh in terms of final energy should be calculated as the ratio of the reference annual heating or DHW need and the total, seasonal space heating or water heating energy efficiency. The energy efficiency of building systems was evaluated based on supplier data [29,31], the Polish regulation [28] and several European reference standards: EN 15243 [32], EN 15316 [33] and EN 15316–3-1:2005 [34]. Seasonal space and water heating energy efficiency of the heat pumps was calculated on basis of data from Table 7 and Table 8 multiplied by the primary energy factor for electrical energy equal to 2.5 according the Regulation No 811/2013 [35]. The total efficiency for both heat pumps is presented in Table 9 and Table 10. The total efficiency of the heating system was calculated on basis of the following formula:
ηH,tot = ηH,g × ηH,e × ηH,d × ηH,s,
where:
- ηH,g—seasonal space heating energy efficiency;
- ηH,e—seasonal control and heat use energy efficiency;
- ηH,d—seasonal heat distribution energy efficiency;
- ηH,s—seasonal heat storage energy efficiency.
The total efficiency of the hot water system was calculated on the basis of the following formula:
ηW,tot = ηW,g × ηW,e × ηW,d × ηW,s,
where:
- ηW,g—seasonal water heating energy efficiency;
- ηW,e—seasonal efficiency of water use;
- ηW,d—seasonal hot water distribution energy efficiency;
- ηW,s—seasonal hot water storage energy efficiency.
The next stage was the calculation of annual, final energy consumption for all standards and systems. The consumption included heating, DHW and electrical energy used by auxiliary systems—control, pumps and ventilation unit (only in case of NF40 and NF15). Results are shown in Table 11.
Results clearly showed that in the case of buildings with high energy efficiency (NF40 and NF15) the energy consumption for water heating was more significant than for heating. Energy used by auxiliary systems decreased with the increase of building standard because the heating season became shorter. At the same time use of mechanical ventilation caused additional energy consumption.
In order to reach the plus energy standard, the amount of energy produced on-site had to be higher than total final energy consumption over the course of a year. For each variant PV panels were used and installed on the south roof surface. The available roof area was limited to 35 m2. In order to maximize the energy production monocrystalline panels were selected in the case of WT2021. They are more effective but also more expensive. The amount of energy produced was calculated on basis of SOLEKO data [36]. The results of the selection can be seen in Table 12.
In the case of WT2021 it was impossible to reach plus energy level, despite the use of more efficient panels. The limited roof area and high energy consumption were the main barriers. The assembly of panels on the external walls was not considered due to their lower efficiency and the risk of shading. The next step of the analysis was the calculation of investment and exploitation costs also for the WT2021 standard. Based on results presented in Table 10 the final energy consumption and production indexes were calculated (Table 13). On their basis possible requirements for a plus energy single family building were proposed.
4. Costs Calculation The WT2021 standard was adopted as the reference. The calculation was made separately for the building envelope and the systems. For the building envelope the cost increased in the case of NF40 and NF15 standards, because of thicker insulation layer, better windows, thermal bridges reduction and increase of air-tightness. System costs included heat pump (and vertical exchanger if required), PV panels and mechanical ventilation. 4.1. Construction Costs
The summary of the additional construction costs resulting from the insulation of building elements is presented in Table 14.
It was necessary to replace external doors and windows so that they met the requirements of specific NF15 standard. Because there is only small difference between WT2021 and NF40 standard no change in the cost was assumed. The prices of doors and windows 34re based on the online calculator [37]. The cost summary is presented in the Table 15.
Another increase in construction costs resulted from the need to limit heat losses through thermal bridges. These costs included, e.g., the installation of window frames in the insulation layer in the NF15 standard. In addition, it was necessary to increase the air-tightness of the building envelope. Based on our own research [38,39,40], it was assumed that both improvements will cost 815 EUR in the NF40 and 1500 EUR in the NF15.
The use of balanced ventilation with heat recovery saved on the cost of building a chimney. In relation to the WT2021 standard with natural ventilation, this saving amounted to 580 EUR for the variant NF40 and NF15. The summary of all construction cost is presented in Figure 3. The minus values represent the savings. In total the costs increased by 1010 EUR for NF40 and by 3930 EUR for NF15 in regard to WT2021.
4.2. Systems Costs
The cost of the photovoltaic system included the cost of solar panels, inverter, additional elements like cables and installation. Depending on peak power and panels type the costs were estimated based on the price list of SOLEKO company [36]. Installation of a solar panel on a roof covered with standard roofing tiles was 35 EUR for each photovoltaic panel. The total cost for each building variant is presented in Table 16.
The cost of the heating and DHW system included the cost of heat pump, hot water tank, control module, additional equipment, vertical exchanger (if required), installation and commissioning. Depending on the heating load and pump type the costs were estimated based on the price list of NIBE company [29,31]. The vertical exchanger cost was calculated based on assumed maximum feat flow of 45 W per one meter of the boreholes and the cost of 25 EUR for each meter of the drilling [31]. The total cost for each building variant is presented in Table 17. As expected, the cost depended on the heating load and the type of heat pump. The ASHPs were almost twice as cheap as GSHPs because there was no need for the vertical exchanger.
Selection of smaller heat pumps (if an appropriate type would be available) in the case of NF15 standard would have little influence on its price. In the case of the air source heat pump from Daikin the difference in price between 4.3 kW and 6.0 kW was lower than 10%. The difference in price between 5.7 kW and 7.6 kW for Vitocal 333-G of Viessmann was 5%.
The last element of the building systems was in case of NF40 and NF15 the balance ventilation with heat recovery. The cost was calculated on a basis of an offer from PRO-VENT [41] company. It included installation of ventilation ducts, ventilation unit with heat recovery, regulation and commissioning of the entire system. NF40 and NF15 standards use the same type of ventilation unit, therefore the cost of EUR 5325for both variants is identical. The summary of all system costs for all standards is shown in Figure 4.
The total systems cost did not change much with the change of the building energy efficiency standard. Although the heat source capacity can be smaller the additional cost of balanced ventilation appeared. Higher differences could be seen in regard to the heat pump type. Use of ASHP reduced the costs from 23% to 33%. A full assessment of investment costs was possible after adding extra construction costs (Figure 5).
Reaching the plus energy standard would be cheapest in case of WT2021 with the ASHP but the amount of energy produced by the PV panels was too small (lower than consumption). Because of that, the NF40 standard with air source heat pump represented the lowest investment cost. Changing to GSHP increased the cost by about 28% and to NF15 by about 9%. The share of additional construction cost was minor because the system cost dominates. 4.3. Replacement and Maintenance Costs
The analysis included the replacement costs of system components during the explanation of the building. It was a periodic cost corresponding to the lifespan of the component. The used lifetime expectancies are shown in Table 18 and based on standard EN 15459-1 [16]. The calculation concentrated mainly on the energy systems of the house. Final value of system components at the end of calculation period was given as a percentage of replacement cost. For example, in a case of heat pumps they would have to be replaced in year 30 which was at the same time calculation period. Therefore, the final value was in this case 100%.
The annual maintenance costs were calculated as percentage of the investment costs related to the system component based on standard EN 15459-1 [16]. For the photovoltaic system and vertical exchanger it was 1% while for heat pumps and balanced ventilation 2%. The operation cost was calculated on a basis of final energy consumption of auxiliary systems and the ventilation unit.
4.4. Annual Costs Related to Energy Consumption
Annuals costs related to energy consumption included heating, DHW and systems operation. Theoretically they should have been zero because the house was designed at plus energy standard. In reality only part of the energy produced by PV panels would be used on site. According to measurements made in Poland [42] around 25% of the consumption is covered by the solar electrical energy. The rest has to be supplied to the grid in the case of buildings without energy storage. Owners of solar power plants with a capacity of up to 10 kWp for each 1 kWh delivered to the grid can get back 0.8 kWh for free, which results from Polish regulations [43]. Such a solution was included in the analysis and was the basis for calculations of electrical energy send back to the grid and used from the grid. The price of 1 kWh was 0.15 EUR. Precise data for each variant are presented in Table 19.
Results showed that even for variants that met the plus energy standard (NF40 and NF15) annual cost related to energy consumption was higher than zero. It was actually the cost of storing the produced electrical energy in the grid. 4.5. Global Cost Calculation For all the house and system variants the global cost was calculated. It was a sum of the present value of all annual costs (with reference to starting year) including investment costs. The annual costs included systems replacement and maintenance, as well as energy consumption. Final value of component or system at the end of the calculation period was considered in the analysis. The following financial data were used:
- duration of the calculation: 30 years
- inflation rate: 2%
- real interest rate: 3%
- evolution of energy prices: 2% (electricity).
The values were based on the data from Polish Office of Competition and Consumer Protection [44] constant during the analysed period. Results of global cost calculation for all variants were shown in Table 20 and in Figure 6.
5. Results and Discussion After analysing all six variants differing in thermal insulation of building elements, the solution of the ventilation system and technical systems, it was possible to assess them from the point of view of economic viability. The global cost values obtained proved that the NF40 (41,732 EUR) and NF15 (42,048 EUR) variants using the air source heat pump were the most favourable. The difference between them was lower than 1%. Another option with a relatively low global cost was a building in the WT2021 standard also with ASHP (global cost higher by 5% in regard to NF40 ASHP). It should be noted, however, that it did not meet the plus energy building criterion. A ground source heat pump with vertical exchanger turned out to be more expensive in each variant. The reason is mainly higher investment costs associated with the need of the heat exchanger (global cost higher by 24%–27% depending on the variant). Investing more money in a higher energy efficiency standard—NF15, proved not entirely justified. Low demand for energy and heating load does not significantly affect the cost of systems. The selected heat pumps were oversized, because in the catalogues of the supplier company no smaller devices were available. From this perspective cost of heating system is the same in case of NF40 and NF15. Also, the cost of PV systems is only slightly different from the cost for the NF40 standard. Increase of energy efficiency of house had visible influence on energy cost in the calculation period. Meeting the plus energy standard caused the share of energy costs in global costs to range from 6%–5% for NF40 to 4%–2% for NF15. In the case of WT2021 it was from 19% to 9%. The replacement and maintenance cost played very important roles in the global cost. Depending on the variant it was between 42% and 47%. It clearly showed that energy systems of the buildings are becoming more important that its energy efficiency. Correct selection of them is crucial from the economic and energy efficiency point of view. Investment costs had the smallest share in case of WT2021 variant. 6. Conclusions The main objective of this paper was to propose possible requirements for plus energy building definition in the heating dominated climate of central Poland. The question was what is more cost-effective: reduction of energy demand or increase of production from renewable energy sources. The obtained analysis allowed the formulation of the following conclusions:
-
It can be definitely stated that the economic sense of using renewable heat sources leaves no doubt, bearing in mind that the efficiency of these devices increases year by year (thanks to new solutions [45]), what causes higher profitability of this type of system. Moreover, the low-energy standards NF40 and NF15 allow for achieving the plus energy level in cold climate of central Poland, which was proved by the study.
- The research has shown that reaching the plus energy standard will be not possible in the case of WT2021—houses meeting only specific requirements of the building code for year 2021. The high energy consumption cannot be covered by on-site energy production.
-
The global cost of the plus energy house (in standard NF40 and NF15) depended mainly on the system type (ASHP or GSHP) and only slightly on energy consumption. The maintenance, replacement and investment cost related with the energy systems had the biggest share in global cost. It clearly showed that proper selection and dimensioning of the systems is the key to plus energy standard. From the economic point of view the use of ASHP seemed to be more effective despite lower efficiency in a cold climate. Another important issue was the storage and utilization of energy produced on site [46].
-
In the analysed model of the house the available roof area was limited to 35 m2. Similar limitation will occur in the majority of single-family buildings in Poland. By referring the maximum energy production to the heated area—6600 kWh/year to 129 m2 a coefficient of 51.2 kWh/(m2 year) can be calculated. To reach a plus energy standard final energy consumption (Table 13), for heating, ventilation, DHW and auxiliary systems, has to lower than this coefficient. The final energy consumption index was 40.3 kWh/(m2 year) for NF40-ASHP, 30.9 kWh/(m2 year) for NF15-ASHP, 37.1 kWh/(m2 year) for NF40-GSHP and 29.5 kWh/(m2 year) for NF15-ASHP. In each case it was lower than maximum energy production coefficient.
The formulated conclusions can be used as a basis for proposing possible requirements for plus energy building standards in central Poland. From the three different energy types—energy need, final energy and primary energy, the final energy taking into consideration the efficiencies of the systems seemed to be most suitable. The potential indicators of the definition should be the index of final (delivered) energy demand QF and the index of on-site energy production QF,P. Based on research the proposed requirements for plus energy single-family residential buildings are as follows:
- The final (delivered) energy demand (including heating, ventilation, DHW and auxiliary systems) QF < 45 kWh/(m² year); and
- The on-site energy production QF,P > 45 kWh/(m² year).
The proposed values are in the middle between maximum energy production and maximum energy consumption. Both requirements should refer to the electrical energy and not to the heat.
Energy Efficiency Standard | Systems | Ventilation Type |
---|---|---|
WT2021 | ASHP + PV | Natural ventilation |
GSHP + PV | ||
NF40 | ASHP + PV | Balanced ventilation with heat recovery |
GSHP + PV | ||
NF15 | ASHP + PV | Balanced ventilation with heat recovery |
GSHP + PV |
Parameter | Value | Units |
---|---|---|
Heated area | 129.0 | m2 |
Heated volume | 307.1 | m3 |
Gross covered area | 91.5 | m2 |
Shape factor | 0.67 | m−1 |
Units | Maximum U-values of Building Elements | WT2021 | NF40 | NF15 |
---|---|---|---|---|
W/(m2 K) | External walls | 0.20 | 0.15 | 0.10 |
Roofs, flat roofs and floors under unheated attics | 0.15 | 0.12 | 0.10 | |
Floors over unheated basements and closed spaces, floors on the ground | 0.30 | 0.20 | 0.12 | |
External and garage doors | 1.3 | 1.3 | 0.8 | |
Windows, balcony doors and transparent facades | 0.90 | 1.0 | 0.8 |
Units | Requirement | WT2021 | NF40 | NF15 |
---|---|---|---|---|
Maximum Ψ-values of thermal bridges | ||||
W/(m K) | Balconies | around 0.70 | 0.20 | 0.01 |
Others places, e.g., window opening | around 0.70 | 0.10 | 0.01 | |
% | Ventilation type and efficiency | natural, no requirements | balanced ventilation with heat recovery, ≥85 | balanced ventilation with heat recovery, ≥90 |
1/h | Envelope air-tightness in n50 | 3.0 | 1.0 | 0.6 |
kWh/(m² year) | Non-renewable primary energy demand | QP ≤ 70 | no | no |
kWh/(m² year) | Energy need for heating | no | QH ≤ 40 | QH ≤ 15 |
Assumption | Value | Units |
---|---|---|
Design outdoor air temperature | −20.0 | °C |
Average yearly outdoor air temperature | 7.6 | °C |
Design indoor air temperature—rooms | 20.0 | °C |
Design indoor air temperature—bathrooms | 24.0 | °C |
Design hot water temperature | 55.0 | °C |
Design hot water consumption | 180.0 | l/day |
Air exchange rate | 0.60 | H−1 |
Energy Efficiency Standard | Energy Need for Heating, QH | Energy Need for DHW Preparation, QDHW | Design Heating Load, Φ |
---|---|---|---|
kWh/(m² year) | kWh/(m² year) | kW | |
WT2021 | 99.4 | 25.0 | 8.7 |
NF40 | 35.1 | 4.6 | |
NF15 | 11.8 | 3.1 |
Technical Parameter | Energy Efficiency Standard | |
---|---|---|
WT2021 | NF40 and NF15 | |
Heat pump model | F2040 12 kW | F2040 6 kW |
Heating capacity range | 3.5–12 kW | 2.0–6 kW |
Electric power | 1.79 kW | 0.55 kW |
Nominal heating capacity | 6.91 kW | 2.32 kW |
Seasonal space heating energy efficiency, cold climate, 35 °C | 142% | 134% |
Water heating energy efficiency, cold climate | 88% | 89% |
Min. working temperature | −20 °C | −20 °C |
Max. DHW temperature | 58 °C | 58 °C |
Sound pressure level | 43 dB | 35 dB |
Technical Parameter | Energy Efficiency Standard | |
---|---|---|
WT2021 | NF40 and NF15 | |
Heat pump model | F1226 12 kW | F1226 6 kW |
Electric power | 2.68 kW | 1.31 kW |
Nominal heating capacity | 11.52 kW | 5.49 kW |
Seasonal space heating energy efficiency, cold climate, 35 °C | 177% | 170% |
Water heating energy efficiency, cold climate | 89% | 91% |
Max. DHW temperature | 63 °C | 63 °C |
Sound pressure level | 29 dB | 28 dB |
System Type | Seasonal Energy Efficiency | WT2021 | NF40 and NF15 |
---|---|---|---|
Floor heating | heat pump | 3.55 | 3.35 |
control and heat use | 0.89 | ||
heat distribution | 0.96 | ||
heat storage | 0.95 | ||
total, seasonal | 2.88 | 2.72 | |
DHW heating | heat pump | 2.20 | 2.23 |
DHW use | 1.0 | ||
DHW distribution | 0.60 | ||
DHW storage | 0.85 | ||
total, seasonal | 1.12 | 1.13 |
System Type | Seasonal Energy Efficiency | WT2021 | NF40 and NF15 |
---|---|---|---|
Floor heating | heat pump | 4.43 | 4.25 |
control and heat use | 0.89 | ||
heat distribution | 0.96 | ||
heat storage | 0.95 | ||
total, seasonal | 3.59 | 3.45 | |
DHW heating | heat pump | 2.23 | 2.28 |
DHW use | 1.0 | ||
DHW distribution | 0.60 | ||
DHW storage | 0.85 | ||
total, seasonal | 1.12 | 1.13 |
Energy Efficiency Standard | Heat Pump Type | Final Energy Consumption for Heating, QF,H | Final Energy Consumption for DHW, QF,DHW | Final Energy Consumption Auxiliary Systems | Final Energy Consumption Ventilation Unit | Total Final Energy Consumption, QF |
---|---|---|---|---|---|---|
kWh/year | kWh/year | kWh/year | kWh/year | kWh/year | ||
WT2021 | ASHP | 4450 | 2827 | 503 | - | 7827 |
NF40 | 1665 | 2842 | 400 | 296 | 5203 | |
NF15 | 560 | 2842 | 284 | 296 | 3982 | |
WT2021 | GSHP | 3570 | 2842 | 503 | - | 6915 |
NF40 | 1313 | 2780 | 400 | 296 | 4788 | |
NF15 | 441 | 2780 | 284 | 296 | 3801 |
Energy Efficiency Standard | Heat Pump Type | Total Final Energy Consumption, QF | Peak Load of PV System | Estimated Electrical Energy Production | Area of the PV Panels | Number of PV Panels |
---|---|---|---|---|---|---|
kWh/year | kWp | kWh/year | m2 | - | ||
WT2021 | ASHP | 7827 | 6.30 | 6600 | 34 | 20 |
NF40 | 5203 | 5.13 | 5400 | 31 | 18 | |
NF15 | 3982 | 3.99 | 4200 | 24 | 14 | |
WT2021 | GSHP | 6915 | 6.30 | 6600 | 34 | 20 |
NF40 | 4788 | 4.56 | 4800 | 28 | 16 | |
NF15 | 3801 | 3.99 | 4200 | 24 | 14 |
Energy Efficiency Standard | Heat Pump Type | Index of Final Energy Consumption | Index of Electrical Energy Production |
---|---|---|---|
kWh/(m2 year) | kWh/(m2 year) | ||
WT2021 | ASHP | 60.7 | 51.2 |
NF40 | 40.3 | 41.9 | |
NF15 | 30.9 | 32.6 | |
WT2021 | GSHP | 53.6 | 51.2 |
NF40 | 37.1 | 37.2 | |
NF15 | 29.5 | 32.6 |
Building Element/Insulation Material | Reference Thickness of the Insulation WT2021 | Additional Layer on Insulation NF40 | Additional Layer on Insulation NF15 | Additional Cost of Insulation NF40 | Additional Cost of Insulation NF40 |
---|---|---|---|---|---|
cm | cm | cm | EUR | EUR | |
External walls/styrofoam | 20 | +1 | +15 | 71 | 967 |
Floor on ground/mineral wool | 10 | +6 | +20 | 192 | 518 |
Floor under unheated attic/mineral wool | 30 | +5 | +10 | 111 | 222 |
Flat roof/mineral wool | 30 | +5 | +10 | 25 | 51 |
Roof/mineral wool | 30 | +8 | +16 | 376 | 693 |
Total cost | 775 | 2451 |
Building Rlement | Reference Thickness U-value WT2021 | U-value NF40 | U-value NF15 | Additional Cost NF40 | Additional Cost NF40 |
---|---|---|---|---|---|
W/(m2∙K) | W/(m2∙K) | W/(m2∙K) | EUR | EUR | |
External doors | 0.90 | 1.0 | 0.80 | 0 | 186 |
External windows | 1.30 | 1.30 | 0.80 | 0 | 373 |
Total cost | 0 | 559 |
Energy Efficiency Standard | Heat Pump Type | Peak Load of PV System | Number of PV Panels | Inverter Cost | PV Panels and Equipment Cost | Installation Cost | Total Cost |
---|---|---|---|---|---|---|---|
kWp | - | EUR | - | EUR | EUR | ||
WT2021 | ASHP | 6.30 | 20 | 1510 | 5350 | 700 | 7560 |
NF40 | 5.13 | 18 | 1479 | 4101 | 630 | 6210 | |
NF15 | 3.99 | 14 | 1260 | 3390 | 490 | 5140 | |
WT2021 | GSHP | 6.30 | 20 | 1510 | 5350 | 700 | 7560 |
NF40 | 4.56 | 16 | 1390 | 3720 | 560 | 5670 | |
NF15 | 3.99 | 14 | 1260 | 3390 | 490 | 5140 |
Energy Efficiency Standard | Heat Pump Type | Heat Pump Model | Heat Pump Cost | Equipment Cost | Vertical Exchanger Cost | Installation Cost | Total Cost |
---|---|---|---|---|---|---|---|
EUR | EUR | EUR | EUR | EUR | |||
WT2021 | ASHP | F2040 12 kW | 7150 | 1840 | - | 535 | 9525 |
NF40 | F2040 6 kW | 4860 | 1840 | - | 535 | 7235 | |
NF15 | |||||||
WT2021 | GSHP | F1226 12 kW | 8730 | 1750 | 6670 | 720 | 17,870 |
NF40 | F1226 6 kW | 7440 | 1750 | 3330 | 720 | 13,240 | |
NF15 |
System Component | Investment Cost | Lifespan 5 Years | Lifespan 10 Years | Lifespan 15 Years | Lifespan 20 Years | Lifespan 25 Years | Lifespan 30 Years |
---|---|---|---|---|---|---|---|
EUR | EUR | EUR | EUR | EUR | EUR | EUR | |
PV system 6.3 kWp | 7560 | 7560 | |||||
PV system 5.13 kWp | 6210 | 6210 | |||||
PV system 4.56 kWp | 5670 | 5670 | |||||
PV system 3.99 kWp | 4140 | 4140 | |||||
ASHP F2040 12 kW | 9525 | 9525 | 9525 | ||||
ASHP F2040 6 kW | 7235 | 7235 | 7235 | ||||
GSHP F1226 12 kW | 11,200 | 11,200 | 11,200 | ||||
GSHPF1226 6 kW | 9910 | 9910 | 9910 | ||||
Vertical exchanger 12 kW | 6670 | 6670 | |||||
Vertical exchanger 6 kW | 3330 | 3330 | |||||
Balance ventilation | 5325 | 5325 | |||||
Final value of the component at the end of period—30 years | 0% | 50% | 100% |
Energy Efficiency Standard | Heat Pump Type | Total Final Energy Consumption QF | Estimated Electrical Energy Production PV | Estimated On-Site Consumption | Energy Sent Back to the Grid | Paid Energy from the Grid | Annual Cost Related to Energy Used from the Grid |
---|---|---|---|---|---|---|---|
kWh/year | kWh/year | kWh/year | kWh/year | kWh/year | EUR/year | ||
WT2021 | ASHP | 7827 | 6600 | 1957 | 4643 | 2156 | 323 |
NF40 | 5203 | 5400 | 1301 | 4099 | 623 | 93 | |
NF15 | 3982 | 4200 | 996 | 3205 | 423 | 63 | |
WT2021 | GSHP | 6915 | 6600 | 1729 | 4871 | 1289 | 193 |
NF40 | 4788 | 4800 | 1197 | 3603 | 709 | 106 | |
NF15 | 3801 | 4200 | 950 | 3250 | 251 | 38 |
Costs | Type | Present Value Factor | WT2021 | NF40 | NF15 | |||
---|---|---|---|---|---|---|---|---|
ASHP | GSHP | ASHP | GSHP | ASHP | GSHP | |||
- | EUR | EUR | EUR | EUR | EUR | EUR | ||
Investment | PV | 1.0 | 7560 | 7560 | 6210 | 5670 | 5140 | 5140 |
heat pump | 1.0 | 9525 | 11,200 | 7235 | 9910 | 7235 | 9910 | |
vertical exchanger | 1.0 | 6670 | 3330 | 3330 | ||||
balanced ventilation | 1.0 | 5325 | 5325 | 5325 | 5325 | |||
construction | 1.0 | 1010 | 1010 | 3930 | 3930 | |||
Replacement | lifespan 15 years | 0.864 | 9525 | 11,200 | 7235 | 9910 | 7235 | 9910 |
lifespan 20 years | 0.823 | 7560 | 7560 | 11,535 | 10,995 | 10,465 | 10,465 | |
lifespan 30 years | 0.746 | 9525 | 17,870 | 7235 | 13,240 | 7235 | 13,240 | |
final value | 0.746 | 13,305 | 21,650 | 13,003 | 18,738 | 12,468 | 18,473 | |
Maintenance | all systems | 25.882 * | 266 | 366 | 313 | 395 | 303 | 389 |
Energy | all systems | 25.882 * | 323 | 193 | 93 | 106 | 63 | 38 |
Global cost | 43,959 | 52,980 | 41,732 | 51,708 | 42,048 | 51,963 |
* in a case of Maintenance and Energy sum of present value factors for the whole calculation period was presented in Table 20.
Funding
This research was funded by Warsaw University of Technology, Faculty of Civil Engineering as part of statutory work.
Acknowledgments
I gratefully thank Wioleta Krupa for the technical support.
Conflicts of Interest
The author declares no conflict of interest.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
© 2019. This work is licensed under http://creativecommons.org/licenses/by/3.0/ (the “License”). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.
Abstract
The main objective of this article is to propose possible requirements for cost-optimal plus energy building in a cold, heating dominated climate. The open question is what is more cost-effective: reduction of energy demand or increase of production from renewable energy sources. The target of the research was to check which solution has the lowest investment and maintenance costs. The analysis was made for a single-family house located in central Poland, including three different energy standards: WT2021 with energy need for heating ≤100 kWh/(m² year), NF40 with energy need for heating ≤40 kWh/(m² year) and NF15 with energy need for heating ≤15 kWh/(m² year)). Air and ground source heat pumps were used as a heat source and a photovoltaic system for the production of the electrical energy. For each case the investment and running costs were calculated very precisely, taking into account heating, ventilation, domestic hot water and auxiliary systems. Global cost for a 30-year period showed that house variants with air source heat pumps are more cost effective. The investment, replacement and maintenance cost related with energy systems have the biggest share in the global cost. Reaching the plus energy standard was possible only in the case of low-energy standard NF40 and NF15. Based on this research the proposed requirements for plus energy single-family residential buildings in central Poland are the following: the final (delivered) electrical energy demand (including heating, ventilation, domestic hot water and auxiliary systems) <45 kWh/(m² year) and the on-site electrical energy production >45 kWh/(m² year).
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer