Full Text

Turn on search term navigation

© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.

Abstract

The impact of ventilation efficiency on radon (222Rn) and carbon dioxide (CO2) concentrations in the indoor air of a residential building was studied by applying transient data analysis within the CONTAM 3.4 program. Continuous measurements of 222Rn and CO2 concentrations, together with basic meteorological parameters, were carried out in an apartment (floor area about 27 m2) located in Ljubljana, Slovenia. Throughout the experiment (October 3–15), frequent ventilation (several times per day), poor ventilation (once to twice per day) and no ventilation scenarios were applied, and the exact ventilation and occupancy schedule were recorded. Based on the measurements, a transient simulation of 222Rn and CO2 concentrations was performed for six sets of scenarios, where the design ventilation rate (DVR) varied based on the ventilation requirements and recommendations. On the days of frequent ventilation, a moderate correlation between the measured and simulated concentrations (r = 0.62 for 222Rn, r = 0.55 for CO2) was found. The results of the simulation indicated the following optimal DVRs: (i) 36.6 m3 h−1 (0.5 air changes per hour, ACH) to ensure a CO2 concentration below 1000 ppm and a 222Rn concentration below 100 Bq m−3; and (ii) 46.9 m3 h−1 (0.7 ACH) to ensure a CO2 concentration below 800 ppm. These levels are the most compatible with the 5C_Cat I (category I of indoor environmental quality, defined by EN 16798-1:2019) scenario, which resulted in concentrations of 656 ± 121 ppm for CO2 and 57 ± 13 Bq m−3 for 222Rn. The approach presented is applicable to various types of residential buildings with high overcrowding rates, where a sufficient amount of air volume to achieve category I indoor environmental quality has to be provided. Lower CO2 and 222Rn concentrations indoors minimise health risk, which is especially important for protecting sensitive and fragile occupants.

Details

Title
Analysis of Ventilation Efficiency as Simultaneous Control of Radon and Carbon Dioxide Levels in Indoor Air Applying Transient Modelling
Author
Dovjak, Mateja 1   VIAFID ORCID Logo  ; Vene, Ožbej 1 ; Vaupotič, Janja 2 

 Buildings and Constructional Complexes, Faculty of Civil and Geodetic Engineering, University of Ljubljana, 1000 Ljubljana, Slovenia; [email protected] 
 Department of Environmental Sciences, Jožef Stefan Institute, 1000 Ljubljana, Slovenia; [email protected] 
First page
2125
Publication year
2022
Publication date
2022
Publisher
MDPI AG
ISSN
1661-7827
e-ISSN
1660-4601
Source type
Scholarly Journal
Language of publication
English
ProQuest document ID
2632959374
Copyright
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.