Full Text

Turn on search term navigation

© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.

Abstract

In recent years, our country’s transmission lines have often been in danger due to geological disasters such as landslides when passing through fragile geological environments, which has brought great challenges and risks to the operation and maintenance of transmission lines. In order to understand the impact of transmission line towers on tower foundation slopes under heavy rainfall conditions, the influence of towers at different locations, rainfall intensities, and slopes on slope stability was analyzed by using Geo-Studio finite element analysis software. The results show that the slope has an important influence on the selection of the reasonable position of the tower. When the tower is located at the lower part of the slope, the safety factor of the slope is the highest. The safety factor of the slope is also reduced, and eventually the slope will be unstable and destroyed; the stability coefficient of the slope in the natural state is 1.221, which is in a stable state. Slopes are prone to overall sliding, with the spoil and overburden as the sliding body and the rock–soil contact surface as the sliding surface. This result provides a scientific basis for further understanding the influence mechanism of the slope angle at the location of the tower pole on this type of landslide under rainfall conditions. Further research can use the results of this paper as a benchmark to carry out corresponding experimental analysis and verification work.

Details

Title
Stability Analysis of a Transmission Line Tower and Slope under Heavy Rainfall
Author
Wu, Zigui 1 ; Huang, Chuansheng 2 ; Shuren Hao 2 ; Li, Junyi 2 ; Li, Miao 2 ; Zhang, Tongyuan 1 

 State Grid Ji’an Electric Power Supply Company, Qingyuan District, Ji’an 250000, China; [email protected] (Z.W.); [email protected] (T.Z.) 
 School of Civil and Architectural Engineering, East China University of Technology, Nanchang 330013, China; [email protected] (C.H.); [email protected] (J.L.); [email protected] (L.M.) 
First page
3654
Publication year
2023
Publication date
2023
Publisher
MDPI AG
e-ISSN
20734441
Source type
Scholarly Journal
Language of publication
English
ProQuest document ID
2882851731
Copyright
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.