© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.

Abstract

Oil lubricates the contact between the orbiting and stationary scroll in the refrigerant scroll compressor, while the sealing between the scrolls is achieved through the refrigerant vapour pressure in the sealed back pressure chamber. The back pressure should be adjusted using the refrigerant oil two-phase flow from the oil separator at the compressor discharge to the back pressure chamber and the refrigerant oil flow from the back pressure chamber to the compressor suction side. Both of the flows are conducted through connecting tubes with corresponding high-pressure and low-pressure nozzles with small diameters. Models for predicting the refrigerant oil critical and subcritical flows through the nozzles were developed and applied in enable the prediction of the back pressure. The models are original, because the slip between the oil and the refrigerant as well as the refrigerant solubility in the oil are taken into account. The critical flow model is validated against the experimental data that are available in the literature. The back pressure is predicted by equating the mass flow rates of refrigerant and oil two-phase mixtures through the high- and low-pressure nozzles. The results show that the critical flow takes place through the high-pressure nozzle, while the subcritical flow through the low-pressure nozzle can also exist in cases with a small pressure difference between the back pressure chamber and the compressor suction side. The refrigerant solubility in the oil has a small influence on the critical and subcritical refrigerant oil mixture mass flow rates, while the influence on the back pressure is more pronounced.

Details

Title
Numerical Prediction of Refrigerant Oil Two-Phase Flow from Scroll Compressor Discharge to the Suction Side via Back Pressure Chamber
Author
Stevanovic, Vladimir D 1   VIAFID ORCID Logo  ; Petrovic, Milan M 1   VIAFID ORCID Logo  ; Cucuz, Stojan 2 ; Milivojevic, Sanja 1   VIAFID ORCID Logo  ; Ilic, Milica 3 

 Faculty of Mechanical Engineering, University of Belgrade, Kraljice Marije 16, 11120 Belgrade, Serbia; [email protected] (M.M.P.); [email protected] (S.M.) 
 Pierburg GmbH, Alfred-Pierburg-Straße 1, 41460 Neuss, Germany; [email protected] 
 Innovation Center, Faculty of Mechanical Engineering, University of Belgrade, Kraljice Marije 16, 11120 Belgrade, Serbia; [email protected] 
First page
6
Publication year
2024
Publication date
2024
Publisher
MDPI AG
e-ISSN
22279717
Source type
Scholarly Journal
Language of publication
English
ProQuest document ID
2918795964
Copyright
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.