1. Introduction
The increasing demands for sustainable, clean, and environmentally friendly energy call for distributed renewable energy resources to frequently be used to support electricity demand. In an electric system, the critical safety-related loads require extremely reliable and high-quality power to function efficiently. Uninterruptible Power Supplies (UPSs) play a key role to provide a continuous power supply and protection against interruptions. When a power outage takes place, a UPS must deliver an emergency backup power to a load and prevent damages. Typically, an ideal UPS provides unity power factor, low Total Harmonic Distortion (THD) sinusoidal, high efficiency, low cost, high reliability, electric isolation, and low transients response time during the transition from grid mode to backup mode and vice versa. Besides, the most important task of UPS is to maintain the pure sinusoidal output voltage with low THD under linear and distorted load conditions. According to the standards of Institute of Electrical and Electronics Engineers (IEEE) 519–1992, the maximum THD of the output voltage in the UPS system should be less than 5% in common applications such as households’ appliances and offices. Similarly, for sensitive applications like safety devices, and airport apparatus, the THD should be less than 3%. The configuration of the UPS system is mainly categorized as off-line or line-preferred, on-line or inverter-preferred and line-interactive UPS system [1,2].
The configuration of a typical off-line UPS system is shown in Figure 1. It usually consists of a static transfer switch, AC/DC rectifier/charger, DC/AC inverter, DC link interface, and a battery pack. The static switch connects the load to the AC grid and the battery pack charges through AC/DC rectifier/charger under normal power condition. When the grid fails, an abnormal power condition occurs, the static switch disconnects the load from the grid and the DC/AC inverter regulates power from the battery pack to the load for the period till the utility grid is back again. This topology offers some advantages such as high efficiency, simple design, passive line conditioning, cheaper, and small size. However, the major disadvantages associated with this configuration are slow transition response from the AC grid to the backup mode, lack of isolation between the load and AC line, and no output voltage regulation.
Likewise, the off-line UPS system, the on-line UPS system is the popular and most used configuration. It consists of an AC/DC rectifier charger, static transfer switch (bypass), a battery pack and a DC/AC inverter. The block diagram of the classical on-line UPS system is shown in Figure 2. In this configuration, the power continuously provides to the load through the rectifier charger and inverter under both normal and abnormal AC grid power conditions. During normal operation the battery pack charges while in case of AC grid power outage, the battery pack discharges and supply full power to the load without utilizing the static switch. The inverter is connected in series with the load. Hence, during the transition from normal mode to the backup mode, the transfer time is zero. In this configuration, the inverter is the main powering path for the load instead of the AC grid. This topology provides advantages such as good powering conditioning, load protection, high power rating, and accurate power regulation for the load. The main drawbacks associated with this topology include low power factor, high cost, low efficiency because of the double stages of power conversion, and large size.
The next topology is the line-interactive UPS system. The components include the static transfer switch, a bidirectional converter, a series inductor, and a battery pack. Technically, this UPS system can work in either mode as standby UPS and as an on-line UPS (series configuration). The series inductor is not necessary for standby line-interactive UPS system. However, in order to enhance both the voltage regulation and power factor of the load, most of the line-interactive UPS system operate on-line.
The classical configuration is shown in Figure 3. While under a normal mode of operation, the bidirectional converter charges the battery pack and the AC grid provides power to the load. In the case of AC grid failure, the static transfer switch isolates the load from the AC grid and the power to the load provides through the bidirectional converter. The main benefits of this configuration are a simple design, more reliable, high efficiency, small size, good harmonics suppression for the input current, and cheaper. The major drawback is that it does not offer any voltage regulation of the load during normal condition.
The UPS system is mainly composed of a voltage-source inverter (VSI) and an output LC filter. Generally, the UPS system performance is influenced by the output filters of the three-phase inverter which are tuned to remove fixed harmonic frequency components. Moreover, the majority of loads supply by UPS systems are unbalanced and/or nonlinear loads. Nonlinear currents drawn by unbalanced and nonlinear loads distort the output voltage of UPS system which leads to high current flow, excessive losses, heating, and malfunctioning of the critical loads. Therefore, the designing of a high-quality three-phase inverter for UPS applications are necessary in order to achieve a pure sinusoidal voltage with low THD and fast transient response during load step variations. Considering the aforementioned issues, many advanced control strategies for UPS systems are proposed in the literature to address the voltage quality enhancement. In [3,4], conventional multi-feedback loop hybrid proportional-integral-derivative (PID) control strategies have been proposed. Both the schemes provide a very good dynamic performance and simple implementation. However, as neither the inductor current nor the load current is considered, if any abnormality occurs on the load side, these schemes cannot guarantee the safe and stable operation of the system. Regarding the three-phase UPS system, the Proportional Resonant (PR) controller in the stationary reference frame has been used to supply nonlinear and unbalanced loads in [5]. This controller reduces THD of the output voltage, eliminate steady-state error, and fast dynamic response. However, in order to attenuate the lower order harmonics, the output filter inductance (L, LC, LCL etc.) values are very large which increases the size and cost of the system.
Nowadays, nonlinear control techniques have gained considerable attention from researchers because these techniques offer some advantages like robustness, less sensitive to external disturbances, and fast dynamic performance. In [6], deadbeat control has been proposed in order to enhance the closed-loop performance of the pulse width modulation (PWM) inverter. Deadbeat control technique provides some advantages such as fast dynamic response, and good performance under a linear load. However, this controller is highly sensitive to parameters changes, model uncertainties, measurement noise, and sometimes to switching frequency. In order to overcome the aforementioned issues, Observer-based deadbeat controllers have been proposed in [7,8]. Though, there is a trade-off between the controller stability margin and the closed-loop performance. In [9,10], the Repetitive controller (RC) for UPS inverters are investigated so as to compensate the unbalance and harmonic distortion. This controller provides a good regulation for distorted loads, eliminate a periodical tracking error and excellent harmonics (both odd and even components) rejection capability. However, the dynamic response is quite slow, thus RC is usually escorted by robust controllers for enhanced dynamics response time of the controller. Additionally, high memory usage which imposes a high computational burden is an extra drawback in the RC controller. Iterative Learning Control (ILC) for UPS inverters is suggested in [11]. This technique is capable of achieving high performance. However, the design is complex and also the switching frequency is very high, which result in huge switching losses. The Model Predictive Control (MPC) techniques are proposed in [12,13,14,15,16] which provide a simple structure and good dynamic performance. A cost function is obtained to predict the next switching state. Also, MPC has the ability to manipulate different constraints like switching frequency minimization. However, the predictive control requires accurate system parameters to reach the desired performance. Further, it is difficult to implement the MPC technique as the cost function calculation compel high computational burden. In [17], a robust control technique for VSC is suggested to compensate the harmonics in the islanded mode of operation. The controller eliminates the system uncertainties and maintains pure sinusoidal three-phase voltage under unbalanced/nonlinear load current conditions. A robust H2/H∞ voltage control strategy for islanded microgrid is addressed in [18]. The droop control and power management system provide the nominal values of voltage and frequency. Additionally, the nonlinear robust H2/H∞ technique provide the ride-through capability, guarantee power-sharing, eliminate small and large signal disturbances, and enhance the performance under nonlinear loads.
Sliding mode control (SMC) is a nonlinear and variable structure control technique has gained a huge interest from the researchers due to its inherent characteristics of simple implementation, strong robustness, good tracking of current reference, excellent dynamic response, high accuracy, and insensitivity to external disturbances and parameter uncertainties. Considering the abovementioned qualities, SMC is extremely suitable for the voltage-source converter (VSC) and can deal effectively with the nonlinear behavior of the power converter. The main problem of SMC is the chattering phenomena because of very high switching frequency result in excessive power losses, electro-magnetic noises, low control accuracy, and problems in the output filter design.
For single and three-phase inverters, SMC is addressed in [2,19,20,21] and [22,23]. The chattering phenomena are attenuated in [19,21] and [23] by smoothing the feedback control law in a narrow boundary layer and the switching function. Also, accomplishing a fixed switching frequency variable hysteresis band comparator. However, the robustness and the reference tracking error of these schemes is nearly degraded. In [24], Particle Swarm Optimization (PSO) for tuning control gains of terminal SMC with a fuzzy estimator of UPS inverter is proposed. This technique provides good dynamic response and improves the performance of the UPS inverter under the transient loading conditions. But, the THD level at the output voltage is high and also this technique cannot eliminate circulating currents. An Adaptive SMC technique with an auto-tuning idea of the sliding switching gain for a three-phase UPS system is recommended in [25]. This technique eliminates chattering phenomena to a great extent and also minimize sliding switching gain without considering the system uncertainties and external perturbations. Nevertheless, the response time is relatively slow, hence, this may encounter a serious stability issue. Nowadays, the decentralized SMC strategies [26,27] have been addressed to enhance the system stability and provide the robustness under unknown load condition. Two separate SMC controllers are designed for hybrid microgrid such as for fundamental positive sequence, direct power SMC scheme is used and for the negative sequence, an SMC current scheme is adopted. The controller ensures the power-sharing, regulate active and reactive powers, and mitigate the current harmonics under unbalanced and nonlinear load current conditions in grid-tied mode and also regulate voltage and frequency in islanded mode.
In the feedback control theory, fractional calculus is the newly emerging concept which deals with the fractional-order derivatives and integrals. In fact, the primary difference between fractional-order derivative and integer-order derivative mainly comprises of two aspects. Firstly, integer-order derivative depicts certain attributes like variation, uncertainties etc. of a physical or mechanical process at a particular instant of time, whereas, in the fractional-order derivative, the entire time domain is considered. Secondly, integer order derivative evaluates a physical process at a certain position within its local domain while on the other hand, fractional order considers the whole space for evaluation. Traditional SMC does not guarantee the convergence of the system. Moreover, chattering phenomena also exist which is not desired. In contrast to classical SMC, the fractional-order sliding mode control (FOSMC) control is an effective method to alleviate chattering phenomena and provides a more flexible degree of freedom [28]. The Riemann-Liouville (RL) fractional derivative is used in designing the sliding surface, and the upgraded exponential law is exploited so as to alleviate the chattering phenomena and to bring and keep the state variable onto the sliding surface. Moreover, to the best of the authors’ knowledge, the behavior of FOSMC for parallel-connected UPS system has not been examined so far, hence to accomplish this research gap, this paper presents nonlinear voltage control strategy based on FOSMC for parallel operating UPS system.
This paper presents a nonlinear control strategy for the voltage control of the parallel-connected UPS system. FOSMC scheme maintains the quality of the output voltage under multiple balanced/unbalanced dynamic load and also under distorted load current condition. Moreover, the proposed control strategy utilized fewer voltage sensors compared to model predictive control and classical SMC methods. A Lyapunov stability theorem is used to prove the stability of the proposed controller. Droop control is designed for the parallel-connected UPS systems to ensure proper power-sharing. Real-time simulation is performed in MATLAB/Simulink to show robustness and precise performance of the controller to maintain system power quality despite linear and/or distorted load current conditions. Additionally, the virtual output impedance loop is designed for the accurate reactive power-sharing with the load. The performance of the proposed FOSMC is compared with conventional proportional integral (PI) controller, and the simulation results show the THD of the output voltage of 0.40% and 1.03% for FOSMC, and 1.82% and 6.84% for PI controller under linear and nonlinear load, respectively.
The paper is organized as follows: Section 2 describes the system description, dynamic model of the inverter, and the mathematical model of the FOSMC such as the design of the sliding surface and feedback control law. Section 3 represents the Lyapunov stability theorem. Section 4 presents the parallel UPS system and droop control explanation. Section 5 explains the virtual output impedance (VOI). Then, Section 6 demonstrates the simulation results and detail comparison between FOSM and the conventional PI controller. Finally, discussions and conclusion are stated in Section 7 and Section 8, respectively.
2. System Description
The circuit and control diagram of the three-phase UPS system is shown in Figure 4. It consists of three-phase VSI connected to load through output LC filter, where L, R and Cf are the inductance, resistance, and capacitance, respectively of the output LC filter. vtabc and voabc are the three-phase output terminal voltages of the inverter and the AC bus or capacitor voltage, respectively. The voltage and current of the output filter are obtained in a sinusoidal dq reference frame, where the subscripts d and q represent the direct axis (d-axis) and quadrature axis (q-axis) of corresponding variables.
The dynamic model of the inverter can be obtained as:
Cfduo→dt=i→−io→
Ld i→dt + R i→= vi→−vo→
where vo→, vi→, i→ and io→ denotes the space-phasors analogous to voabc , vt , iabc and ioabc respectively. Elimination of i→ from Equations (1) and (2), gives us:
d2vo→dt2 = −RLdvo→dt−vo→LCf−1Cfdio→dt−RioLCf→+viLCf→
The terminal voltage of the VSI is associated with the pulse width modulation (PWM), the modulating signals of VSI is vi→ = (Vdc2) m→ . Equation (3) becomes:
d2vo→dt2=−RLdvo→dt−voLCf→−1Cfdio→dt−RioLCf→+Vdcm2LCf→
The d, q reference frame representation of Equation (4) will be:
d2[(vod +jvoq)ejθ]dt2=−RLd[(vod +jvoq)ejθ]dt−(vod +jvoq)ejθLCf−1Cfd[(iod +jioq)ejθ]−R(iod +jioq)ejθLCf+Vdc(md+jmq)ejθ2LCf
where θ is the transformation angle that the d-axis form against the α -axis and dθdt is the angular speed of space-phasors rotating in an anti-clockwise direction. Equation (5) can be divide into d and q axis:
d2 voddt2 = 2ωdvoqdt−RLdvoddt+(ω2−1LCf)vod+RωLvoq−1Cfdioddt+ωCfioq−RLCfiod+Vdc2LCfmd
d2 voqdt2=−2ωdvoddt−RLdvoqdt+(ω2−1LCf)voq−RωLvod−1Cfdioqdt−ωCfiod−RLCfioq+Vdc2LCfmq
Proposed Control Scheme Based on Frictional-Order SMC
This section addressed the proposed control scheme based on FOSMC. The proposed control strategy regulates the rotatory reference frame d and q-axis of the VSI external terminal voltage voabc . Equations (6) and (7) become:
d2 voddt2 = v¨od=d2 voddt2 = fd(vod ,voq ,iod ,ioq) + zmd + βd
d2 voqdt2=v¨oq=d2 voqdt2 = fq(vod ,voq ,iod ,ioq) + zmq + βq
where:
z = Vdc2LCf
and βd and βq are model disturbances:
fd = 2ωdvoqdt−RLdvoddt + (ω2−1LCf)vod + RωLvoq−1Cfdioddt + ωCfioq−RLCfiod
fd=−2ωdvoddt−RLdvoqdt + (ω2−1LCf)voq−RωLvod−1Cfdioqdt + ωCfiod−RLCfioq
where fd and fq are two nonlinear functions.
SMC is based on two main parameters; Sliding surface and control law. It is necessary for the system to track the sliding surface under the proposed control law. For d and q-axis control loop, the proposed non-integer sliding mode surface is defined by:
Sd=e˙d + λ Dα−1(sig(ed)γ)
Sq=e˙q + λ Dα−1(sig(eq)γ)
ed = vod−vodref
eq = voq−voqref
where ed and eq denote voltage-tracking error, Dα−1 denotes the fractional integral of (α−1)th order. where α, γ and λ are design choices positive parameters (α < 1 and γ < 1).
The sig () function is defined as:
sig(x)γ = |x|sgn(x)
sgn () function is defined as:
sgn(x)={x|x|if x ≠ 00 if x = 0
The details of the fractional calculus i.e., theorems and properties are presented in Appendix A.
S˙d=v¨od−v¨odref + λDαRL(sig(ed)γ)
S˙q=v¨oq−v¨oqref + λDαRL(sig(eq)γ)
where RL Dα is Riemann-Liouville (RL) fractional derivative of αth order. If vodref and voqref are assumed to be constant, hence v¨odref and v¨oqref are small values and can be neglected; also substituting values of v¨od and v¨oq from Equations (8) and (9) we get:
S˙d = fd + zmd + βd + λDαRL(sig(ed)γ)
S˙q = fq + zmq + βq + λDαRL(sig(eq)γ)
Considering Equations (21) and (22), the control laws are proposed in order to slide the system on a sliding surface to guarantee the fast and robust voltage-tracking error convergence is:
md=−[fd +λDαRL(sig(ed)γ) + Kdsgn(Sd)]z
mq=−[fq + λDαRL(sig(eq)γ) + Kqsgn(Sq)]z
where Kd and Kq are sliding gains.
The schematic diagram of FOSMC and the inverter is shown in Figure 5. The modulation signals are obtained based on proposed control laws of (23) and (24), sinusoidal pulse width modulation (SPWM) scheme is performed to generate gate signals for VSI. Figure 6 illustrates the flowchart of overall FOSMC.
The main drawback of the conventional SMC is the undesirable chattering phenomena because of very high switching frequency result in high oscillations in the system, excessive power losses, and low control accuracy. However, FOSMC strategy eliminates the chattering phenomena and accelerate the reaching speed [29,30].
3. Stability Analysis
The proposed controller can be justified by positive-defined Lyapunov candidate function:
V(t) = 12(Sd 2 + Sq 2)
The time derivative of (23) with respect to time, and putting (19) and (20), we get:
V˙(t) = Sd S˙d + Sq S˙q = Sd(v¨od + λRL Dα(sig(ed)γ) + Sq(v¨oq + λ RL Dα(sig(eq)γ)
Now substituting (8) and (9) and external disturbances Wd and Wq in (24) :
V˙(t) = Sd(fd + zmd + Wd + λRL Dα(sig(ed)γ)) + Sq (fq + zmq + Wq + λ RL Dα(sig(eq)γ)
Further substituting md and mq from (23) and (24) in (27), and sgn(Sd)=|Sd|Sd , then:
V˙(t) = (Sd Wd−Kd|Sd|) + Sq Wq−Kq|Sq|)
Sliding gains; Kd=|Wd| + ρd and Kq=|Wq| + ρq , where ρd and ρq are +ve parameters, thus:
V˙(t) ≤ −ρd|Sd|−ρq|Sq| ≤ −min(ρd ,ρq)(|Sd| + |Sq|)=−min(ρd ,ρq)∥S∥1
Equation (29) shows that the derivative of V(t) i.e., V˙(t) is negative definite, thus ensures that the sliding surfaces Sd and Sq will reach zero in a finite time.
4. Parallel UPS System
Usually, the UPS system feeds critical loads that cannot afford power failure. Although, it is necessary to fulfill the growing load demand without upgrading the present UPS system. Therefore, parallel-connected UPS systems approach provides low cost, reliability, and redundant solution to supply continuous power to the common ac bus despite any disruption in order to enhance the system stability. Moreover, a system true redundancy such as better stability and robustness can be achieved via the independent operation of the parallel UPS system. In parallel-connected UPS systems, the accurate active and reactive power-sharing among them is necessary which can be achieved by using two main control schemes i.e., wired control and wireless control. One of the most used and sophisticated wireless power-sharing technique is droop method. The block diagram of two parallel-connected UPS systems feeding load through an AC common bus is shown in Figure 7. The separate primary control which includes inner-loop control and outer-loop control is designed for each parallel-connected UPS system. The inner-loop control contains voltage control based on FOSMC to regulate the output voltage of the inverter and the droop control scheme is adopted in the outer-loop for the proper power-sharing.
4.1. Droop Control
With the objective of connecting parallel VSI without the critical communication link, the droop control approach is often proposed. The absence of the communication signals between the inverters helps to improve the reliability and also removes the restrictions on the physical locations of inverter units. The droop idea is obtained from the power system theory, in which the active power P is determined by the phase angle or power angle ∅ and the reactive power Q is dependent on the voltage amplitude difference E-V. In a power system the droop concept is used, where the load sharing among parallel operating generators is accomplished, based on the ω-P and E-Q droop characteristics. The droop curves are shown in Figure 8a,b, depending upon the output impedance. Considering the parallel-connected UPS inverters, the reactive power Q can be controlled by varying the voltage amplitude E and the active power P by angular frequency ω . The droop control schemes can be defined as:
ω = ω*−kPP
E = E*−kQQ
where E and ω are the amplitude and frequency of the inverter output voltage, kP and kQ are the droop coefficients of frequency and amplitude of output voltage, respectively; ω* and E* represents frequency and amplitude at the no-load condition.
The active and reactive power flow between the UPS inverter and the point of common coupling (PCC) can be expressed as follows:
P = (PVZcos∅−V2Z)cosθ + EVZsin∅cosθ
Q = (EVZcos∅−V2Z)sinθ−EVZsin∅cosθ
where V and Z are the voltage of the PCC and the magnitude of the output impedance, respectively; θ and ∅ represents the output impedance angle and phase angle, respectively.
4.1.1. Inductive Output Impedance Case: Z=jX
The equivalent model of the two parallel connected inverters to a common bus with output inductive impedance supporting common load is shown in Figure 9a. Traditionally, the VSI output and line impedances both are assumed to be inductive because of large filter inductor and line impedance which is inductive in nature. In this case, the active and reactive power expressions can be simplified by assuming a small phase angle ∅ difference between V and E (sin ∅ ≈ ∅ and cos∅ ≈ 1) :
P = EVXsin∅
Q = EVcos∅−V2X
4.1.2. Resistive Output Impedance Case: Z=R
The equivalent model of the two parallel connected inverters to a common bus with output resistive impedance supporting common load is shown in Figure 9b.
In low voltage systems, the line impedance is mainly resistive, the active and reactive power becomes:
P = EVcos∅−V2R
Q = −EVRsin∅
Therefore, due to the highly resistive output impedance of the inverter the droop scheme exchanges their roles:
ω = ω* + kPQ
E = E*−kQP
Hence, in the case of an output inductive impedance, the droop control concept based on P-ω and Q-V droop is often used, whereas for output resistive impedance the P-V and Q-ω droops scheme is often adopted. The droop control scheme depends upon the output impedance angle θ , and it has a different form for the different type of inverter output impedance as listed in Table 1. The droop coefficients kP and kQ of frequency and amplitude of output voltage are a function of the nominal values of active power P and reactive power Q, and the maximum permitted deviation in voltage amplitude ΔE and frequency Δω .
There is a trade-off between droop coefficients and voltage regulation, increasing droop coefficients will result in an accurate power-sharing but degraded voltage regulation. Droop control has many advantages like the absence of communication-based method among parallel operating VSI system provides high reliability and flexibility. However, there are so many issues associated with droop control technique like a very poor transient response, an intrinsic tradeoff between load sharing and voltage regulation, and mismatch in line impedance of parallel operating VSI systems that resulted in poor powering sharing.
5. Virtual Impedance Loop
As discussed early, there are so many cases which result in poor reactive power sharing during parallel operation of UPS inverter systems. For example, in low voltage network output line impedance is often resistive, as (R/X) of output line impedance is comparatively high, therefore, VSI will share the only active power to fulfill load demand. But this is a very rare case, usually medium or high voltage network make distributive network where line impedance is the sum of both resistor and inductor. In other words, if VSI output and line impedance are not purely inductive, then conventional droop control technique is not effective to guarantee accurate power sharing. Also, UPS system operating in parallel feeding an ac common load bus has different filter and output line impedance which will result in different reactive power, hence, this deteriorates the reactive power-sharing. In the literature, multiple solutions have been presented to enhance reactive power-sharing [31,32,33]. By changing the inclination of the droop curve resulting in improve reactive power sharing but will degrade voltage regulation. Another solution which is based on virtual impedance is most effective and accurate reactive power sharing technique called Virtual output impedance (VOI) loop-based droop control, it is a fictitious and robust control loop which mimic the output line impedance. The virtual impedance loop voltage reference for single VSI is expressed as:
Vref = Vo *−Zv Io
where Zv is VOI, Vo * is a droop control output voltage reference and Io is the filter output current. Figure 10 shows, an equivalent circuit of virtual impedance and phasor diagram, where VOI ( Zv) is greater than line impedance (Zl) . It means selection of VOI should dominate the actual line impedance value in order to ensure inductive response for low-frequency signals and resistive response for high-frequency signals, as ( R/X) ratio of output line impedance will affect reactive power-sharing. In literature, VOI is calculated indifference Reference Frame for the requirement of different controllers.
In dq reference frame, VOI can be calculated as:
VZvd = RZv Iod−LZv ωIoq
VZvq = RZv Ioq + LZv ωIod
Figure 11 shows the block diagram of the droop control with VOI. When UPS inverters of different rating are connected in parallel with the common ac bus having nominal apparent power Si of each UPS system:
Zv1 S1 = Zv2 S2 = … = ZvN SN
Furthermore, the VOI can provide extra features such as plug “n” play capability and sharing of the nonlinear load [34,35]. When the UPS system is suddenly connected to the ac bus, there is a current spike occur due to the small difference in phase/amplitude. These features are beyond the scope of this paper.
6. Simulation Results
The performance of the proposed FOSMC is illustrated through MATLAB/Simulink simulating the real-time single and multiple parallel-connected UPS system supplying an ac common bus. Moreover, the results of the proposed control strategy are compared with the conventional PI controller. The electrical parameters of the inverter and control parameters are shown in Table 2 and Table 3. The effectiveness of the proposed controller is evaluated for four case studies i.e., a balanced linear load, an unbalanced linear load, a nonlinear load, step load change condition, and parallel operation of UPS system.
6.1. Balanced Linear Load Condition
In this section, the performance of the proposed controller is examined under balanced linear load. The waveforms of the output voltage and current are illustrated in Figure 12a. Initially, the vodref is set zero while the balanced load is connected. At t = 0 s, voltage vodref value is stepped up to 500 V and kept constant for the remaining time as shown in Figure 12b, and the balance linear load is energized of P = 4 kW and Q = 100 Var.
As it can be seen, both voltage and current waveforms are stable and sinusoidal. The proposed controller is efficiently tracking the reference sinusoidal signal which indicates robustness and precise response of control framework under balanced load condition. The THD of the output voltage is 0.41% which is well under the IEEE standard.
6.2. Unbalanced Linear Load Condition
The aim of this section is to study the robust performance of the proposed control strategy under unbalanced linear load condition. It is supposed that the inverter system initially operates under a balanced load condition. At t = 0.4 s, the balanced load is switched off and an unbalanced series resistive-inductive (RL) load is energized (load connected to phase ‘a’ and ‘b’: 4 kW and 100 VAR, while the phase ‘c’ is opened). This causes the output load current non-sinusoidal but the FOSMC is capable of removing oscillation from the output voltage, thus the voltage waveform looks quite sinusoidal. The proposed FOSMC waveforms of output voltage and current are illustrated in Figure 13a. On the other hand, the conventional PI controller waveforms of the output voltage and current are shown in Figure 13b. The PI controller has alleviated slightly the effect of load current imbalance, but the output voltage is notably unbalanced. Hence, the proposed controller performance is quite effective under unbalanced load condition. Also, the THD of the output voltage is well under the IEEE standards.
6.3. Nonlinear Load Condition
In this case, the proposed FOSMC is tested for the nonlinear loading condition as shown in Figure 14a. At t = 0.4 s, a three-phase diode bridge rectifier, feeding series RL load (P = 4 kW, Q = 100 Var), is connected to the system. The proposed control strategy maintains the output voltage stable and sinusoidal throughout the time while the current waveform is distorted due to the nonlinearity of the output load. The proposed controller completely removes the harmonics distortions of the output voltage ( voabc ) with THD of 1.53%, which is under acceptable value (5%) recommended by IEEE. Furthermore, the proposed technique is robust against disturbances under different load conditions. Also, it is demonstrated that SMVC is able to provide a good performance in tracking the reference voltage signal. On the other hand, the PI controller is unsuccessful in mitigating the harmonic distortions of the output voltage, both output voltage and current waveforms are shown in Figure 14b. The THD of the output voltage is 6.85% which is much higher as compared to the proposed control scheme i.e., 1.03%.
6.4. Step Load Change Condition
In this case, the response of the proposed controller is examined under the fluctuating load. The system is energized and the voltage is stepped up to 500 V and kept constant for onwards time. The system is subjected to two-step changes i.e., at t = 0 s half load is connected while at t = 0.25 s, the load change from 50% to 100% means the full load is connected shown in Figure 15. In both the cases, the voltage, and current waveforms are stable, however, the amplitude of the current is increased depending upon the load requirements, while maintaining the output voltage ( voabc ) constant, equal to its reference value. This validates that the controller effectively rejected the dynamics load variations.
From simulation results, it can be concluded that the proposed FOSMC performance is robust and precise under different load current conditions. Moreover, the proposed scheme is less sensitive to external disturbance and system uncertainties and can achieve a very good voltage regulation performance and exceptional THD compensation, hence, surpassed the conventional PI controller performance. Table 4 shows the comparison between the proposed FOSMC and conventional PI controller under different load conditions. Similarly, Table 5 demonstrates the comparison of different control strategies in term of THD of output voltage under linear and nonlinear load conditions. It can be observed that the proposed control strategy harmonics compensation capability is far better as compared to other techniques.
According to Table 6, the proposed control strategy provides significant advantages compared to classical SMC such as alleviate chattering phenomena, low THD at the output voltage, and high-quality tracking accuracy.
Further, the main inherent characteristic of the FOSMC is robustness because the addition of fractional-order calculus in SMC provide an extra degree of freedom which improves robustness and accuracy.
6.5. Parallel Connected UPS Systems Operation
This case explains the parallel operation of two parallel-connected UPS systems feeding load through an ac common bus. Extensive simulations have been performed to show system response for parallel operation. Two types of load i.e., linear and distorted load have been investigated under proposed FOSMC control. Droop control approach ensures accurate active and reactive power-sharing between UPS systems. Figure 16 illustrates voltage and current waveforms of the parallel operation of two UPS systems for the linear RL-series load, where the waveforms are sinusoidal and stable. The output response for the distorted load is shown in Figure 17, where the system output voltage is stable. However, the current waveform is distorted due to the nonlinearity of the output load. Furthermore, the controller completely eliminates the harmonic distortions of the output voltage. In order to satisfy proper active and reactive power-sharing, the output responses of the droop control for two VSI’s for the linear load is shown in Figure 18. The initial UPS-1 states are P1 = 2 kW, Q1 = 400 Var. The output active power of UPS-1 is changed at t = 0.25 s, from 2 kW to 4 kW, and the reactive power is changed from 400 Var to 800 Var when additional load is switched on. At t = 0.32 s, output active and reactive power switched back to previous values when additional load is disconnected. Similarly, for UPS-2 initial values of P2 = 2 kW and Q2 = 400 Var are kept. At t = 0.25 s, output active power is changed from 8 kW to 4 kW and reactive power is changed from 400 Var to 800 Var when additional load is connected in order to fulfill load power requirements. After t = 0.32 s, additional load is shaded and power values switched back to its initial results. Hence, the implemented droop control approach efficiently and effectively satisfied power-sharing between UPS systems.
7. Discussion
The main objective of this paper was to design a nonlinear voltage control strategy for single and multi-parallel connected UPS system to maintain the quality of the output voltage despite linear, unbalanced, nonlinear, and step load change current conditions. The performance was validated using real-time domain simulation in MATLAB/Simulink. The behavior of FOSMC for parallel-connected UPS system had not been examined so far, hence the main achievement of this paper is the implementation of the proposed FOSMC for the parallel-connected UPS system feeding common ac bus.
8. Conclusions
In this paper, the voltage control strategy was proposed for single and parallel-connected UPS system. The performance of the proposed nonlinear frictional-order SMC has been examined under different load sceneries. It was demonstrated through real-time simulation that the control strategy can effectively eliminate the THD of the output voltage and show robust response under unbalanced load current condition. Furthermore, it maintains very good voltage regulation such as dynamic response and steady-state error under the nonlinear or unbalanced load current conditions. The FOSMC were less sensitive to external disturbances and system parametric uncertainties. The stability of the proposed control strategy was proven by applying Lyapunov stability theory. The performance of the proposed FOSMC was compared with conventional proportional integral (PI) controller, and the simulation results show that the THD of the output voltage is 0.40% and 1.03% for FOSMC, and 1.82% and 6.84% for PI controller under linear and nonlinear load, respectively.
In the future, the proposed control strategy will be extended to hybrid electric vehicles, and bidirectional converter in a hybrid microgrid to maintain the power quality in both modes of operation namely; inversion mode and rectification mode. The simulated results can be verified using the hardware implementation.
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
[Image omitted. See PDF.]
Output Impedance | Z = jX (Inductive ∅=90°) | Z = R (Resistive ∅=90°) |
---|---|---|
Active Power | P = EVXsin∅ ≅ EVX∅ | P = EVcos∅−V2R ≅ VR(E−V) |
Reactive Power | Q = EVcos∅−V2X ≅ VX(E−V) | Q = −EVRsin∅ ≅ −EVR∅ |
Frequency Droop | ω = ω*−kPP | ω = ω* + kPQ |
Amplitude Droop | E = E*−kQQ | E = E*−kQP |
Droop coefficient | kP=ΔωPN | kP=Δω2QN |
Droop coefficient | kQ=ΔE2QN | kQ=ΔEPN |
Parameters | Symbol | Values |
---|---|---|
Switching frequency | f | 10 kHz |
Filter inductor | L | 25 mH |
Filter capacitor | Cf | 600 µF |
Resistor | R | 4 mΩ |
Dc-link voltage | Vdc | 670 V |
Angular frequency | wo | 314 rad/s |
Parameters | Symbol | Values |
---|---|---|
FOSMC parameter | γ | 0.9 |
FOSMC parameter | λ | 1500 |
Fractional-order Slide gains | Kd, Kq | 4.5 × 106 |
PI proportional gain | KP | 0.15 |
PI integral gain | KI | 42 |
Load Types | Proposed FOSMC Voltage THD (%) | Conventional PI Controller Voltage THD (%) |
---|---|---|
Balanced load | 0.44 | 1.83 |
Nonlinear load | 1.03 | 6.84 |
No Load | 0.37 | 1.53 |
Reference | Control Technique | %Voltage THD Linear Load | %Voltage THD Nonlinear Load | Controller Complexity |
---|---|---|---|---|
[3] | PI | 16 | 42 | Low |
[7] | Dead Beat | 2.1 | 4.8 | Medium |
[5] | PR | 1.4 | 4.6 | Low |
[14] | MPC (observer based) | 2.82 | 3.8 | Medium |
Proposed | Fractional-order SMC | 0.44 | 1.03 | Low |
Characteristics | Proposed FOSMC | [23] | [36] | [37] | [38] |
---|---|---|---|---|---|
Response time | Very High | High | High | High | High |
Tracking accuracy | Fast | Medium | Medium | Fast | Medium |
Robustness | Very High | Moderate | Moderate | High | High |
Chattering phenomena | No | No | Yes | No | No |
Harmonic compensation | Excellent | Good | Good | Excellent | Excellent |
Transient response | Very Fast | Fast | Fast | Very Fast | Fast |
THD% (Nonlinear load) | 1.03 | 1.7 | 1.9 | 1.3 | 1.0 |
THD% (Linear load) | 0.44 | 0.4 | 0.6 | 0.4 | 0.7 |
Reference tracking error (ev%) | 1.89 | 2.7 | - | - | 2 |
Author Contributions
M.A. studied the literature review and found the research gap, performed the simulation work, and wrote the paper. H.S.K. helped in controller stability analysis. A.W. and F.H. actively contributed to the arrangement and format of the paper. A.R.J. helped to revise the paper. M.A. supervised this research work.
Funding
This research received no external funding.
Conflicts of Interest
The authors declare no conflict of interest.
Nomenclature
Cf Filter capacitor
L Filter inductor
R Filter resistor
vo→ Three-phase inverter output voltage
vi→ AC bus or capacitor voltage
i→ Inverter terminal current
io→ AC bus current
m→ Modulation index
Vdc Dc-link voltage
θ Transformation angle
ω Angular frequency
βd andβq Model uncertainties in dq axis
ed andeq Voltage tracking error in dq axis
α,γandλ Design choice parameters
Sd and Sq Sliding surface in dq axis
DαRL Riemann-Liouville (RL) fractional derivative
md and mq Feedback control law in dq axis
Kd andKq Sliding gain in dq axis
Appendix A
Appendix A.1. Basic Fractional Calculus
The most commonly used three types of fractional-order calculus (FOC) are: the Grunwald-Letnikov (G-L) type, the Riemann-Liouville (R-L) type, and the Caputo type. Three basic definitions of the FOC operators are:
Definition A1.
The αth order R-L fractional derivative and integration of a function f(t) with respect to t is given by:
D0,tαRlf(t)=dαdtαf(t)=1Γ(m-α)dmdtm∫αtf(τ)(t-τ)α-m+1dτ
I0,tαf(t)=D0,t-αf(t)=1Γ(α)∫αtf(τ)(t-τ)1-αdτ
where m-1 ≤ α < m (m∈ N) and Γ(.) is Euler's Gamma Function Γ(α)=∫0-∞e-t tα-1dt .
Definition A2.
The αth order G-L fractional derivative and integration of a function f(t) is defined as:
DtααGLf(t)=1Γ(-α)∫αtf(τ)(t-τ)α+1dτ
Itααf(t)=Dt-ααGLf(t)=1Γ(α)∫αt(t-τ)α-1f(τ)dτ
Definition A3.
The αth order Caputo fractional derivative of a function f(t) is defined as:
Dtααcf(t)={1Γ(m-α)∫αtfm(τ)(t-τ)α-m+1dτdmdtmf(t)
Appendix A.2. Fractional Differentiator Approximation
Oustaloups recursive approximation algorithm is used to realize the fractional-order non-integer differentiator (Dα) and integrator (Dα-1 orIα) blocks of the proposed controller. Therefore, it approximates the following transfer function:
H(s)=sr,r∈R,r∈[-1,1]
by an integer-order transfer function of the form:
H^(s)=C0∏k=-MMs+ωk´s+ωk,
where frequency range ωb<ω<ωh , and the remaining unknown parameters of H^(s) are found by:
ωk´=ωb (ωhωb)k+M+0.5(1-r)2M+1
ωk =ωb (ωhωb)k+M+0.5(1+r)2M+1
C0=(ωhωb)-r2∏k=-MMωkωk´,
where ωb andωh are the lower and upper limits of frequency and (2M + 1) represents the order of H^(s) .
© 2018 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (http://creativecommons.org/licenses/by/4.0/).
1. Aamir, M.; Kalwar, K.A.; Mekhilef, S. Uninterruptible power supply (ups) system. Renew. Sustain. Energy Rev. 2016, 58, 1395-1410.
2. Aamir, M.; Mekhilef, S. An online transformerless uninterruptible power supply (ups) system with a smaller battery bank for low-power applications. IEEE Trans. Power Electr. 2017, 32, 233-247.
3. Loh, P.C.; Newman, M.J.; Zmood, D.N.; Holmes, D.G. A comparative analysis of multiloop voltage regulation strategies for single and three-phase ups systems. IEEE Trans. Power Electr. 2003, 18, 1176-1185.
4. Guerrero, J.M.; Loh, P.C.; Lee, T.-L.; Chandorkar, M. Advanced control architectures for intelligent microgrids-Part II: Power quality, energy storage, and ac/dc microgrids. IEEE Trans. Ind. Electr. 2013, 60, 1263-1270.
5. Hasanzadeh, A.; Onar, O.C.; Mokhtari, H.; Khaligh, A. A proportional-resonant controller-based wireless control strategy with a reduced number of sensors for parallel-operated upss. IEEE Trans. Power Deliv. 2010, 25, 468-478.
6. Kawabata, T.; Miyashita, T.; Yamamoto, Y. Dead beat control of three phase pwm inverter. IEEE Trans. Power Electr. 1990, 5, 21-28.
7. Mattavelli, P. An improved deadbeat control for ups using disturbance observers. IEEE Trans. Ind. Electr. 2005, 52, 206-212.
8. Wang, M.; Li, F.; Liu, Y.; Huang, L.; Sakane, M. Distributed parallel operation of modified deadbeat controlled ups inverters. In Proceedings of the Power Electronics Specialists Conference, Orlando, FL, USA, 17-21 June 2007; pp. 1727-1732.
9. Zhang, K.; Kang, Y.; Xiong, J.; Chen, J. Direct repetitive control of spwm inverter for ups purpose. IEEE Trans. Power Electr. 2003, 18, 784-792.
10. Escobar, G.; Valdez, A.A.; Leyva-Ramos, J.; Mattavelli, P. Repetitive-based controller for a ups inverter to compensate unbalance and harmonic distortion. IEEE Trans. Ind. Electr. 2007, 54, 504-510.
11. Deng, H.; Oruganti, R.; Srinivasan, D. Analysis and design of iterative learning control strategies for ups inverters. IEEE Trans. Ind. Electr. 2007, 54, 1739-1751.
12. Cortes, P.; Rodriguez, J.; Vazquez, S.; Franquelo, L.G. Predictive control of a three-phase ups inverter using two steps prediction horizon. In Proceedings of the 2010 IEEE International Conference on Industrial Technology (ICIT), Vina del Mar, Chile, 14-17 March 2010; pp. 1283-1288.
13. Kim, D.-E.; Lee, D.-C. Feedback linearization control of three-phase ups inverter systems. IEEE Trans. Ind. Electr. 2010, 57, 963-968.
14. Cortés, P.; Ortiz, G.; Yuz, J.I.; Rodríguez, J.; Vazquez, S.; Franquelo, L.G. Model predictive control of an inverter with output LC filter for ups applications. IEEE Trans. Ind. Electr. 2009, 56, 1875-1883.
15. Low, K.-S.; Cao, R. Model predictive control of parallel-connected inverters for uninterruptible power supplies. IEEE Trans. Ind. Electr. 2008, 55, 2884-2893.
16. Yaramasu, V.; Rivera, M.; Narimani, M.; Wu, B.; Rodriguez, J. Model predictive approach for a simple and effective load voltage control of four-leg inverter with an output LC filter. IEEE Trans. Ind. Electr. 2014, 61, 5259-5270.
17. Hamzeh, M.; Emamian, S.; Karimi, H.; Mahseredjian, J. Robust control of an islanded microgrid under unbalanced and nonlinear load conditions. IEEE J. Emerging Sel. Top. Power Electr. 2016, 4, 512-520.
18. Baghaee, H.R.; Mirsalim, M.; Gharehpetian, G.B.; Talebi, H.A. A decentralized robust mixed H2/H∞ voltage control scheme to improve small/large-signal stability and frt capability of islanded multi-der microgrid considering load disturbances. IEEE Syst. J. 2018, 12, 2610-2621.
19. Abrishamifar, A.; Ahmad, A.; Mohamadian, M. Fixed switching frequency sliding mode control for single-phase unipolar inverters. IEEE Trans. Power Electr. 2012, 27, 2507-2514.
20. Matas, J.; De Vicuna, L.G.; Miret, J.; Guerrero, J.M.; Castilla, M. Feedback linearization of a single-phase active power filter via sliding mode control. IEEE Trans. Power Electr. 2008, 23, 116-125.
21. Komurcugil, H. Rotating-sliding-line-based sliding-mode control for single-phase ups inverters. IEEE Trans. Ind. Electr. 2012, 59, 3719-3726.
22. Saetieo, S.; Devaraj, R.; Torrey, D.A. The design and implementation of a three-phase active power filter based on sliding mode control. IEEE Trans. Ind. Appl. 1995, 31, 993-1000.
23. Pichan, M.; Rastegar, H. Sliding-mode control of four-leg inverter with fixed switching frequency for uninterruptible power supply applications. IEEE Trans. Ind. Electr. 2017, 64, 6805-6814.
24. Chang, E.-C.; Su, Z.; Xu, Z.; Wu, R.-C. Particle swarm optimization tuned fuzzy terminal sliding mode control for ups inverters. J. Intell. Fuzzy Syst. 2015, 29, 2483-2488.
25. Choi, Y.; Choi, H.; Jung, J. An adaptive sliding-mode control technique for three-phase ups system with auto-tuning of switching gain. Electr. Eng. 2014, 96, 373-383.
26. Baghaee, H.R.; Mirsalim, M.; Gharehpetian, G.B.; Talebi, H.A. A decentralized power management and sliding mode control strategy for hybrid ac/dc microgrids including renewable energy resources. IEEE Trans. Ind. Inf. 2017.
27. Baghaee, H.R.; Mirsalim, M.; Gharehpetian, G.B.; Talebi, H.A. Decentralized sliding mode control of wg/pv/fc microgrids under unbalanced and nonlinear load conditions for on-and off-grid modes. IEEE Syst. J. 2017.
28. Pan, I.; Das, S. Chaotic multi-objective optimization based design of fractional order piλdμ controller in avr system. Int. J. Electr. Power Energy Syst. 2012, 43, 393-407.
29. Orlowska-Kowalska, T.; Dybkowski, M.; Szabat, K. Adaptive sliding-mode neuro-fuzzy control of the two-mass induction motor drive without mechanical sensors. IEEE Trans. Ind. Electr. 2010, 57, 553-564.
30. DeCarlo, R.A.; Zak, S.H.; Matthews, G.P. Variable structure control of nonlinear multivariable systems: A tutorial. Proc. IEEE 1988, 76, 212-232.
31. Pei, Y.; Jiang, G.; Yang, X.; Wang, Z. In Auto-master-slave control technique of parallel inverters in distributed ac power systems and ups. In Proceedings of the Power Electronics Specialists Conference, Aachen, Germany, 20-25 June 2004; pp. 2050-2053.
32. Mahmood, H.; Michaelson, D.; Jiang, J. Accurate reactive power sharing in an islanded microgrid using adaptive virtual impedances. IEEE Trans. Power Electr. 2015, 30, 1605-1617.
33. Han, H.; Hou, X.; Yang, J.; Wu, J.; Su, M.; Guerrero, J.M. Review of power sharing control strategies for islanding operation of ac microgrids. IEEE Trans. Smart Grid 2016, 7, 200-215.
34. Guerrero, J.M.; Matas, J.; de Vicuna, L.G.; Castilla, M.; Miret, J. Decentralized control for parallel operation of distributed generation inverters using resistive output impedance. IEEE Trans. Ind. Electr. 2007, 54, 994-1004.
35. Guerrero, J.M.; Vasquez, J.C.; Matas, J.; De Vicuña, L.G.; Castilla, M. Hierarchical control of droop-controlled ac and dc microgrids-A general approach toward standardization. IEEE Trans. Ind. Electr. 2011, 58, 158-172.
36. Delghavi, M.B.; Yazdani, A. Sliding-mode control of ac voltages and currents of dispatchable distributed energy resources in master-slave-organized inverter-based microgrids. IEEE Trans. Smart Grid 2017.
37. Delghavi, M.B.; Shoja-Majidabad, S.; Yazdani, A. Fractional-order sliding-mode control of islanded distributed energy resource systems. IEEE Trans. Sustain. Energy 2016, 7, 1482-1491.
38. Zheng, L.; Jiang, F.; Song, J.; Gao, Y.; Tian, M. A discrete-time repetitive sliding mode control for voltage source inverters. IEEE J. Emerg. Sel. Top. Power Electr. 2018, 6, 1553-1566.
Department of Electrical Engineering, Bahria University, Islamabad 44000, Pakistan
*Author to whom correspondence should be addressed.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
© 2018. This work is licensed under https://creativecommons.org/licenses/by/4.0/ (the “License”). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.
Abstract
According to the standards of Institute of Electrical and Electronics Engineers (IEEE) 519–1992, the maximum THD of the output voltage in the UPS system should be less than 5% in common applications such as households’ appliances and offices. The Riemann-Liouville (RL) fractional derivative is used in designing the sliding surface, and the upgraded exponential law is exploited so as to alleviate the chattering phenomena and to bring and keep the state variable onto the sliding surface. [...]to the best of the authors’ knowledge, the behavior of FOSMC for parallel-connected UPS system has not been examined so far, hence to accomplish this research gap, this paper presents nonlinear voltage control strategy based on FOSMC for parallel operating UPS system. According to Table 6, the proposed control strategy provides significant advantages compared to classical SMC such as alleviate chattering phenomena, low THD at the output voltage, and high-quality tracking accuracy. Fractional Differentiator Approximation Oustaloups recursive approximation algorithm is used to realize the fractional-order non-integer differentiator (Dα) and integrator (Dα-1 orIα) blocks of the proposed controller. [...]it approximates the following transfer function: H(s)=sr,r∈R,r∈[-1,1] by an integer-order transfer function of the form: H^(s)=C0∏k=-MMs+ωk´s+ωk, where frequency range ωb<ω<ωh , and the remaining unknown parameters of H^(s) are found by: ωk´=ωb (ωhωb)k+M+0.5(1-r)2M+1 ωk =ωb (ωhωb)k+M+0.5(1+r)2M+1 C0=(ωhωb)-r2∏k=-MMωkωk´, where ωb andωh are the lower and upper limits of frequency and (2M + 1) represents the order of H^(s) . © 2018 by the authors.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer