1. Introduction
Precast concrete has not been used widely as a framing system for buildings located in several seismic regions. Precast concrete joints between the prefabricated members have some issues. Connections, in particular beam-to-column connections, are the vital part of precast concrete construction. To satisfy the structural requirements of the overall frame, each connection must have the ability to transfer vertical shear, transverse horizontal shear, axial tension and compression, and occasionally bending moment and torsion between one precast component and another, safely. The transfer of forces between the components and eventually the behavior of frames are governed by the characteristics of the connections. However, in practice, the behavior of precast connections is not well established and not fully understood to fulfill the requirements needed in the design and construction development of precast technology [1–3].
Current technology is widely available to satisfy the growing demand required of engineers to provide communities with superior levels of structural performance during an earthquake. As more advances are made in seismic engineering, the available technology becomes more cost-competitive when compared to traditional construction practice: further financial benefits can be associated with the improved response of the system considering the seismic risk applied over the working life of the structure. High performing systems will be designed to operate more efficiently as they are tuned to their direct application. As a result, the seismic demand imposed onto a structure (maximum displacements and accelerations) can be significantly reduced, thereby reducing material costs and construction time. However, in developing this new technology, design recommendations are required to ensure the technology is appropriately utilized.
This paper focuses on understanding the behavior of the HPHS (high-performance hybrid system) under seismic action. The validity of the HPHC system was demonstrated by a series of experimental tests, which proved the system has good performance under lateral loading. For application of the HPHS to the real structure, the seismic performance of single connections for several primary variables has to be assessed. In this study, parametric study for the HPHS connection was carried out based on test and FEM analysis. Investigated parameters include (1) axial load on column, (2) beam connection steel plate length, (3) inner bolt stress contribution, and (4) plastic hinge area. Therefore, this paper is aimed at developing and calibrating a nonlinear FE model and further uses it to investigate the behavior of HPHS by varying the main control parameters [4].
2. Previous Development Connection and Test Results
The new connection detail suggested in this study is characterized by ductile connection, steel connectors, and engineered cementitious composite (ECC) which is a kind of high-performance fiber reinforced cement composite with multiple fine cracks (HPFRCCs) and used in order to improve the constructability of joint and efficiently transfer stress between discontinued precast members. Making steel connector consists of bolting steel tubes and steel plates which are usually placed inside the precast column and beam and casting the ECC to some parts of the beam and joint in the field (refer to Figures 1, and 2) [1–3].
[figure omitted; refer to PDF]
Generally, in the composite structure, there are many problems with contact area of concrete and steel. Therefore, all interfaces between two contact surfaces were constrained with each other. The general contact formulation used in ABAQUS involves a master-slave algorithm. This formulation considers the hard contact for normal direction of each surface and frictional contact behavior for tangential direction. Surface interactions and constrained area are shown in Figure 10. Boundary conditions for generated model are shown in Figure 11. Bottom of the column was supported by pin, and the end of the beam was supported through roller condition. These boundary conditions were determined from the test assumptions. The beam end was restrained only in roller, and the bottom of the column was restrained with a hinge. The FE models were loaded in two steps. Axial load was applied in first step at the column, and lateral load was applied to the same location in second step, cyclically. Cyclic load was applied by displacement control, and this is shown in Figure 12.
[figure omitted; refer to PDF][figure omitted; refer to PDF][figure omitted; refer to PDF]3.3. FE Analysis Results
To verify the finite element model, the analytical results were compared with the experimental results. The specimens were modeled with a truss elements and the remaining plane stress 2D elements. Concrete was modeled using 2D plane stress elements which were isoparametric elements. On the other hand, the reinforcing steel bars were modeled as two-node truss elements. At the joint core region, the area of truss elements close to the boundary was increased appropriately to simulate their corresponding steel area contributions. The beam bottom bars were discontinued at the face of the column. Steel plates, which were used for the connection at the joint, extended inside the beam at one side and abutted with the column face on the other side. These plates were simulated as 2D plane stress elements. These elements were assigned with steel plate thickness and its material properties. The concrete on the front and rear side of these elements was neglected in the analysis as it was filled up after the connections were fastened. Four rows of 2D elements at the bottom of the joint were treated as being connected by the steel plates, and their equivalent area was transferred to the column main bars and transverse links.
The predicted and observed responses of the specimens are presented in Figure 13. From Figure 13(a) of specimen RC-control, it can be seen that the analytical model seemed to have predicted a good response with respect to the experimental observations. Although the displacements of the analytical model for a few initial cycles were slightly higher, the later cycles’ predicted results were in good agreement with the experimental counterparts. Specimen RC-control achieved a displacement ductility factor (
[figures omitted; refer to PDF]
Comparison of the analytical and experimental results of all the specimens showed that the lateral load-displacement hysteresis loops obtained from the FE analyses were quite similar to the experimental observations. Besides, the failure modes and the ultimate ductility capacities correlated well with the experimental results. The FE analyses also showed that results of the deformations and cracking patterns matched well with the experimental observations. From the aforementioned observations and predictions of both the global and local behaviors using the FE analysis, the use of FE modeling techniques can, therefore, be further extended to study the joint performance by varying different parameters.
4. Parametric Studies
4.1. Influence of Axial Loads on Behavior of Beam-Column Joints
Axial loading is a critical parameter in the studies of beam-column joints, but its effect on seismic behavior of beam-column joints has not been fully understood. Previous investigations have shown that axial force is beneficial to the joint shear resistance [3]. Since the neutral axis depth in the column increases with axial compression load, a larger portion of the bond forces from the beam bars can be assumed to be transferred to the diagonal strut. Therefore, the concrete contribution to the joint shear resistance will be increased. In [7], the authors experimentally investigated two nonductile interior beam-column joints with different axial loading levels. However, both of these specimens failed due to the pullout of the embedded beam bottom bars instead of joint shear failure.
Lin and Restreop’s investigations [8] showed that axial compression in excess of
In this study, the influence of axial loading on the seismic behavior of hybrid-steel concrete joints is investigated. Axial load was applied in first step at the column, and lateral load was applied to the same location in second step, cyclically. The same loading histories as those used in the analysis of specimens without axial loading were applied, and the story shear force versus horizontal displacement plots corresponding to different axial load levels were plotted for specimen PC-I50-0.2. It can be seen that Specimen inter series attained an optimum value of ultimate story shear when axial load ratio was
4.2. Formation of Plastic Hinge
When designing the reinforced concrete frame, the most important design consideration is the moment strength ratio of beam and column and plastic hinge location. Furthermore, steel plates would be a very important design parameter because this parameter determines the strength and stiffness of beams.
The moment strength ratio is defined as the ratio of the sum of the nominal moment strengths of the column above and below the joint to the sum of the nominal moment strengths of all the beams in one plane framing into the joint. Theoretically, a moment strength ratio greater than one should cause the plastic hinges to form in the beams and not in the column. However, ACI318 Building Code [2] and ASCE-ACI Committee 352 recommend the moment strength ratio to be greater than or equal to 1.2 and 1.4, respectively. For the beam failure of proposed connection, specimens were designed to have the moment strength ratio as 1.6. For designing the proposed connection system more economically, plate length and thickness should be examined widely. Therefore, in this section, FE models were investigated. Investigated range of connection detail was determined according to the moment strength ratio of 1 to 1.6.
As a result of finite element analysis, the capacity of beam-to-column joint specimen could be determined by the strength of beam for most cases. However, the failure mode of the beam-to-column specimen for the case of moment capacity ratio 1 had shown beam-joint failure. Other test specimens which have a moment strength capacity of 1.2 ∼ 1.6 have shown beam failure mode. As the moment capacity ratio increased, the plastic hinge location moved to the outside of the joint. And cracks were more concentrated to plastic hinge. It is shown in Figures 15 and 16.
[figures omitted; refer to PDF]
[figures omitted; refer to PDF]
Strain distribution is very important information for plastic hinge location; from the strain information of FEA results, plastic hinge location was clearly observed. All specimens have experienced yielding of reinforcements. However, decreasing the moment strength ratio decreases the stress in plastic hinge region. At low level of moment strength ratio yielding of reinforcement was shown latterly, than other cases of specimens. It is shown in Figure 17. Furthermore, to verify the contribution of steel plate and to locate the plastic hinge region, more FE analyses were performed. As described above, the stiffness of the beam section is the main parameter for locating plastic hinge region. As a result of FE analysis, the crack pattern of each FE model, which has different lengths of connecting plate, is clearly different. The location of plastic hinge was determined by the length of plates clearly. This is shown in Figure 18.
[figures omitted; refer to PDF]
[figures omitted; refer to PDF]
5. Design Consideration
To determine the moment capacity of bolt connection, the strain distribution of bolts and connecting plates should be investigated. Because bolt strain cannot be measured from the test, 3D finite element analysis was performed. Because too many components were needed to compensate details of the proposed connection system, analysis was performed in monotonic loading, only. The finite element model consisted of 3 parts: concrete parts, steel parts, and reinforcement. For the reality of finite element modeling, each part was modeled separately. And reinforcements were embedded in concrete components. These models are illustrated in Figure 19. Boundary conditions and other restraints are made with the same method of 2D finite element analysis.
[figures omitted; refer to PDF]
As a result of finite element analysis, stress contour and strain field were provided. Especially, stress and strain of bolts components were investigated for the distribution of resultants forces for connecting area. The stress distribution is illustrated in Figure 20. In the connecting area, most of stress was concentrated in end of the plate. Because stress was flowing along the normal direction of contact area, stress concentration of concrete was shown at the end part of the steel plate. However, concrete of the column remained in elastic range. For locating the plastic hinge of beam elements, the stress distribution of reinforcements was investigated. Basically, stress was concentrated at the end of the steel plate. Therefore, using the proposed connection system, plastic hinge could be controlled by the plate length. This is shown in Figure 21. For the design purposes, stress distribution of connecting steel plate would be needed. Using the information of stress distribution at the center of bolt element, which was described in this section, resultant force could be calculated. This is also shown in Figure 22.
[figure omitted; refer to PDF][figure omitted; refer to PDF][figures omitted; refer to PDF]
Neutral axis was formed at the third bolt from the compressive extreme fiber. Because stiffness could be increased with the composite action at compressive area, compressive stress area was bigger than tensile one. Provided stress is shown in Table 4.
Table 4
Stress distribution and resultant force results.
Element ID | Stress type | Strain compatibility | FEM | ||
Stress (MPa) | Resultant force (kN) | Stress (MPa) | Resultant force (kN) | ||
El. 1 | Tension | 400 | 624 | 368 | 574 |
El. 2 | Tension | 280 | 302 | 253 | 272 |
El. 3 | Tension | 180 | 151 | 150 | 125 |
El. 4 | Tension | 90 | 76 | 65 | 54 |
El. 5 | Compression | 92 | 77 | 113 | 94 |
El. 6 | Compression | 200 | 73 | 253 | 92 |
Cc | Compression | 30 | 770 | 36 | 720 |
6. Conclusion
FE models used in this study well predict the behavior of test specimens. However, the initial stiffness problems encountered by the embedded truss model should be solved for the more wide parametric study such as serviceability check in design process.
According to the parametric study, the effect of axial load was investigated. There is a reduction in story shear and ultimate number of cycles after enhancement in axial load ratio beyond 0.3 (i.e.,
Plastic hinge region is very important design criteria for frame action. From the result of the parametric study, plastic hinge location is determined by the moment strength ratio and plate length. Generally, plastic hinge was formed far from the column face with the increase of moment strength ratio. It was clarified by investigating the stress distribution of reinforcement. For low value of moment strength ratio, reinforcement is hard to yield and plastic hinge cannot be formed easily, in the area of plate installed area. However, the length of plates is an important parameter for location of plastic hinge. Investigation from the test and FE model revealed that plastic hinge occurred at the end of steel plates. Therefore, using the proposed connecting system, plastic hinge location can be controlled by the designers.
Complicated 3D model for the proposed connecting system would be used for design strength calculation for connection. The stress distribution of bolt elements is similar to the stress distribution resulted from strain compatibility methods. Therefore, the proposed connection can be designed using conventional design methods.
Acknowledgments
This study was supported by Kyungnam University Foundation Grant, 2016.
[1] H.-K. Choi, Y.-C. Choi, C.-S. Choi, "Development and testing of precast concrete beam-to-column connections," Engineering Structures, vol. 56, pp. 1820-1835, DOI: 10.1016/j.engstruct.2013.07.021, 2013.
[2] H.-K. Choi, Y.-C. Choi, C.-S. Choi, "Hysteretic behavior and seismic resistant capacity of precast concrete beam-to-column connections," Journal of the Earthquake Engineering Society of Korea, vol. 14 no. 4, pp. 61-71, DOI: 10.5000/EESK.2010.14.4.061, 2010.
[3] C.-S. Choi, S.-H. Kim, Y.-C. Choi, H.-K. Choi, "Analytical study on hybrid precast concrete beam-column connections," Journal of the Korea Concrete Institute, vol. 25 no. 6, pp. 631-639, DOI: 10.4334/jkci.2013.25.6.631, 2013.
[4] S. A. Kulkarni, B. Li, W. K. Yip, "Finite element analysis of precast hybrid-steel concrete connections under cyclic loading," Journal of Constructional Steel Research, vol. 64 no. 2, pp. 190-201, DOI: 10.1016/j.jcsr.2007.05.002, 2008.
[5] J. Hu, "Design and modeling for smart PR-CFT connection systems," Smart Connection Systems, 2015.
[6] L. Torres, F. López-Almansa, L. M. Bozzo, "Tension-stiffening model for cracked flexural concrete members," ASCE, vol. 130 no. 8, pp. 1242-1251, 2004.
[7] M. Attila B, S. P. Pessiki, R. N. White, P. Gergely, "Implications of experiments on the seismic behavior of gravity load designed RC beam-to-column connections," Earthquake Spectra, vol. 12 no. 2, pp. 185-198, DOI: 10.1193/1.1585876, 1996.
[8] C. M. Lin, J. I. Restreop, "Seismic behaviour and design of reinforced concrete interior beam-column joints," Bulletin of the New Zealand for Society Earthquake Engineering, vol. 35 no. 2, pp. 108-128, DOI: 10.5459/bnzsee.35.2.108-128, 2002.
[9] J. P. Fu, T. Chen, Z. Wang, S. Bai, "Effect of axial load ratio on seismic behaviour of interior beam-column joints," Proceedings of the 12WCEE 2000, .
[10] B. Li, C. L. Leong, "Experimental and numerical investigations of the seismic behavior of high-strength concrete beam-column joints with column axial load," ASCE, vol. 141 no. 9, pp. 1842-1853, 2004.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
Copyright © 2020 H.-K. Choi. This is an open access article distributed under the Creative Commons Attribution License (the “License”), which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited. Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License. https://creativecommons.org/licenses/by/4.0/
Abstract
In this paper, a nonlinear finite element (FE) analysis of high-performance hybrid system (HPHS) beam-column connections is presented. The detailed experimental results of the ten half-scale hybrid connections with limited seismic detailing have been discussed in a different paper. However, due to the inherent complexity of HPHS beam-column joints and the unique features of the tested specimens, the experimental study was not comprehensive enough. The new connection (HPHS) detail suggested in this study is characterized by ductile connection, steel connectors, and engineered cementitious composite (ECC) which is a kind of high-performance fiber reinforced cement composite with multiple fine cracks (HPFRCCs). Therefore, in this paper, FE analysis results are compared with experimental results from the cycle tests of the two specimens (RC and PC) to assess model accuracy, and detailed model descriptions are presented, including the determination of stiffness and strength. The critical parameters influencing the joint’s behavior are the axial load on column, beam connection steel plate length, inner bolt stress contribution, and plastic hinge area.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer