1. Introduction
An AWG generates liquid water from the ambient air humidity [1]. This device is a water harvester, which condenses the water vapor by cooling the air below its dew point [1]. The dew point is the temperature at which the air water vapor reaches saturation and it is condensed into dew [2]. Under constant atmospheric pressure, the dew point depends only on the Relative Humidity (RH) and the ambient temperature (Tamb ) [3]. The conventional AWG systems have been studied as a strategy to face water scarcity problems without power or size constraints for agricultural or domestic purposes [1,4,5,6,7,8]. A Portable Atmospheric Water Generator (PAWG) is an AWG device characterized by a smaller size, lighter weight, and lower power consumption than a conventional AWG [9]. The PAWG would be useful for cyclists, hikers, or expeditionaries because they can transport their water source [10]. Therefore, a PAWG must be designed under energy and size constraints for people who perform activities in outdoor environments [10]. Furthermore, a self-sustaining PAWG based on water and solar harvesters has been explored to increase the device and user autonomy of energy and water sources, respectively [11].
The AWG devices could be based on the vapor compression cycle, a Thermoelectric Cooler (TEC), or adsorption/absorption refrigeration [1]. However, the PAWGs reported in the analyzed literature are based on TEC devices. In an AWG system based on a TEC, the dew point is reached by cooling the air using the thermoelectric cooling effect (or Peltier effect) [12]. The general structure of a PAWG is shown in Figure 1. In a PAWG device, the TEC transforms electric energy into a temperature difference by the thermoelectric cooling effect, which consists of heat transfer from the cool side to the hot one [13]. This heat transfer could be optimized by the use of heat sinks on both sides of the cooler [14]. In this paper, the inside heat sink will be referred to as the water condenser element because the water vapor condensation takes place in this heat sink, and the system composed of the TEC and its heat sinks will be referred to as the extended TEC. Furthermore, the airflow (inside or outside) could be produced by natural or forced convection. Typically in forced convection, the airflow is forced in both the outside and inside of the AWG. Moreover, the outside and inside airflow is produced by an active heat sink and a semi-closed cooling cabin with inlet and/or outlet fans, respectively.
Several PAWG prototypes with embedded TECs have been developed in the literature [9,10,11,12,14]. In [9,10], the authors designed a portable AWG with two TEC modules. The system experimentally investigated the effect of the inlet airflow rate andRH. The results showed that the amount of water increased with the risingRH and inlet airflow rate. In [11], a PWAG with two TECs to sustain young plants in drier periods was presented. The authors evaluated an autonomous solar photovoltaic system and a control algorithm to optimize energy consumption versus generated water under different environmental conditions. They found that the specific power density of the PAWG must be increased to increase the volume of water condensed. Furthermore, they found that this trend presents a saturation phenomenon when theRH is too low. In [12], the authors developed a PAWG with ten Peltier modules. This research found a direct correlation between the water generated and the surface area of the water condensation element. In their prototype, an increase in the area of the water condenser element of 1150% increased the generated water by 81%. In [14], the authors designed a PAWG using four TECs. They analyzed the effect of the TEC current and the use of an intake fan in the water generation. The results showed that the increase of the voltage difference across the TECs increased the water generation rates but increased the energy consumption. Additionally, in [15], a PAWG model based on an electric analogy was proposed, which was validated experimentally. Their prototype was optimized by parameter tuning under experimental conditions. The analyzed parameters were the supply voltages of the TEC and inlet fan. Moreover, in [16], a computer-aided design approach based on computational fluid dynamics was presented. The authors optimized the cooling cabin considering physical parameters such as temperature,RH , airflow magnitude, pressure, the form of airflow, and water productivity. Finally, in [17], a low-power and low-cost PAWG was proposed; the system is shown in Figure 2. The authors developed a low-cost control device, which could control the main parameters of the PAWG prototype (i.e., the supply voltages of the TEC, active heat sink, and inlet fan). This approach allows optimizing the PAWG prototype by dynamic parametric tuning. Considering the presented State-of-the-Art (SoA), the main factors involved in the design and optimization of PAWG based on TECs are summarized in Figure 3. Furthermore, the main drawback of published PAWGs based on TEC technologies is their high energy consumption. Moreover, the main involved variables are well identified. However, their interaction is not well known. Besides, the optimization of the PAWG parameters in the design phase and the prototype phase has been little explored, especially for low-power devices.
In this paper, the experimental parameter tuning of a PAWG prototype developed in [17] is presented. In this process, the temperature and airflow on the cooling cabin are tuned to maximize the generated water and the system performance (i.e., the ratio between the generated water and consumed power in mL/Wh). The results show the existence of the optimum value of the tuned parameters (i.e., the supply voltage of the TEC and the inlet fan) under a constant value of theRH . The outline of the paper is as follows. The AWG prototype is shown in Section 2. The parameter tuning process is described in Section 3. The results and their analysis are presented in Section 4. Finally, the conclusions are given in Section 6.
2. AWG Prototype
The AWG prototype analyzed in this paper consists of an extended TEC and a cooling cabin with an inlet fan. The thermoelectric cooler is the TEC1-12706, which uses bismuth telluride (Bi2Te3) as the thermoelectric material, having 127 P-N couples, a maximum voltage (Vmax) of 14.4 V, and a maximum current (Imax) of 6.4 A. The active heat sink is a Central Processing Unit (CPU) air cooler with dimensions of 12.0 cm × 8.1 cm × 12.25 cm, which uses heat core touch technology with three ultra-efficient thermal heat pipes, a thermal design power up to 120 W, and a Pulse-Width Modulation (PWM) high-pressure fan. This element is placed on the hot zone of the thermoelectric cooler to provide heat dissipation and allows temperatures on the cold zone below the dew point.
In the cooling cabin, the water condenser element is placed, and the ventilation system is located in a physical assembly. The water condenser element is a specific device, whose geometric structure was developed to facilitate the water condensation process in the AWG prototype [17]. It is composed of five aluminum sheets with vertical slots, which are placed on an aluminum square base with horizontal grooves by pressure coupling, as shown in Figure 4. The ventilation system consists of a 5.0 cm × 1.1 cm × 5.0 cm DC fan with a nominal power of 1.2 W (0.1 A at 12 V), which provides constant airflow to the water condenser element. The physical assembly is a 10.65 cm × 6.70 cm × 7.05 cm structure that has a cooling space to place the water condenser element, an airflow inlet that physically supports the ventilation system fan, and an air outlet hole. Furthermore, this part collects the condensed water through the water outlet hole and provides physical stability to the prototype, as shown in Figure 5. The AWG final prototype is shown in Figure 6. It groups the heat sink, the thermoelectric cooler, and the cooling cabin with plastic ties placed on the heat sink and heat sink brackets. Moreover, this prototype includes a cubic base and a container for collecting water.
3. Description and Results of the Parameter Tuning Process
The amount of water generated by an AWG prototype depends on multiple factors, as shown in Figure 3. On the one hand, theRHandTambare uncontrolled environmental variables. On the other hand, the cooling cabin and water condenser element dimensions are design variables, which could be optimized only in the design phase of the AWG system. Therefore, the supply voltages of the TEC, the inlet fan, and the active heat sink (i.e.,VC,VFAN, andVH) are the only system parameters that can be optimized in the proposed AWG prototype. The tests were performed with a fixed value ofVH(i.e., 12 V) and under quasi-fixed environmental conditions. Therefore,VCestablishes the condenser element temperature (Tcold), andVFANdetermines the cooling cabin airflow (ACC ). The Figure of Merit (FoM) is the quantity used to characterize the performance of a device related to its alternatives. The performance of the PAWG proposed in [17] was analyzed through the FoM defined as:
Psys=wg/h PAWGmLmLhhW
wherewg/his the generated water rate in mL/h andPAWGis the power consumed by the PAWG in W, which are given by:
wg/h=wAWGt
PAWG=PH+PFAN+PC
wherewAWGis the generated water during the test, t is the test time,PHis the power consumed by the active heat sink,PFANis the power consumed by the inlet fan, andPCis the power consumed by TEC module.
However, in the analyzed literature, only one FoM is not well established. Furthermore, sometimes,wg/horPAWGare reported as the main FoMs. UsingPsysandwg/has the tuning goals, the values of the system variables were examined in sixteen tests. The developed process consists of an experimental evaluation of the goals under parametric sweeps of the voltage variables. In this process,VCandVFANwere swept, and their optimum values were found. TheVC parametric sweep was made from 2 V to 14 V, with steps of 4 V, and the parametric sweep was made from 3 V to 12 V, with steps of 3 V. The proposed test grid is shown in Figure 7.
TheVCvoltage is related to the specific power density of the extended TEC (SPDEC), which is given by:
SPDEC=PEC VEC
whereVECandPECare the volume and consumed power of the extended TEC, respectively. In the prototype, theVECvalue is0.1319m3(0.0118m3,0.048m3, and0.072m3are the volumes of the active heat sink, TEC, and water condenser element, respectively).PECis calculated as:
PEC=PH+PC
wherePHis the power consumed by the active heat sink andPCis the power consumed by the thermoelectric cooler.PHhas a fixed power value of 2.4 ± 0.0648 W (i.e., 12 ± 0.0050 V @ 0.2 ± 0.0054 A), andPCis calculated asPC=VC ICfrom the measured voltage and current values of the TEC module operating in the PAWG device (i.e.,VCandIC, respectively). The empirical data and the calculated values ofPC are plotted in Figure 8. Finally,SPDECis calculated based onPECandVEC , and the results are summarized in Table 1.
To quantify this relationship betweenVFANandACC, an empirical characterization of the system is required. However, assuming a constant torque of the inlet fan, the maximumACCvalue could be estimated as:
ACCmax=AnVFAN VFANn
whereAnandVFANnare the nominal airflow and voltage of the inlet fan, respectively. We searched the datasheet of our low-cost inlet fan (i.e., Supertone VN-251, 12V @ 0.1 A, with seven blades and 50 mm × 50 mm × 10 mm in size); however, it was not available at the time of this report. As a rough approximation,ACCmax is calculated based on the datasheet of the DC0501012H2B [18], which has the same size, electrical specification, and geometrical variables (i.e., the number and shape of blades) as our fan. The estimated values ofACCmax are summarized in Table 1.
At the beginning of each test, we measured with a digital multimeter (i.e., Fluke 45) the DC voltage and current of the inlet fan (i.e.,VFANandIFAN), the DC voltage and current of the active heat sink (i.e.,VHandIH), and the DC voltage and current of the thermoelectric cooler (i.e.,VCandIC . The Fluke 45 has an accuracy as described in [19]. During the tests, the PAWG used an energy recovery system to improve its performance; this system harvest and conducts the cool airflow through a tube from the air outlet hole to the active heat sink to decrease its external temperature, as shown in Figure 9a. Furthermore, as is shown in Figure 9b,c, the PAWG was equipped with type-K thermocouples to measure the physical variables related to the extended TEC, which are the temperatures of the active heat sink (Thot) and the water condenser element (Tcold). The thermocouple analog voltages were measured with the NI USB-621 data acquisition module. The uncertainty of this measurement isΔT = ±4.35°C, which is given by the sum of the thermocouple accuracy (i.e., ±2.2° C or ±0.75% [20]) and the acquisition module accuracy (i.e., ±2.15° C) [21]. The acquisition module accuracy is given by:
ΔT=88μV41μVV°C°C=2.15°C
where 88 μV is the full-scale accuracy of the USB-621 device (considering a scale between −0.2 V and 0.2 V [22]) and 41 μV/° C is the thermocouple sensitivity of a standard type-K thermocouple at room temperature [23]. In these measures, the data were acquired on a computer using SignalExpress™ software with a period rate of a second during the test time (i.e., an hour). It is important to note that the cooling cabin was designed to allow the pass of the thermocouple of the water condenser element through the thermocouple slot shown in Figure 5.
Moreover, and during the test, the environmental conditions (RHandTamb ) were measured with the BME280 sensor, which was placed 12 cm from the PAWG device, as shown in Figure 9d. This sensor transmits one data measurement each second by a serial communication protocol (i.e., I2C) to an Arduino Mega 2560 board, which displays the data in the serial monitor of the Arduino integrated development environment. The resulting data have an error ofΔRH= ±3% andΔTamb= ±1° C under nominal operation [24]. Finally, at the end of each test, the amount of water generated by the PAWG (wAWG ) was measured using a syringe of 5 mL with an accuracy of ±0.1 mL. It is important to note that during Tests 1, 2, 5, 6, and 9, frost was generated in the water condenser element, as shown in Figure 10. In these cases, the amount of generated water was measured after the frost had thawed. Each test was developed for an hour, which was measured by an alarm set in a standard computer clock, and we estimated an error of one minute produced by the time gap between the alarm clock alert and the full disconnection of the system by the researcher.
The overall system measurements with their uncertainties are summarized in Table 2. It is important to note that even though the tests were performed in a laboratory room without any control of the environmental variables, these variables were very similar to each other. Furthermore, they were characterized by a low Standard deviation (Std. dev.) over the mean (i.e., a meanTambof 19.71°C and a meanRHof 60.40%, with an Std. dev. of 0.64° C and 2.57%, respectively). Finally, the PAWG FoMs were calculated based on the measured data and Equations (1) and (2). Furthermore, their uncertainties were calculated through the error propagation, and they are given by:
ΔP(H,C,FAN)=P(H,C,FAN)ΔV(H,C,FAN)V(H,C,FAN)2+ΔI(H,C,FAN)I(H,C,FAN)2
ΔPAWG=ΔPH2+ΔPFAN2+ΔPC2
Δwg/h=wg/hΔwAWGwAWG2+Δtt2
ΔPsys=PsysΔwg/hwg/h2+ΔPAWGPAWG2
whereΔX is the uncertainty of the variable X. The resulting FoMs and their uncertainties are summarized in Table 3.
4. Parameter Tuning Analysis
A color map with a blue scale is used to represent the consumed power, the generated water rate, and the system performance, where darker colors mean higher values. These FoMs are presented in Figure 11, Figure 12 and Figure 13. According to the presented results, the maximum power consumed by the prototype was 53.88 W in Test 4, using the maximum voltage ratings of the devices, as shown in Figure 11. The maximum generated water rate was obtained in Tests 4 and 8 (3.3 mL/h), followed by Tests 7 and 11 (3.0 mL/h and 2.7 mL/h, respectively), as shown in Figure 12. Additionally, the highest system performance was 0.22 mL/Wh in Test 11, followed by 0.20 mL/W in Test 12.
According to the mentioned swept test results, we found two optimal operating points of the prototype. The first point maximized the generated water rate at 3.3 mL/h using aVCandVFANof 10 V and 12 V, respectively. Although this value was obtained in two tests (4 and 8), Test 8 was selected because it had the lowest consumed power. The second operating point maximized the system performance to 0.22 mL/Wh with a water generation of approximately 2.7 mL/h. This optimum operation was achieved using aVCandVFANof 6 V and 9 V, respectively.
5. Comparison of the Proposed PAWG with the SoA
The results showed a maximum system performance of 0.22 mL/Wh. In Table 4, the proposed PAWG is compared with the SoA through the devices’ FoMs. Furthermore, it summarizes other relevant characteristics of the compared prototypes, such as the size, the volume, the test conditions, the number of TECs, and the consumed power.
The highestPsys was 0.5 mL/Wh, which was reported in [14], and the lowestPsys was 0.04 mL/Wh, which was reported in [12]. Although our device presented aPsysbelow the mean (0.27 mL/Wh), it had the lowest (12.5 W), which is 8.5% of the mean (67.9 W). Furthermore, the proposed prototype is portable, simple, and low-cost because of its volume and simple topology with only one TEC module. However, the proposed PAWG design must be improved to increase the PAWGPsys. For instance, the cooling cabin design could be improved.
6. Conclusions This paper presents an experimental parameter tuning process. The results show the existence of two optimal operation points of the analyzed PAWG under a constant value of relative humidity. One optimum point maximizes the amount of generated water, and the other maximizes the system performance. The resulting FoMs of the developed PAWG prototype are 0.33 mL/h of generated water and 0.22 mL/Wh for the system performance. Furthermore, these optimum points are not located in the extreme values of the analyzed tuning parameters. Therefore, to guarantee optimum operation under varying humidity conditions, an automatic tuning process could be explored. From the comparison of the developed PAWG with the SoA, the system performance is acceptable with a very low power consumption (12.5 W); therefore, it could be easily powered by an energy harvester device.
Figure 1. Structure of an Portable Atmospheric Water Generator (PAWG) prototype based on Thermoelectric Cooler (TEC).
Figure 2. PAWG prototype [17]. (a) right side view; (b) left side view; (c) rear view.
Figure 3. Factors affecting water generation in an Atmospheric Water Generator (AWG) system based on a thermoelectric cooler.
Figure 8. Experimental data of the thermoelectric cooler TEC1-12706 operating in the PAWG. (a) Current vs. voltage plot; (b) Power vs. voltage plot.
Figure 9. Test conditions (a) air outlet tube used; (b) thermocouple heat sink location; (c) thermocouple location of the water condenser element; (d) BME280 sensor location.
Physical Variable | Test-Grid Axes | Type | Test-Grid Scale Relationship | |||
---|---|---|---|---|---|---|
VC(V) | X-axis | Experimental | 2.0 | 6.0 | 10.0 | 14.0 |
SPDEC(W/m3) | X-axis | Calculated | 25.0 | 84.2 | 203.9 | 375.9 |
VFAN(V) | Y-axis | Experimental | 3.0 | 6.0 | 9.0 | 12.0 |
ACCmax* (ft3/min) | Y-axis | Estimated | 3.2 | 6.4 | 9.5 | 12.7 |
* Estimated using An = 12.7 ft3/min andVFANn = 12 V.
Tests Number | VC(V) | IC(A) | VFAN(V) | IFAN(A) | wAWG a (mL) | t b(h) | AverageTamb c (°C) | AverageRH d(%) | AverageThot e (°C) | AverageTcold e (°C) |
---|---|---|---|---|---|---|---|---|---|---|
1 | 14.00 ± 0.0055 | 3.62 ± 0.0122 | 3.01 ± 0.0028 | 0.03 ± 0.00004 | 0.4 | 1 | 20.11 | 56.90 | 25.76 | −10.88 |
2 | 14.00 ± 0.0055 | 3.61 ± 0.0122 | 6.00 ± 0.0035 | 0.06 ± 0.00005 | 1.8 | 1 | 20.29 | 58.67 | 25.20 | −5.69 |
3 | 14.00 ± 0.0055 | 3.58 ± 0.0122 | 9.00 ± 0.0043 | 0.07 ± 0.00006 | 1.9 | 1 | 19.66 | 60.36 | 26.01 | −0.28 |
4 | 14.00 ± 0.0055 | 3.60 ± 0.0122 | 12.00 ± 0.0050 | 0.09 ± 0.00007 | 3.3 | 1 | 18.79 | 62.65 | 24.93 | 5.52 |
5 | 10.00 ± 0.0045 | 2.63 ± 0.0103 | 3.01 ± 0.0028 | 0.03 ± 0.00004 | 0.4 | 1 | 19.86 | 57.31 | 22.75 | −12.21 |
6 | 10.00 ± 0.0045 | 2.62 ± 0.0102 | 6.00 ± 0.0035 | 0.06 ± 0.00005 | 1.9 | 1 | 20.04 | 61.19 | 22.98 | −6.31 |
7 | 10.00 ± 0.0045 | 2.65 ± 0.0103 | 9.00 ± 0.0043 | 0.07 ± 0.00006 | 3.0 | 1 | 20.54 | 61.54 | 23.47 | −1.63 |
8 | 10.00 ± 0.0045 | 2.64 ± 0.0103 | 12.00 ± 0.0050 | 0.09 ± 0.00007 | 3.3 | 1 | 19.24 | 60.29 | 23.02 | 0.48 |
9 | 6.00 ± 0.0035 | 1.53 ± 0.0081 | 3.01 ± 0.0028 | 0.03 ± 0.00004 | 0.4 | 1 | 19.59 | 56.94 | 21.64 | −5.53 |
10 | 6.01 ± 0.0035 | 1.57 ± 0.0081 | 6.00 ± 0.0035 | 0.06 ± 0.00005 | 1.1 | 1 | 19.93 | 61.75 | 21.46 | −0.83 |
11 | 6.00 ± 0.0035 | 1.58 ± 0.0082 | 9.00 ± 0.0043 | 0.07 ± 0.00006 | 2.7 | 1 | 20.64 | 62.14 | 21.55 | 2.77 |
12 | 5.99 ± 0.0035 | 1.58 ± 0.0082 | 12.00 ± 0.0050 | 0.09 ± 0.00007 | 2.6 | 1 | 19.41 | 59.43 | 21.27 | 4.09 |
13 | 2.00 ± 0.0025 | 0.47 ± 0.0059 | 2.99 ± 0.0027 | 0.03 ± 0.00004 | 0.1 | 1 | 19.47 | 56.34 | 19.50 | 12.40 |
14 | 2.00 ± 0.0025 | 0.45 ± 0.0059 | 6.00 ± 0.0035 | 0.06 ± 0.00005 | 0.1 | 1 | 19.48 | 62.62 | 20.82 | 11.95 |
15 | 2.00 ± 0.0025 | 0.47 ± 0.0059 | 9.00 ± 0.0043 | 0.07 ± 0.00006 | 0.1 | 1 | 20.16 | 64.54 | 20.50 | 12.54 |
16 | 2.00 ± 0.0025 | 0.49 ± 0.0060 | 12.00 ± 0.0050 | 0.08 ± 0.00006 | 0.1 | 1 | 18.13 | 63.76 | 21.86 | 14.31 |
a(±0.1 mL),b(±0.0167 h),c(±1°C),d (±3%), e (±4.35° C).
Tests Number | PC(W) | PFAN(W) | PAWGa(W) | wg/h(mL/h) | Psys(mL/Wh) |
---|---|---|---|---|---|
1 | 50.68 ± 0.1725 | 0.09 ± 0.0001 | 53.17 ± 0.1843 | 0.4 ± 0.1002 | 0.01 ± 0.0019 |
2 | 50.54 ± 0.1019 | 0.36 ± 0.0002 | 53.30 ± 0.1207 | 1.8 ± 0.1044 | 0.03 ± 0.0020 |
3 | 50.12 ± 0.1010 | 0.63 ± 0.0004 | 53.15 ± 0.1200 | 1.9 ± 0.1049 | 0.04 ± 0.0020 |
4 | 50.40 ± 0.1016 | 1.08 ± 0.0006 | 53.88 ± 0.1205 | 3.3 ± 0.1141 | 0.06 ± 0.0021 |
5 | 26.30 ± 0.0530 | 0.09 ± 0.0001 | 28.79 ± 0.0837 | 0.4 ± 0.1002 | 0.01 ± 0.0035 |
6 | 26.20 ± 0.0528 | 0.36 ± 0.0002 | 28.96 ± 0.0836 | 1.9 ± 0.1049 | 0.07 ± 0.0036 |
7 | 26.50 ± 0.0534 | 0.63 ± 0.0004 | 29.53 ± 0.0840 | 3.0 ± 0.1118 | 0.10 ± 0.0038 |
8 | 26.40 ± 0.0532 | 1.08 ± 0.0006 | 29.88 ± 0.0839 | 3.3 ± 0.1141 | 0.11 ± 0.0038 |
9 | 9.18 ± 0.0185 | 0.09 ± 0.0001 | 11.67 ± 0.0674 | 0.4 ± 0.1002 | 0.03 ± 0.0086 |
10 | 9.44 ± 0.0190 | 0.36 ± 0.0002 | 12.20 ± 0.0675 | 1.1 ± 0.1017 | 0.09 ± 0.0084 |
11 | 9.48 ± 0.0191 | 0.63 ± 0.0004 | 12.51 ± 0.0676 | 2.7 ± 0.1097 | 0.22 ± 0.0088 |
12 | 9.46 ± 0.0191 | 1.08 ± 0.0006 | 12.94 ± 0.0676 | 2.6 ± 0.1090 | 0.20 ± 0.0085 |
13 | 0.94 ± 0.0019 | 0.09 ± 0.0001 | 3.43 ± 0.0648 | 0.1 ± 0.1000 | 0.03 ± 0.0292 |
14 | 0.90 ± 0.0018 | 0.36 ± 0.0002 | 3.66 ± 0.0648 | 0.1 ± 0.1000 | 0.03 ± 0.0273 |
15 | 0.94 ± 0.0019 | 0.63 ± 0.0004 | 3.97 ± 0.0648 | 0.1 ± 0.1000 | 0.03 ± 0.0252 |
16 | 0.98 ± 0.0020 | 0.96 ± 0.0005 | 4.34 ± 0.0648 | 0.1 ± 0.1000 | 0.02 ± 0.0230 |
aCalculated using aPH of 2.4 ± 0.0648 W.
Ref. | Publication Year | Tamb(°C) | RH(%) | PAWG Size L × H × W (m) | PAWG Volume (m3) | TEC Number | PAWG(W) | wg/h(mL/h) | Psys (mL/Wh) |
---|---|---|---|---|---|---|---|---|---|
[12] | 2017 | 30.0 | 63.0 | 0.7 × 0.40 × 0.45 | 0.1260 | 10 | 135.0 | 5 | 0.04 |
[11] | 2013 | 18.0 | 60.0 | unknown | unknown | 2 | 50.0 | 4 | 0.08 |
[9,10] | 2017, 2020 | 24.3 | 67.8 | 0.46 × 0.14 × 0.15 | 0.0097 | 2 | 52.3 | 11.2 | 0.21 |
This work (Test 11) | 2019 | 20.6 | 62.1 | 0.12 × 0.10 × 0.27 | 0.0032 | 1 | 12.5 | 2.7 | 0.22 |
[15] | 2002 | 27.0 | 82.0 | 0.20 × 0.18 × 0.30 | 0.0108 | 3 | 100.0 | 40.3 | 0.40 |
[16] | 2016 | 25.3 | 60.0 | 0.35 × 0.10 × 0.10 | 0.0035 | 2 | 65.5 | 27.9 | 0.43 |
[14] | 2018 | 30.0 | 60.0 | 0.43 × 0.34 × 0.17 | 0.0249 | 4 | 60.0 | 30 | 0.50 |
Author Contributions
Conceptualization, all authors; methodology, I.C. and C.-I.P.-R.; validation, all authors; analysis, all authors; writing, original draft preparation, all authors; writing, review and editing, all authors; visualization, all authors; supervision, C.-I.P.-R., M.P. and A.F. All authors read and agreed to the published version of the manuscript.
Funding
This research received no external funding.
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
The data presented in this study are available on request from the corresponding author.
Acknowledgments
The authors would like to thank the Electronics Department and Electronics laboratory of the Pontificia Universidad Javeriana, for providing the required resources to conduct this study. Additionally, the authors would like to thank the Pontificia Universidad Javeriana for financial support in the publication of the results of this study.
Conflicts of Interest
The authors declare no conflict of interest.
Abbreviations
The following abbreviations are used in this manuscript:
AWG | Atmospheric Water Generator |
PAWG | Portable Atmospheric Water Generator |
CPU | Central Processing Unit |
FoM | Figure of Merit |
PWM | Pulse-Width Modulation |
RH | Relative Humidity |
TEC | Thermoelectric Cooler |
SoA | State-of-the-Art |
Std. dev. | Standard deviation |
1. Tu, R.; Hwang, Y. Reviews of atmospheric water harvesting technologies. Energy 2020, 117630.
2. Martines, E.; Lira, L. Cálculo de la Temperatura de Punto de Rocío a Diferentes Valores de Presión; Simposio de Metrología: Santiago de Querétaro, Mexico, 2008; Volume 22.
3. Lawrence, M.G. The relationship between relative humidity and the dewpoint temperature in moist air: A simple conversion and applications. Bull. Am. Meteorol. Soc. 2005, 86, 225-234.
4. Pereira, L.S.; Cordery, I.; Iacovides, I. Coping with Water Scarcity: Addressing the Challenges; Springer: Berlin/Heidelberg, Germany, 2009.
5. Molden, D. Water for Food Water for Life: A Comprehensive Assessment of Water Management in Agriculture; Routledge: London, UK, 2013.
6. Cerro, C. Developing solutions for dealing with water and food scarcity: Atmospheric water generator and urban farm tower. In Proceedings of the 2018 IEEE Advances in Science and Engineering Technology International Conferences (ASET), Abu Dhabi, UAE, 6 February-5 April 2018; pp. 1-6.
7. Pontious, K.; Weidner, B.; Guerin, N.; Dates, A.; Pierrakos, O.; Altaii, K. Design of an atmospheric water generator: Harvesting water out of thin air. In Proceedings of the 2016 IEEE Systems and Information Engineering Design Symposium (SIEDS), Charlottesville, VA, USA, 29 April 2016; pp. 6-11.
8. Sondergeld, A.; Wang, G.; Dutta, A. Modeling the Viability of a Refrigeration-Based Atmospheric Water Generator under the Present-Day Climate. In Proceedings of the 2019 IEEE Global Humanitarian Technology Conference (GHTC), Seattle, WA, USA, 17-20 October 2019; pp. 1-5.
9. Liu, S.; He, W.; Hu, D.; Lv, S.; Chen, D.; Wu, X.; Xu, F.; Li, S. Experimental analysis of a portable atmospheric water generator by thermoelectric cooling method. Energy Procedia 2017, 142, 1609-1614.
10. He, W.; Yu, P.; Hu, Z.; Lv, S.; Qin, M.; Yu, C. Experimental Study and Performance Analysis of a Portable Atmospheric Water Generator. Energies 2020, 13, 73.
11. Muñoz-García, M.; Moreda, G.; Raga-Arroyo, M.; Marín-González, O. Water harvesting for young trees using Peltier modules powered by photovoltaic solar energy. Comput. Electron. Agric. 2013, 93, 60-67.
12. Joshi, V.; Joshi, V.; Kothari, H.; Mahajan, M.; Chaudhari, M.; Sant, K. Experimental investigations on a portable fresh water generator using a thermoelectric cooler. Energy Procedia 2017, 109, 161-166.
13. Zhao, D.; Tan, G. A review of thermoelectric cooling: Materials, modeling and applications. Appl. Therm. Eng. 2014, 66, 15-24.
14. Shourideh, A.H.; Ajram, W.B.; Al Lami, J.; Haggag, S.; Mansouri, A. A comprehensive study of an atmospheric water generator using Peltier effect. Therm. Sci. Eng. Prog. 2018, 6, 14-26.
15. Vián, J.; Astrain, D.; Domınguez, M. Numerical modelling and a design of a thermoelectric dehumidifier. Appl. Therm. Eng. 2002, 22, 407-422.
16. Suryaningsih, S.; Nurhilal, O. Optimal design of an atmospheric water generator (AWG) based on thermo-electric cooler (TEC) for drought in rural area. In AIP Conference Proceedings; AIP Publishing LLC: Melville, NY, USA, 2016; Volume 1712, p. 030009.
17. Casallas, I.; Paéz, C.; Fajardo, A. Recolección de Agua Líquida por Condensación de Humedad Atmosférica Usando el Efecto Peltier; Pontificia Universidad Javeriana: Bogota, Colombia, 2019.
18. DC FANS-50 × 50 × 10 mm. Available online: http://www.wakefieldvette.com/Portals/0/DC%20Fans/DC%20FANS%20Wakefield%20Vette%20Data%20Sheet_rev%20A.pdf (accessed on 28 December 2020).
19. Bench Multimeters, 45 Dual Display Multimeter. FLUKE. Available online: http://www.smart-inc.com.tw/uploads/root/fluke45.pdf (accessed on 28 December 2020).
20. Type K Thermocouple. REOTEMP. Available online: https://www.thermocoupleinfo.com/type-k-thermocouple.htm (accessed on 28 December 2020).
21. Calculating Thermocouple Measurement Error in DMM/Switch Temperature Measurement Systems. National Instruments. Available online: https://knowledge.ni.com/KnowledgeArticleDetails?id=kA03q000000x0dBCAQ&l=es-CO (accessed on 28 December 2020).
22. NI USB-621x Specification. National Instruments. Available online: http://www.dept.aoe.vt.edu/~devenpor/aoe3054/manual/inst3/USB-6211.pdf (accessed on 28 December 2020).
23. Duff, M.; Towey, J. Two Ways to Measure Temperature Using Thermocouples Feature Simplicity, Accuracy, and Flexibility. Analog Dialogue. 2010. Available online: https://www.analog.com/en/analog-dialogue/articles/measuring-temp-using-thermocouples.html (accessed on 28 December 2020).
24. BME280, Combined Humidity and Pressure Sensor. BOSCH. Available online: https://www.bosch-sensortec.com/media/boschsensortec/downloads/datasheets/bst-bme280-ds002.pdf (accessed on 28 December 2020).
Ingrid Casallas
,
Manuel Pérez
,
Arturo Fajardo
* and
Carlos-Ivan Paez-Rueda
Department of Electronic Engineering, Pontificia Universidad Javeriana, Bogotá 110311, Colombia
*Author to whom correspondence should be addressed.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
© 2021. This work is licensed under http://creativecommons.org/licenses/by/3.0/ (the “License”). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.
Abstract
Atmospheric Water Generators (AWG) are a promising technology solution to the water scarcity in the world. However, their main drawback is the high power consumption. This paper presents the experimental optimization process of a Portable Atmospheric Water Generator (PAWG) prototype based on a thermometric cooler. This process was developed by an exhaustive search of the experimental solution space, which was generated by parametric sweeps of two parameters (i.e., control voltages in the PAWG), which are related to the power consumption of the PAWG and the physical variables involved in the water condensation process (i.e., the airflow and the temperature on the water condenser element). As a result, we found the existence of two optimal operation points under a constant value of relative humidity; one of them maximizes the amount of water generated, and the other one maximizes the system performance (i.e., the ratio between the generated water and consumed power in mL/Wh). The resulting Figures of Merit (FoMs) of the PAWG prototype were 0.33 mL/h of generated water and 0.22 mL/Wh for the system performance.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer