This paper describes the results of a comprehensive and ongoing project to control unsteady fluid-dynamic behaviour and associated effects at Svorka hydro power plant (25 MW, 260 m, 600 rpm), operated by Statkraft in Norway. This Francis unit had an original air admission system installed on the draft tube wall and turbine shaft. However, these systems did not perform satisfactorily to prevent high intensity pressure fluctuations due to vortex rope at part load. To mitigate them, a complementary draft tube water injection system, designed by Flow Design Bureau AS (FDB), was installed in 2010. Moreover, the runner suffered from cavitation pitting on the blades and a measuring campaign with several accelerometers and an acoustic emission sensor concluded that the unit was susceptible to high load cavitation erosion. Given the complexity of the turbine flow, it was decided to install four transparent acrylic glass windows on the draft tube, allowing for visual access to the runner blades and outlet flow. To evaluate the influence of the draft tube injection system on the cavitation behaviour, a series of measurements of cavitation intensity were carried out. High frequency data from the sensors were processed with demodulation techniques at various expected modulation frequencies, particularly the blade passing frequency and the frequency of the draft tube vortex rope. Furthermore, the pressure pulsations were measured and quantified with pressure sensors on the draft tube wall. The results indicate that draft tube water injection has little or no effect on the measured cavitation intensity in the runner. However, other aspects of the machine, including the seasonal and daily variation of the submergence level, must be taken into consideration. In conclusion, it appears that additional long-term observations are needed to clarify the global dynamic behaviour along the entire operating range.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
Details
1 Norwegian University of Science and Technology, Trondheim, Norway; Flow Design Bureau AS, Stavanger, Norway
2 Flow Design Bureau AS, Stavanger, Norway
3 Universitat Politècnica de Catalunya, Barcelona, Spain
4 Norwegian University of Science and Technology, Trondheim, Norway