Abstract

All Grounding planning of a substation is important and various design applications are available using calculation uniform soil resistivity, even though actual resistivity data measured is more than one layer. This is caused by limited availability of the application in processing data only for resistivity one layer. Substation grounding grid application (ASPG) 1.0 can be used for designing grid grounding. The ASPG was developed from Lab View software and has ability to data process for resistivity two-layer that to refer IEEE Std. 80-2013. Grid grounding resistance is considering a combination of grid conductor and ground conductor. This paper discusses the calculation of the magnitude of substation grid grounding using formulas developed by Schwarz, Sulivan and Sunde. The design result obtained is more accurate in substitute resistivity for resistivity two-layer model and calculation grounding resistance substation.

Details

Title
Design grounding grid resistance of substation for two soil layer model
Author
Hardi, Surya 1 ; Nasution, Azwar 2 ; Harahap, R 1 ; Fitriani, Ayu 1 

 Department of Electrical Engineering, Universitas Sumatera Utara , Medan , Indonesia 
 Department of Electrical Engineering BBPLK Medan , Indonesia 
First page
012033
Publication year
2022
Publication date
Feb 2022
Publisher
IOP Publishing
ISSN
17426588
e-ISSN
17426596
Source type
Scholarly Journal
Language of publication
English
ProQuest document ID
2635728291
Copyright
Published under licence by IOP Publishing Ltd. This work is published under http://creativecommons.org/licenses/by/3.0/ (the “License”). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.