1. Introduction
Indoor environmental quality (IEQ) depends on the quality of the thermal environment, acoustic environment, indoor air quality (IAQ), and visual environment [1]. IEQ is a primary concern because people spend a significant portion of their time in buildings [2]. A growing body of studies has shown the influence of IEQ on occupants’ health, comfort, and well-being, at homes, offices, and schools [3,4].
In the last twenty years, it has been shown that poor schools’ IEQ can affect children’s health. The study of Gaffin et al. [5] showed that exposure to a concentration of NO2 greater than 8 ppb in urban American schools was associated with respiratory airflow obstruction in children. Meanwhile, a growing body of studies showed that low indoor environmental quality in schools can impact children’s school performance. The study of Wargocki et al. [6] showed that improved classroom ventilation, as indicated by reduced carbon dioxide (CO2) concentrations from 2100 to 900 ppm, resulted in improved children’s academic performance by 12%, while the performance was increased by 20% when classroom temperatures were reduced from 30 to 20 °C [7]. Most of the work published to date examined the effects of one parameter, and no relationships were created between the quality of the indoor environment and health effects and children’s school performance. One reason is the complexity and cost of performing measurements. The other is the lack of a rating scheme for IEQ. The latter is needed to take into account interactions between different parameters and their influence on children.
Recently, Wei et al. [8] reviewed parameters measured to characterize IEQ in offices and hotels. Nearly 100 parameters were identified, but no common rating scheme was identified for IEQ. Consequently, the TAIL (Thermal, Acoustic, IAQ, Lighting) rating scheme was developed including twelve IEQ parameters [9]. Moreover, the method to predict the parameters included in TAIL through simulation was developed and is called predicTAIL [10]. No similar rating exists for schools. In this context, the development of this approach to assess IEQ in school buildings is a relevant issue.
Green Building Certification (GBC) schemes identify some parameters to be monitored to describe IEQ. These are Beam plus [11], BREEAM [12], DGNB [13], Green Globes [14], Green Mark [15], Green Star [16], GREENSHIP [17], HQE [18], KLIMA [19], LEED [20], Lotus [21], Trees [22]. They, however, do not share similar methods or a homogeneous approach. Furthermore, only DGNB, HQE and LEED have a specific section focusing on classrooms and schools. GBC schemes are voluntary, therefore criteria applied in these schemes are not systematically used during measurements in schools. In an attempt to develop an IEQ rating scheme for schools, the present work aimed to review existing measurements of IEQ parameters in schools. Three specific research questions were examined: (1) which IEQ parameters were often measured in schools; (2) what measuring methods were used; and (3) what are the main findings from these measurements?
2. Materials and Methods
The Scopus database was used to search for relevant literature. The following combination of keywords was used: (“indoor environmental quality” OR “IEQ” OR “thermal” OR “acoustic” OR “indoor air quality” OR “IAQ” OR “luminous” OR “visual” OR “lighting”) AND (“school” OR “daycare center” OR “nursery” OR “university”) AND (“measurement”). To ensure a collection of studies with the latest and up-to-date measurement protocols, the search only covered papers published from 2010 with the following topics: environmental sciences, engineering, social sciences, energy, and multidisciplinary.
A total of 573 papers were identified. A geo-localization filter was applied as only studies in Europe and North America were included to ensure comparability across studies regarding climate conditions, surrounding environment, and building characteristics. Consequently, 324 articles were retained and used for screening. Non-relevant to IEQ measurements in schools, simulation studies, and studies based only on questionnaires were removed. This screening resulted in 79 papers. Nine additional papers were identified and added manually although they did not appear in the initial search. Finally, 88 papers were analyzed in this review. Figure 1 presents a PRISMA flowchart describing the paper selection. It should be noted that 11 studies in university classrooms were included in the review because universities are school environments, even though the students are young adults and no longer children.
3. Results
Among the 88 articles analyzed in this review, some were issued from the same study. Two articles by Branco et al. [23,24] reported results from a measuring campaign in four nurseries in Porto, Portugal; one focused on CO2 and comfort, the second one on IAQ pollutants. The report by Csobod et al. [25] on the thermal environment and IAQ and the article by Baloch et al. [26] on the results of the visual environment both reported findings from the SINPHONIE pan-European study. Among the 88 articles, IAQ parameters were measured in 73 studies, thermal parameters in 43 studies, visual parameters in 15 studies, and acoustic parameters in 13 studies. In 40 studies, the parameters describing at least two of the four IEQ components were measured. Only four studies [27,28,29,30] measured parameters of the four IEQ components. These studies were carried out in 28 countries (Figure S1 in Supplementary Materials (SM)).
Nine studies were conducted in day-care centers, nine in nursery schools, 40 in elementary schools, 24 in secondary schools, 12 in high schools, and 11 in universities. In 59 studies, schools had no mechanical ventilation system. In eight studies, an HVAC (Heating, ventilation, and air conditioning) system with heat recovery was installed. In nine studies, measurements were performed in both classrooms with no ventilation system and classrooms equipped with a mechanical ventilation system. In three studies, no information on ventilation type was available, and only acoustic and visual measurements were conducted [31,32,33]. Table 1 summarizes all studies presented in this review. Table 2 summarizes the main findings with the range of results from the 88 articles.
3.1. Thermal Environment
Thermal environment was assessed in 43 studies. The air temperature, radiant temperature, operative temperature, humidity or air speed were measured. Some studies additionally estimated thermal comfort using the model developed by Fanger [110].
3.1.1. Air Temperature
The air temperature was measured in 43 studies; it was often measured simultaneously with relative humidity. Measurements were performed during winter (heating season) in eight studies, during non-heating season, i.e., spring and autumn in 29 studies, during summer in six studies, and seven studies did not provide any information.
Temperature was mainly recorded continuously for the periods of over thirty minutes to three months with a time step ranging from two to ten minutes. In three studies, only spot measurements were carried out. In one study, a combination of continuous measurements over three months and spot measurements four times in each classroom were carried out.
Different numbers of sensors, at various locations in each classroom, were used. Thirty-eight studies used only one sensor for each classroom, and three studies used three sensors per classroom. Laborda et al. [66] measured air temperature in 12 locations in the classroom: six at 0.6 m and six at 1.7 m, divided into two arrays close to the window and next to the entrance doors. Papadopoulos et al. [79] measured air temperature in 11 locations in the classrooms, with their height situated from 0.5 to 2.5 m above the ground to be compliant with the students’ breathing zone. Nine studies reported that their sensors were placed at 0.6 m above the ground, and seven other studies placed their sensors from 0.7 to 2 m above the ground. Fabbri et al. [53] measured air temperature at two different heights: 0.6 and 1.3 m. The detailed protocols and results can be found in Table S1 in Supplementary Materials.
Studies from Western Europe (Italy, Spain, Portugal, France, and Greece) measured temperatures ranging from 13 to 38 °C with a mean of 22 °C. Studies from Northern Europe (Sweden and Finland) measured temperatures ranging from 12 to 26 °C with a mean of 21 °C.
3.1.2. Humidity
Relative humidity (RH) was measured simultaneously with air temperature using hygrometer sensor. In one study, absolute humidity was also determined along with relative humidity. Humidity was reported in 43 studies. Findings on the number of sensors, their location, and the duration of measurements are identical to air temperature measurements since the two parameters were always measured together in the reviewed studies. RH ranged between 22% with a mean air temperature of 23 °C and 96% with a mean air temperature of 25 °C. Among the classrooms with mechanical ventilation, the relative humidity varied between 30 and 72%, while the air temperature varied between 21 and 25 °C.The detailed protocols and results can be found in Table S2 in Supplementary Materials.
3.1.3. Mean Radiant Temperature
Mean radiant temperature was measured in 11 studies. In eight studies, the measurements were made using one globe thermometer, placed in the center of the room in each study, with a measurement duration ranging from one to five days. Other studies made spot measurements of the radiant plane temperature to estimate the mean radiant temperature but the monitoring protocol was not detailed and in two studies, air and mean radiant temperature were measured over 24 h. Papadopoulos et al. [79] used a thermal imaging camera to estimate the mean radiant temperature from surface temperatures. The mean radiant temperature measured in the 11 studies ranged between 13 and 24 °C. Table S3 in Supplementary Materials shows the details concerning measuring protocols and results.
3.1.4. Operative Temperature
Operative temperature was reported in six studies based on the measurement of globe temperature, and air velocity. In these studies, a small sample of classrooms (less than ten) was monitored, but the measurements were made at different classroom locations and repeated. In their study in 145 classrooms in Sweden, Simanic et al. [94] assumed that the operative temperature was similar to air temperature, as these schools were well insulated [15].Reported operative temperature from five studies ranged from 19 to 22 °C. Table S3 in Supplementary Materials provides details regarding measuring protocols and results.
3.1.5. Airspeed
Airspeed was measured in 12 studies in schools. These measurements were made to assess thermal comfort. Spot measurements were always made using an anemometer, but its position was never clearly mentioned. The reported results were all under 0.1 m/s.
3.2. Acoustic Environment
Thirteen studies reported measurements of parameters characterizing acoustic environment in schools. Parameters measured included noise level, reverberation time (RT) and speech intelligibility.
3.2.1. Noise Level
The background noise level was the most frequently measured acoustic parameter. It is also a parameter commonly used to assess occupants’ long-term noise exposure [111]. Background noise level can be estimated using the variation of the pressure in the air caused by sound waves (sound pressure level-SPL) or the equivalent continuous sound level, e.g., LAeq, defined as the total energy from the sound pressure level during the measurement period [112].
LAeq was measured in nine studies, with one or two sound meters per classroom. The location of the sound meter was mentioned in three studies: Chetoni et al. [46] measured in the center of the room and one meter from the window, Shield et al. [93] also measured at two positions in the classroom, and de la Hoz-Torres et al. [29] only used one sound-meter placed in the center of the room.
Measurements were a spot measurement of one minute or continuous from two hours to two days. In some studies, measurements were made during day without students in the classrooms, while in other studies, measurements were made when the students were occupying the classrooms.
The average measured LAeq in studied classrooms varied between 29 and 82 dB(A). Chetoni et al. [46] used the LDAY indicator, defined as the daily LAeq over the 12 h diurnal period from 7 a.m. to 7 p.m. since this parameter is used in Italy’s national regulation for outdoor acoustic. The LDAY ranged between 23 and 63 dB(A). Smith et al. [97] in their study quantified the influence of the different mechanical ventilation systems (single- and multi-zone HVAC systems) on the non-speech noise during occupied periods. The average LAeq was 66 dB(A) for unit ventilators, 67 dB(A) for centralized systems, and 66 dB(A) for systems with decentralized heat pumps. Details on measurement protocol and results can be found in Table S4 in Supplementary Materials.
3.2.2. Reverberation Time
A room reverberation time (RT) expresses the time required for the sound to decay after the sound source has stopped; for example, T20 is the time it takes for sound to decay by 20 dB, and T60 is the time for a decay of 60 dB, T20 as the time for a decay by 20 dB, respectively [112]. There is a linear relationship between T20 and T60 in the same environment, as the measurement of T20 can be used to evaluate T60, which is the case in the study by Loreti et al. [30].
RT was measured in in four studies in Italy [30,32,43,46], one study in Poland [71], one in Denmark [64], one in Germany [61], and one in England [93]; all referred to the measurement methods defined in the ISO 3382 standard [112], using an impulsive response method for a controlled and continuous (white noise) generated by an omnidirectional loudspeaker, blank gun noise, or maximum-length sequence signals. Two to twelve microphones were placed in children’s seat positions, i.e., at least 1.1 m of height, and the results were expressed as the average of all these measurements. Mikulski et al. [71] measured the Tmf which is the arithmetic mean of RT for 500 Hz, 1000 Hz, and 2000 Hz, as well as the Twf which is the arithmetic mean of RT for 250 Hz, 500 Hz, 1000 Hz, 2000 Hz, and 4000 Hz. The authors specified that measuring Tmf alone does not always correspond with the subjective evaluation of the acoustical properties of the room. Other studies, such as the Klatte et al. [61] study, measured the T20 averaged from results of octave bands from 250 to 2000 Hz. The measured RT ranged from 0.9 to 1.1 s for T60 and 1.1 to 1.4 s for T20. Details on measurement protocol and results can be found in Table S6 in Supplementary Materials.
3.2.3. Speech Intelligibility
Speech intelligibility depends on the spoken language familiarity of the listeners and is limited in children due to a lack of vocabulary and grammar skills [113]. Speech transmission is the physical measurement of the speech intelligibility, which depends on classroom acoustic characteristics such as the RT and the background noise level.
One indicator of speech intelligibility is the signal-to-noise (SNR) ratio. It is defined as the ratio of the signal power to the background noise power and is expressed in decibels. A review on speech intelligibility in school has shown that high background noise levels can mask speech sounds, as the authors stated that a recommended SNR should be greater than +15 dB, and ideally at +25 dB [114]. Sarantopoulos et al. [90] measured the SNR using LA90 in an occupied classroom with a teacher talking. LA90, defined as the 90th percentile of LAeq in a one-minute measurement period, was considered as a proxy to background noise during the active teaching period. The SNR was calculated by subtracting the measured teacher’s speech noise to the LA90. For 41 teachers in 15 classrooms, the average SNR for teaching was 12.0 ± 3.6 dB(A), ranging from +6.8 dB(A) to + 21.6 dB(A).
Another indicator of speech intelligibility is the speech transmission index (STI), which ranges between 0 and 100% and represents the transmission quality of speech concerning intelligibility by a speech transmission channel, according to the standard EN 60268-16, 2011 [115]. STI was assessed in four studies in Italy [30,32,43,46], one study in Poland [71], and one in England [93] by emitting a speech-like sound signal and measuring its transmission quantity at another point in the room, referring to the methods described in the standard EN 60268-16, 2011 [115]. Measurements were performed in unoccupied classrooms as students’ presence can alter the STI results, and the results ranged from 41 to 76%.
The clarity index is also used to assess speech intelligibility. It is the difference between the emitted sound energy and the later arriving sound energy after a time limit [112], expressed in dB. C50 is the clarity index in case of a time limit of 50 ms (ISO 3392-1 standard, 2010). C50 was measured simultaneously with STI in the same three studies in Italy [30,32,43], and in one study in England [93]. The results ranged from −6.28 to 5.55 dB in 66% of classrooms. Details on measurement protocol and results of measured SNR, STI, and C50 can be found in Table S5 in Supplementary Materials.
3.2.4. Sound Insulation
Sound insulation is the ability of buildings’ components to reduce sound transmission through the envelope and the internal walls and floors. Façade insulation measurement can be determined by measuring the airborne sound reduction index between outside and inside the buildings. Different methods exist (ISO 16283-3 standard, 2016 [116]) and aim at assessing either the sound reduction index of an element of the building façade, such as windows, or the reduction of indoor noise levels due to building façade with actual traffic conditions. In some countries, minimum sound insulation level requirements exist in building regulations: at least 38 dB(A) façade insulation in the Italian technical regulation and at least 30 dB(A) façade insulation in the French regulation [116].
Chetoni et al. [46] in Italy determined the total insulation of the school building façade exposed to road traffic and calculated the weighted standardized level insulation (D2m,nT,w), following ISO 16283-3 [116]. The study found that the façade insulation index was below the regulatory value of 38 dB in 23 out of 24 classrooms. Different classrooms in the same school had different results, as there are various conditions of poor quality or even damaged windows and doors.
In the same study, airborne sound insulation between two classrooms or between classrooms and corridors was assessed by measuring wall insulation between interior spaces (R’w). Results showed that in 11 out of 24 classrooms, the R’w between two classrooms [46] was below the Italian regulatory value of 41 dB [54]. A large variability of R’w (at a maximum of 18 dB) between the classrooms was observed. It was explained by the different construction technologies, either with load bearing or only with a partition wall.
3.3. Indoor Air Quality (IAQ)
IAQ depends on the concentrations of pollutants having outdoor or indoor origin. Sixty-two studies performed IAQ measurements, including the following parameters: carbon dioxide, different ventilation parameters, formaldehyde and other aldehydes, volatile organic compounds (VOC), semi-volatile organic compounds (SVOC), particulate matter, nitrogen dioxide, bio-contaminants and radon.
3.3.1. Carbon Dioxide (CO2), Ventilation Rate (VR), and Air Change Rate (ACR)
CO2 is a marker of ventilation adequacy in the presence of people indoors and is the most prevalently measured parameter in connection with IAQ monitoring [117]. CO2 was measured mainly with a non-dispersive infrared (NDIR) sensor. The concentrations were determined using spot or continuous measurements, the latter for a period of 30 min to three months with a time interval ranging from two to ten minutes. The number of measurement locations was either one in the center of the room or in multiple locations.
Across 32 studies that measured CO2 in a naturally ventilated classroom, average mean concentrations ranged between 591 and 3494 ppm. In all naturally ventilated classrooms, CO2 concentration varied throughout the day depending on children’s presence and the frequency of window opening. Studies in classrooms equipped with mechanical ventilation systems showed that CO2 concentrations did not exceed 1000 ppm.
Details on measurement protocols of CO2 and results from studies can be found in Table S7 in Supplementary Materials.
The air change rate (ACR) and ventilation rate (VR) can be calculated using the measured CO2 concentrations. Six studies calculated the ACR using the CO2 decay rate during the non-occupied period, and one study calculated VR using the CO2 production rate during the occupied period. The estimated ACR ranged between 0.11 and 0.39 h−1 in naturally ventilated classrooms, and between 1.4 and 3.2 h−1 in classrooms with mechanical ventilation systems.
In 70 classrooms equipped with either air handling units (17%), fan coil units (21%), or individual unit ventilators (62%) in the USA, VR was calculated using the peak level of measured CO2 and mean VR was estimated to be 3.6 ± 2.3 L/s per person. The VR was calculated using measured CO2 concentrations in 51 classrooms in France (14 classrooms had mechanical ventilation systems and 37 had natural ventilation). Mean VR was estimated to be 4.2 ± 1.7 L/s per person in mechanically ventilated classrooms and 2.4 ± 1.4 L/s per person in naturally-ventilated classroom. In the pan-European SINPHONIE study, the mean VR ranged from 0.87 L/s per child in Western Europe to 3.4 L/s per child in Northern Europe.
Detailed protocols regarding ACR/VR can be found in Table S8 in Supplementary Materials.
3.3.2. Formaldehyde and Other Aldehydes
Formaldehyde was measured in 15 studies, while other aldehydes were measured in six studies. A summary of formaldehyde measurements is provided in Table S9 in Supplementary Materials while Table S10 presents the measurements of other aldehydes.
Formaldehyde can be measured using passive (12 studies) or active (three studies) methods. It is sampled on a cartridge containing an organic reagent, such as 2,4-dinitrophenylhydrazine (DNPH), then analyzed with high-performance liquid chromatography (HPLC) and ultraviolet (UV) detection, as recommended in the ISO 16000-4 standard [118] for lightweight aldehydes. One or two passive samplers were deployed per classroom, and their locations were not always reported. The sampling duration for passive samplers ranged from two days to two weeks. The three studies that used active sampling had measured in either spot measurements from one minute [24] and 30 min [108], or 2.5 h [119]. The mean concentration of formaldehyde ranged between 1.4 and 89 µg/m3. Summaries of measurement protocols and results of formaldehyde and other aldehydes are provided in Tables S9 and S10 in Supplementary Materials.
3.3.3. Volatile Organic Compounds (VOCs)
The most frequently measured VOCs were BTEX: benzene, toluene, ethylbenzene, and xylenes. Fourteen studies measured BTEX, among which three also measured concentration of total volatile organic compounds (TVOC), and eleven measured a larger number of VOCs. Three studies used a portable analyzer including a photoionization detector with UV to measure organic compounds. The other studies used diffusive passive samplers for a duration of two to four weeks. The location of the samplers was usually in the center of the room with other measurement devices, but in most studies, it was not reported. The mean indoor concentrations ranged between 0.5 and 3.2 µg/m3 for benzene, 0.2 and 17 µg/m3 for toluene, less than the limit of detection and 9.0 µg/m3 for ethylbenzene, and 0.6 to 12 µg/m3 for xylenes. A summary of all the measured BTEX compounds and other VOCs, their protocols and results can be found in Table S11 and Table S12 in Supplementary Materials, respectively.
3.3.4. Semi-Volatile Organic Compounds (SVOCs)
SVOCs are less volatile than VOCs and can also be present in the particulate phase in addition to the gas phase. Four groups of SVOCs were measured and reported in eleven studies. They were polycyclic aromatic hydrocarbons, PAH (acenaphthene, anthracene, benzo(a)pyrene), flame retardants (tributylphosphate, polybrominated diphenyl ethers), phthalates (BBP, DBP, DEHP, DEP, DiBP), and synthetic musks (tonalide, galaxolide). Phthalates were the most frequently detected SVOCs in the air. Active sampling on polyurethane foam (PUF) was often used to trap the SVOC gas phase. The samples were then analyzed using GC-MS. The sampling duration ranged from 24 h to one week at one point in the room, with the accurate location not specified. SVOC measurement protocols and concentrations can be found in Tables S14–S16 in Supplementary Materials.
3.3.5. Particulate Matter (PM)
Particulate matter (PM) can originate from indoor (e.g., cooking and heating) and outdoor (e.g., traffic) sources. Twenty-two studies measured PM in classrooms, among which ten measured PM10, 21 measured PM2.5, one measured PM4, two measured PM1, and one measured PM0.1.
PM concentrations can be measured using optical and gravimetric methods. Optical PM counters use a laser to count the particles passing a small volume, with results expressed in the total particle count adjusted to the volume. The gravimetric method uses an air pump to drive air through an impactor that collects PM according to their size. Eight studies used an optical counter, and twelve used the gravimetric method to measure PM concentrations. Two studies used condensation particle counters (CPC) that can measure small particles, such as PM0.1 and PM0.5. The sampling duration ranged from eight hours to ten months, with a time interval from one to ten minutes. The sampling locations in the classrooms were not specified.
The measured concentrations ranged from 34 to 2061 µg/m3 for PM10, and from 1.3 to 106 µg/m3 for PM2.5. PM1 was measured in one study with a mean concentration of 19.2 ± 7.2 µg/m3 in two classrooms during school hours. One study measured PM0.5 in two classrooms and reported concentrations ranging from 2.1 to 22 µg/m3. One study measured the ultrafine particles, with concentrations ranging from 1560 to 16,780 particles/cm3. The measurement protocols and results can be found in Table S13 in Supplementary Materials.
3.3.6. Nitrogen Dioxide (NO2)
Nitrogen dioxide (NO2) is primarily emitted by combustion and mainly comes from outdoors, particularly from traffic. Among eleven studies that measured NO2, nine conducted long-term (five to fourteen days) passive measurements, and two used a chemiluminescence continuous analyzer for a period of thirty minutes or 24 h. The location of the samplers was usually in the center of the room with other measurement devices, but in most studies, it was not reported. The mean NO2 concentration ranged from 4.9 to 125 µg/m3, with a maximum concentration of 292 µg/m3. Details on the measurement protocols and results can be found in Table S17 in Supplementary Materials.
3.3.7. Bio-Contaminants
Dampness and high relative humidity in buildings lead to microbial growth, dust mites and their allergens [120]. Bio-contaminants assessment was reported in three studies in Finland, one in Portugal, and in one pan-European study.
Mold exposure can be assessed either by visual inspection or by measurements of airborne spores. Visual inspection has been reported in one study in Finland, with two out of seventeen schools showing visible mold. For measurements of airborne spores, two studies in Finland measured indoor airborne cultivable microorganisms, and reported an average concentration of 22 to 260 CFU/m3 of airborne cultivable microorganisms. Finally, the SINPHONIE pan-European study reported that 7% of classrooms had visible signs of mold.
3.3.8. Radon
Radon is a chemically inert gas emitted naturally from underground. It was measured in sixteen studies identified in the present review. Measurements can be made with a passive dosimeter, which was the case in fifteen studies, for a duration ranging from three months to one year. Passive dosimeters were placed on the ground floor or on the lowest floor of the buildings. Only one study used an active measurement device that provided a value every sixty minutes over 24 h. The mean radon concentration ranged from 56 to 579 Bq/m3. The measurement protocol and the results showing measured radon concentrations are presented in Table S18 in Supplementary Materials.
3.4. Visual Environment
Lighting conditions determine the quality of the visual environment. They include the contributions of both daylight and artificial light emitted by the installed luminaires. Visual environment was investigated in 15 studies; most of them were spot measurement using an illuminance meter placed at students’ desks. The number of measurement points varied from one per class to 319. Leccese et al. [31] measured numerous parameters for the purpose of determining the most influential parameters on students’ visual comfort.
3.4.1. Daylighting
Daylighting measurements can be made by assessing the daylight factor via simulation or by simply measuring desk illuminance in classrooms with artificial light turned off. Daylight factor (%) is the ratio between the indoor horizontal illuminance at a given location and the outdoor horizontal illuminance measured under the unobstructed sky vault in overcast conditions. One study reported the daylight factor, with a result of 2.2%. Leccese et al. [31] also reported that daylight glare is the most important factor contributing to students’ visual comfort.
Five studies reported daylighting by measuring the total illuminance with artificial lighting on students’ desk. Rucinska et al. [33] measured the average illuminance in a classroom during two periods: one period with a clear sky and the other period with an overcast sky. This study included the highest number of measurement points per classroom, with 319 points grouped in three different longitudinal rows of tables, i.e., near the windows, in the middle of the room, and next to the entrance door away from the windows. Results showed a 9-fold decrease of mean illuminance in the middle of the room and an 18-fold decrease next to the entrance door, compared to the illuminance on the desks near the windows. In overcast conditions, these ratios were about 3 and 8, respectively. In the other studies, mean measured total illuminance ranged from 303 lx to 1255 lx.
3.4.2. Artificial lighting
Artificial lighting is provided by luminaires installed inside the classroom. Artificial lighting should be able to compensate for an insufficient level of daylight indoors.
The measurement of artificial lighting follows the same principle with the use of an illuminance-meter. To correctly evaluate only artificial lighting, measurements should be done with controlled daylighting, by selecting low daylight timeframe, or simply by closing solar protections if any in the classroom. All performed measurements were spot measurements. Artificial lighting was measured in eight studies. Six out of the eight studies measured only at the center of the classroom, one study reported at least four measurements points and one study measured at six points in the room, additionally reporting the values of the lighting uniformity factors. The illuminance values reported were in the range of 241 lx to 748 lx. Table S19 combines all measurement protocols and results of all studies on lighting conditions.
4. Discussion
This review highlighted that out of the 88 reviewed articles, all four components of IEQ were measured only in four studies [27,28,29,30]. Identical parameters were measured in these four studies (air temperature, RH, CO2, illuminance, noise level), with a sample size of less than five classrooms in three studies. The study by de la Hoz–Torres et al. [29] measured IEQ parameters in 15 classrooms in six buildings in Portugal and Spain. As shown in Figure 2, eight studies measured at least three out of the four IEQ components—seven studies measured IAQ, visual and thermal parameters [25,48,49,50,63,66,74], and one study measured visual, thermal and acoustic parameters [43].
As shown in Figure 3, most studies had a small sample size; the median was six schools and 17 classrooms. Twenty-six studies only measured IEQ parameters in one school, and thirteen of them only instrumented one classroom. In 19 out of these 26 studies, there were at least two IEQ components measured including three studies that measured all four IEQ components [27,28,30]. In 11 studies that targeted more than 100 schools, only three performed measurements of more than one IEQ component, including the pan-European SINPHONIE study, which measured thermal, IAQ, and visual parameters in 114 schools and 342 classrooms across 23 countries [25,38]. One study had the largest sample size of 1000 classrooms in 438 schools but only radon was measured with passive dosimeters [100]. Overall, it was seldom that many parameters were measured when the study included many classrooms and schools.
Among the different aspects retrieved from the reviewed studies (sampling location, type of sampling, duration, etc.), the measured parameters were the first point of interest of the review. Targeted parameters varied between studies depending on their objective and their capabilities in terms of equipment, safety considerations, and cost. Whilst most parameters could be used to characterize IEQ or evaluate children’s pollutant exposure and comfort, some parameters show limitations. Indeed, to characterize thermal environment, air temperature was measured in all studies. However, this measurement may not be sufficient to characterize children’s thermal sensations which depends also on other parameters such as relative humidity, airspeed, and mean radiant temperature [53,121]. Operative temperature is based on the measurement of air temperature with a temperature thermocouple sensor, air velocity with an anemometer, and mean air radiant temperature with a globe thermometer. It requires advanced measurement systems which are complex and expensive to implement in a large sample of classrooms over a long period [94]. We stipulate that it was the reason why it was measured only in five studies and in two of them as spot measurements before the monitoring week due to the safety considerations [27,81]. In these studies, the differences between mean radiant temperature and air temperature were always below 3 °C, suggesting that the choice of measuring air temperature is somewhat justified. In 145 classrooms of six schools in Sweden, air temperature was measured from May to October and the difference between operative temperature and air temperature was below 1 °C because the schools were well insulated; this provides additional justification for using only air temperature measurements [94].
The second discussion point deals with the measurement protocols. Measuring protocols for some parameters have shown significant differences in sampling strategies and statistical indicators. The sampling strategies were inhomogeneous concerning the position, the height, the duration of the measurements in the classrooms, the sampling frequency, and the devices ‘accuracy’ were not systematically mentioned in many studies including calibration. This variability was observed for the four IEQ components, especially for the numerous IAQ parameters. For example, particles were monitored with optical or gravimetric methods, with various sampling strategies during occupancy or non-occupancy periods. These variations were also observed for the background noise level, which was measured either when children were in the classrooms or not in the classrooms. These differences led to inhomogeneity in results, metrics, and difficulty to interpret the results. Many measuring methods and indicators were complex and trained field technicians were needed to perform measurements. This mainly concerns parameters of acoustic and visual components. For example, speech intelligibility, essential for providing an adequate learning environment for children, was measured in five studies using three different indicators: SNR, STI, and C50, RT, which is also an essential factor for acoustic quality in classrooms [122], was measured with different protocols, especially for the generation of the noise, but always followed the standard ISO 3382 [112]. For the visual environment, many parameters, including illuminance, uniformity, luminance distribution, glare, effects of temporal light modulation such as flicker and the stroboscopic effect, and color temperature, should be considered to have well-balanced lighting in classrooms essential for health, well-being, and learning. Illuminance on desks was measured in all the studies dealing with visual environment. It is the less complex parameter to assess using a lux-meter. Other indices, such as glare indices, have been shown to have more impact on students’ perception but are based on equations correlating luminance values in the occupant’s field of view and human’ sensation. These parameters were only measured one time, in one lighting’s specific study in one classroom, demonstrating its difficulty to implement them in a large sample of schools [31]. The factors that primarily influence occupant visual comfort were daylight glare and luminance, which are not commonly measured as previously mentioned.
Finally, main results from the reviewed studies provide an overall picture of IEQ in schools within the scope of our review. Most IEQ parameters identified in this review have reference values in the regulations, standards, and guidelines from WHO and the governments or GBC. Table 2 presents the summary results for each IEQ parameter from 88 retrieved papers and their reference values. IAQ parameters have fewer guideline values compared to other parameters, especially for VOCs and SVOCs. While a growing body of studies on IAQ parameters in schools has shown associated risks to children’s health, well-being, and cognitive performance, further development and future studies are still needed to highlight the relationship between children’ exposure to air pollutants and health outcomes, for the purpose of establishing their reference values. For acoustic and visual components, some parameters are regulated in European countries and the USA for school buildings, such as façade insulation, sound insulation between two rooms, and RT. The illuminance-regulated value has been mentioned in the labor code in France. This review highlighted that many parameters in the four components exceeded threshold values [123].
This review creates the background for developing an IEQ rating scheme in schools by listing the measured parameters and assessing their respective prominence, limitation, and applicability to the school environment. The most measured parameters for the four IEQ components are air temperature and relative humidity for thermal, concentrations of carbon dioxide, particulate matter, radon, formaldehyde, and some volatile organic compounds for IAQ, noise level, and reverberation time for acoustic and illuminance for visual environments. The popularity of these parameters in studies indicates their pertinence in characterizing the IEQ parameters in schools. However, a consensus measurement protocol of all IEQ parameters must be set to facilitate inter-comparison between measurements at different schools. Another question can be raised on whether and how occupant perception can be used to assess the IEQ, as studies have shown limitations of some parameters when evaluating children’s comfort. Future works should propose harmonized protocols and define the threshold values for each parameter to ensure children can spend time at school without harming their health, well-being, and cognitive performance.
5. Conclusions
This review provides an overview of IEQ parameters measured in schools in Europe and North America since 2010 and compares different monitoring protocols and results in 88 articles. This review aims to provide an overview of IEQ parameters often measured in schools, their measuring methods, and the main findings from these measurements. These studies mainly focused on individual IEQ components in small samples of schools (median of six schools). Twenty-two parameters or families of parameters were reviewed. Measurement protocols, including the number and position of samples and the sampling duration, did not present a consensus between studies, which leads to the difficulty in comparing the results. Some parameters also present limitations in the current schools’ environment and need further developments to be adapted to the school’s environment and children’s exposure. Air temperature and relative humidity for thermal, concentrations of carbon dioxide, particulate matter, radon, formaldehyde, and some volatile organic compounds for IAQ, noise level, and reverberation time for acoustic and illuminance for visual environments can be defined as adequate parameters for the purpose of characterizing IEQ in schools.
Overall, a holistic approach to quantifying IEQ in schools is needed with a set of measurable parameters for the four components with consensus on measurement protocols, and threshold values that reflect children’s pollutant exposure and comfort perception.
Conceptualization, M.T.T., W.W., C.D., P.W., V.H. and C.M. (Corinne Mandin); methodology, M.T.T., C.D., P.D. and C.M. (Christophe Martinsons); investigation, M.T.T.; writing—original draft preparation, M.T.T. and C.D.; writing—review and editing, W.W., P.W., V.H., C.M. (Christophe Martinsons), P.D. and C.M. (Corinne Mandin); supervision, P.W. and V.H.; project administration, W.W. and C.D. All authors have read and agreed to the published version of the manuscript.
Not applicable.
Not applicable.
The data presented in this study are available in
The authors declare no conflict of interest.
Abbreviation | Signification |
IEQ | Indoor environmental quality |
IAQ | Indoor air quality |
CO2 | Carbon dioxide |
TAIL | Thermal, Acoustic, IAQ, Lighting |
GBC | Green building certification |
SM | Supplementary material |
HVAC | Heating, ventilation, and air conditioning |
PMV | Perceived mean vote |
PPD | Percentage person dissatisfied |
VOCs | Volatile organic compounds |
BTEX | Benzene, toluene, ethyl-benzene, xylene |
SVOCs | Semi-volatile organic compounds |
PM | Particulate matter |
ACR | Air change rate |
VR | Ventilation rate |
NO2 | Nitrogen dioxide |
CFU | Colony forming unit |
RH | Relative humidity |
LAeq | Background noise equivalent level |
RT | Reverberation time |
SNR | Speech to noise ratio |
STI | Speech transmission index |
HPLC | High-performance liquid chromatography |
UV | Ultra violet |
TVOC | Total volatile organic compounds |
DNPH | 2,4-dinitrophenylhydrazine |
PAH | Polycyclic aromatic hydrocarbons |
BBP, DBP, DEHP, DEP, DiBP | Phthalates |
PUF | Polyurethane foam |
Footnotes
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.
Figure 2. Number of studies according to the IEQ components measured (n = 88 articles).
Figure 3. Number of schools and classrooms per study where the measurements were made. Each dot represents a study with the number of measured schools on the x-axis and the number of measured classrooms on the y-axis.
Summary of the investigated studies (n = 88 articles).
Study [Reference] | Location | Season | Type of School | IEQ Component |
---|---|---|---|---|
Aguilar et al., 2022 [ |
Spain | Winter | University | Thermal, IAQ |
Ahmed et al., 2019 [ |
Finland, Estonia | Winter | Daycare, elementary | Thermal, IAQ |
Alves et al., 2013 [ |
Portugal | Winter | Kindergarten, elementary | Thermal, IAQ |
Annesi-Maesano et al., 2012 [ |
France | N/A | Elementary | IAQ |
Azara et al., 2018 | Italy | Spring |
Elementary, secondary, high school | IAQ |
Baloch et al., 2021 [ |
Europe | Spring |
Kindergarten, elementary | Visual |
Barmparesos et al., 2018 [ |
Greece | Summer | Elementary | Thermal, IAQ |
Becerra et al., 2020 [ |
Spain | Spring | Kindergarten, elementary, secondary, high school | IAQ |
Branco et al., 2015 [ |
Portugal | Spring |
Daycare | Thermal, IAQ |
Branco et al., 2015 [ |
Portugal | Spring |
Daycare | IAQ |
Branco et al., 2016 [ |
Portugal | Year long | Daycare, elementary | IAQ |
Brdaric et al., 2019 [ |
Croatia | Spring | Elementary | Thermal, IAQ |
Buratti et al., 2018 [ |
Italy | Spring |
University | Thermal, Acoustic, Visual |
Canha et al., 2016 [ |
France | Winter | Daycare, elementary | Thermal, IAQ |
Cequier et al., 2014 [ |
Norway | Winter |
Elementary | IAQ |
Chetoni et al., 2016 [ |
Italy | N/A | Secondary, high school | Acoustic |
Csobod et al., 2014 [ |
Europe | Spring |
Kindergarten, elementary | Thermal, IAQ, Visual |
de Gennaro et al., 2013 [ |
Italy | N/A | Elementary | IAQ |
De Giuli et al., 2012 [ |
Italy | Spring | Elementary | Thermal, IAQ, Visual |
De Giuli et al., 2014 [ |
Italy | Spring | Elementary | Thermal, IAQ, Visual |
De Giuli et al., 2015 [ |
Italy | Spring | Elementary | Thermal, IAQ, Visual |
de la Hoz –Torres et al., 2022 [ |
Portugal, Spain | Fall | University | Thermal, Acoustic, IAQ, Visual |
Dhoqina et al., 2019 [ |
Albania | Spring | Elementary, secondary, high school | IAQ |
Erlandson et al., 2019 [ |
United States | University | Thermal, IAQ | |
Fabbri 2013 [ |
Italy | Fall | Kindergarten | Thermal |
Franci et al., 2014 [ |
Italy | Winter | Elementary, secondary, high school | IAQ |
Gaffin et al., 2018 [ |
United States | Fall |
Elementary, secondary | IAQ |
Harcarova et al., 2020 [ |
Slovakia | N/A | Elementary | Thermal, Acoustic, IAQ, Visual |
Heracleous et al., 2019 [ |
Cyprus | Winter | Secondary | Thermal, IAQ |
Irulegi et al., 2017 [ |
Spain | Spring | University | Thermal |
Istrate et al., 2016 [ |
Romania | Summer | High school | Thermal, IAQ |
Ivanova et al., 2014 [ |
Bulgaria | Spring | Kindergarten | IAQ |
Ivanova et al., 2021 [ |
Bulgaria | Fall |
Elementary | IAQ |
Jovanovic et al., 2014 [ |
Serbia | Spring | Elementary | Thermal, IAQ |
Klatte et al., 2010 [ |
Germany | N/A | Elementary | Acoustic |
Kojo et al., 2020 [ |
Finland | Winter |
Daycare, Elementary | IAQ |
Korsavi et al., 2019 [ |
England | Summer |
Elementary | Thermal, IAQ, Visual |
Kristiansen et al., 2011 [ |
Denmark | Fall |
Secondary | Acoustic |
Krugly et al., 2014 [ |
Lithuania | Winter | Elementary | IAQ |
Laborda et al., 2020 [ |
Spain | Winter | Secondary | Thermal, IAQ, Visual |
Larsson et al., 2017 [ |
Sweden | Spring |
Kindergarten | IAQ |
Leccese et al., 2020 [ |
Italy | Spring |
University | Visual |
Liaud et al., 2021 [ |
France | Spring | High school | IAQ |
Loreti et al., 2016 [ |
Italy | N/A | Secondary | Thermal, Acoustic, IAQ, Visual |
Madudeira et al., 2015 [ |
Portugal | Fall |
Elementary | Thermal, IAQ |
Mainka et al., 2015 [ |
Poland | Winter | Daycare | IAQ |
Mikulski et al., 2011 [ |
Poland | N/A | Elementary | Acoustic |
Müllerova et al., 2017 [ |
Hungary, Poland, Slovakia | Fall |
Kindergarten | IAQ |
Nunes et al., 2016 [ |
Portugal | Spring | Nursery | IAQ |
Oldham et al., 2020 [ |
United States | Fall |
Elementary | Thermal, IAQ, Visual |
Oliveira et al., 2016 [ |
Portugal | Spring | Kindergarten | Thermal, IAQ |
Oliveira et al., 2017 [ |
Portugal | Winter |
Kindergarten | IAQ |
Oliveira et al., 2017 [ |
Portugal | Spring | Kindergarten | Thermal, IAQ |
Onishchenko et al., 2017 [ |
Russia | N/A | Kindergarten | IAQ |
Papadopoulos et al., 2020 [ |
Greece | Winter | University | Thermal, IAQ |
Papazoglou et al., 2019 [ |
Greece | Summer | University | Thermal |
Pereira et al., 2014 [ |
Portugal | Spring | Secondary | Thermal, IAQ |
Pereira et al., 2015 [ |
Portugal | Spring | Secondary | Thermal, IAQ |
Persson et al., 2018 [ |
Sweden | Year long | Kindergarten | IAQ |
Poulin et al., 2012 [ |
Canada | Winter | Elementary, secondary, high school | IAQ |
Raffy et al., 2017 [ |
France | N/A | Nursery, elementary | IAQ |
Ramalho et al., 2015 [ |
France | N/A | Nursery, elementary | IAQ |
Rivas et al., 2014 [ |
Spain | Winter |
Elementary, secondary | IAQ |
Romagnoli et al., 2014 [ |
Italy | Winter |
Elementary, secondary, high school | IAQ |
Rovelli et al., 2014 [ |
Italy | Winter | Elementary, secondary | IAQ |
Rucinska et al., 2020 [ |
Poland | Winter | University | Visual |
Russo et al., 2019 [ |
Italy | N/A | Elementary | Acoustic |
Sarantopoulos et al., 2014 [ |
Greece | Spring | Elementary | Acoustic |
Sarka Langer et al., 2020 [ |
Sweden | Fall |
Elementary | Thermal, IAQ |
Senitkova et al., 2017 [ |
Czech Republic | N/A | Daycare | Thermal, IAQ |
Shield et al., 2015 [ |
England | N/A | Secondary | Acoustic |
Simanic et al., 2019 [ |
Sweden | Fall |
Elementary | Thermal, IAQ |
Sivanantham et al., 2021 [ |
France | Fall |
Daycare, Elementary | Thermal, IAQ |
Slezakova et al., 2019 [ |
Portugal | Winter |
Elementary | IAQ |
Smith et al., 2019 [ |
United States | N/A | Elementary, secondary | Acoustic |
Stamp et al., 2020 [ |
United Kingdom | N/A | Secondary | Thermal, IAQ |
Toftum et al., 2015 [ |
Denmark | N/A | Elementary | Thermal, IAQ |
Trevisi et al., 2012 [ |
Italy | Year long | Daycare, elementary, secondary | IAQ |
Ulla Haverinen-Shaughnessy et al., 2015 [ |
United States | Fall |
Elementary | IAQ |
Verriele et al., 2016 [ |
France | N/A | Elementary, secondary | Thermal, IAQ |
Vilcekova et al., 2017 [ |
Slovakia | Fall | Elementary | Thermal, Acoustic, IAQ, Visual |
Villanueva et al., 2018 [ |
Spain | Spring | Elementary | IAQ |
Vornanen Winqvist et al., 2018 [ |
Finland | Spring | Secondary | Thermal, IAQ |
Vornanen Winqvist et al., 2020 [ |
Finland | Winter | Secondary | Thermal, IAQ |
Z.Curguz et al., 2020 [ |
Bosnia and Herzegovina | N/A | Elementary, secondary, high school | IAQ |
Zecevic et al., 2018 [ |
Bosnia and Herzegovina | Winter |
University | Thermal, IAQ |
Zhong et al., 2017 [ |
United States | Winter |
Elementary | Thermal, IAQ |
Živković et al., 2015 [ |
Serbia | Winter |
Elementary, secondary, high school | IAQ |
Summary of the main results (n = 88 articles).
Parameters | Number of Studies | Main Findings | Reference Values |
---|---|---|---|
Thermal environment | |||
Air temperature (°C) | 43 | Western Europe: Range: 13 °C to 38 °C with a mean of 22 °C |
22 ± 1 °C |
Relative humidity (%) | 43 | Naturally ventilated classrooms range 22% with a mean air temperature of 23 °C to 78% with a mean air temperature of 25 °C. |
30–50% |
PMV/PPD (derivative) | 8 | Mean result: ±0.5 from 0 °C | ±0.2 °C (EN 16798-1) |
Mean radiant temperature (°C) | 7 | Range: 13 to 24 °C | N/A |
Air speed (m/s) | 7 | All reported results are under 0.1 m/s | N/A |
Operative temperature (°C) | 5 | Range: 19 to 22 °C | N/A |
Acoustic environment | |||
Background noise level (db(A)) | 8 | Range: 41 to 82 db(A) | <30 db(A) (EN 16798-1) |
Reverberation time (s) | 8 | Range: 0.9 to 1.1 s | 0.5 s for small spaces |
Speech intelligibility (%) | 7 | SNR range: 12 ± 3.6 db |
N/A |
IAQ | |||
CO2 (ppm) | 42 | Naturally ventilated classrooms, range: 591 to 3494 ppm |
≤550 ppm (concentration above outdoor) |
PM (µg/m3) | 22 | PM10 range: 34 to 2061 µg/m3 |
PM2.5 ≤ 5 µg/m3 |
Radon (Bq/m3) | 16 | Range: 56 to 579 Bq/m3 | 100 Bq/m3 (WHO) |
BTEX (µg/m3) | 14 | Benzene range: 0.5 to 3.2 µg/m3 |
Benzene: <2 µg/m3 |
SVOCs (ng/m3) |
|
N/A | |
Aldehydes (µg/m3) | 15 | Formaldehyde range: 1.4 to 89 µg/m3 | Formaldehyde: <30 µg/m3 |
ACR/ VR (h−1 or l/s/p) | 11 | ACR range: 0.1 to 0.4 h−1 |
≥10 L/s per person + 2.0 L/s/m2 floor |
VOCs (µg/m3) | 10 |
|
N/A |
NO2 (µg/m3) | 11 | Range: 4.9 to 125 µg/m3 | <10 µg/m3 (WHO) |
Mold inspection (cm2 or CFU/m3) | 4 | Range: 22 to 260 CFU/m3 | <400 cm2 (Nordic classification and Levels) |
Visual environment | |||
Artificial illuminance (lx) | 4 | Range: 241 to 748 lx | 500 lx |
Total lighting (natural + artificial) | 4 |
|
N/A |
Natural lighting | 3 |
|
>5% (EN 17037) |
Supplementary Materials
The following supporting information can be downloaded at:
References
1. Altomonte, S.; Allen, J.; Bluyssen, P.M.; Brager, G.; Heschong, L.; Loder, A.; Schiavon, S.; Veitch, J.A.; Wang, L.; Wargocki, P. Ten Questions Concerning Well-Being in the Built Environment. Build. Environ.; 2020; 180, 106949. [DOI: https://dx.doi.org/10.1016/j.buildenv.2020.106949]
2. Klepeis, N.E.; Nelson, W.C.; Ott, W.R.; Robinson, J.P.; Tsang, A.M.; Switzer, P.; Behar, J.V.; Hern, S.C.; Engelmann, W.H. The National Human Activity Pattern Survey (NHAPS): A Resource for Assessing Exposure to Environmental Pollutants. J. Expo. Anal. Environ. Epidemiol.; 2001; 11, pp. 231-252. [DOI: https://dx.doi.org/10.1038/sj.jea.7500165] [PubMed: https://www.ncbi.nlm.nih.gov/pubmed/11477521]
3. Nimlyat, P.S. Indoor Environmental Quality Performance and Occupants’ Satisfaction [IEQPOS] as Assessment Criteria for Green Healthcare Building Rating. Build. Environ.; 2018; 144, pp. 598-610. [DOI: https://dx.doi.org/10.1016/j.buildenv.2018.09.003]
4. Wu, H.; Wu, Y.; Sun, X.; Liu, J. Combined Effects of Acoustic, Thermal, and Illumination on Human Perception and Performance: A Review. Build. Environ.; 2020; 169, 106593. [DOI: https://dx.doi.org/10.1016/j.buildenv.2019.106593]
5. Gaffin, J.M.; Hauptman, M.; Petty, C.R.; Sheehan, W.J.; Lai, P.S.; Wolfson, J.M.; Gold, D.R.; Coull, B.A.; Koutrakis, P.; Phipatanakul, W. Nitrogen Dioxide Exposure in School Classrooms of Inner-City Children with Asthma. J. Allergy Clin. Immunol.; 2018; 141, pp. 2249-2255.e2. [DOI: https://dx.doi.org/10.1016/j.jaci.2017.08.028]
6. Wargocki, P.; Porras-Salazar, J.A.; Contreras-Espinoza, S.; Bahnfleth, W. The Relationships between Classroom Air Quality and Children’s Performance in School. Build. Environ.; 2020; 173, 106749. [DOI: https://dx.doi.org/10.1016/j.buildenv.2020.106749]
7. Wargocki, P.; Porras-Salazar, J.A.; Contreras-Espinoza, S. The Relationship between Classroom Temperature and Children’s Performance in School. Build. Environ.; 2019; 157, pp. 197-204. [DOI: https://dx.doi.org/10.1016/j.buildenv.2019.04.046]
8. Wei, W.; Wargocki, P.; Zirngibl, J.; Bendžalová, J.; Mandin, C. Review of Parameters Used to Assess the Quality of the Indoor Environment in Green Building Certification Schemes for Offices and Hotels. Energy Build.; 2020; 209, 109683. [DOI: https://dx.doi.org/10.1016/j.enbuild.2019.109683]
9. Wargocki, P.; Wei, W.; Bendžalová, J.; Espigares-Correa, C.; Gerard, C.; Greslou, O.; Rivallain, M.; Sesana, M.M.; Olesen, B.W.; Zirngibl, J. et al. TAIL, a New Scheme for Rating Indoor Environmental Quality in Offices and Hotels Undergoing Deep Energy Renovation (EU ALDREN Project). Energy Build.; 2021; 244, 111029. [DOI: https://dx.doi.org/10.1016/j.enbuild.2021.111029]
10. Wei, W.; Wargocki, P.; Ke, Y.; Bailhache, S.; Diallo, T.; Carré, S.; Ducruet, P.; Maria Sesana, M.; Salvalai, G.; Espigares-Correa, C. et al. PredicTAIL, a Prediction Method for Indoor Environmental Quality in Buildings Undergoing Deep Energy Renovation Based on the TAIL Rating Scheme. Energy Build.; 2022; 258, 111839. [DOI: https://dx.doi.org/10.1016/j.enbuild.2022.111839]
11. B.S Limited BEAM Plus New Buildings Version 2.0. 2019; Available online: https://www.hkgbc.org.hk/eng/beam-plus/file/BEAMPlus_New_Buildings_v2_0.pdf (accessed on 30 January 2023).
12. BRE Global Breeam UK New Construction. 2018; Available online: https://files.bregroup.com/breeam/technicalmanuals/NC2018/ (accessed on 30 January 2023).
13. DGNB GmbH. DGNB System Buildings in Use Criteria Set. 2020; Available online: https://static.dgnb.de/fileadmin/dgnb-system/downloads/criteria/DGNB-Criteria-Set-Buildings-In-Use-Version-2020.pdf (accessed on 30 January 2023).
14. Green Building Initiative. Green Globes Technical Reference Manual. 2018; Available online: http://www.greenglobes.com/v3/newconstruction/Green_Globes_for_New_Construction_2021_Technical_Reference_Manual.pdf (accessed on 30 January 2023).
15. Ministry of National Development. Green Mark for Non-Residential Buildings NRB:2015. 2015; Available online: https://www.bca.gov.sg/greenmark/others/GM_NREB_V3.pdf (accessed on 30 January 2023).
16. GBCA. Green Star—Design & As Built 2017, 1.2, 1–48. Available online: https://new.gbca.org.au/green-star/rating-system/design-and-built/ (accessed on 30 January 2023).
17. Green Building Council Indonesia. GREENSHIP Rating Tool for INTERIOR SPACE. 2012, 22. Available online: https://www.gbcindonesia.org/greens/existing (accessed on 30 January 2023).
18. Certivea Certification NF HQE Bâtiments Tertiaires En Exploitation. 2014; Available online: https://certivea.fr/solutions/hqe-batiment/ (accessed on 30 January 2023).
19. Ministry Republic of Austria for Sustainability and Tourism. Klimaaktiv Quality and Criteria New Buildings and Renovations. 2019; ISBN 9783990910054 Available online: https://www.klimaaktiv.at/bauen-sanieren.html (accessed on 30 January 2023).
20. USGBC. Leed v4.1 Building Design and Construction. 2021; Available online: https://www.usgbc.org/leed/v41 (accessed on 30 January 2023).
21. USGBC. LOTUS-New Construction V3. 2019; Available online: https://vgbc.vn/en/lotus-new-construction-lotus-nc/ (accessed on 30 January 2023).
22. TGBI. TREES—NC Thai’ s Rating of Energy and Environmental Sustainability; Volume 75. Available online: https://tgbi.or.th/uploads/trees/2017_03_TREES-EB-Eng.pdf (accessed on 30 January 2023).
23. Branco, P.T.B.S.; Alvim-Ferraz, M.C.M.; Martins, F.G.; Sousa, S.I.V. Children’s Exposure to Indoor Air in Urban Nurseries-Part I: CO2 and Comfort Assessment. Environ. Res.; 2015; 140, pp. 1-9. [DOI: https://dx.doi.org/10.1016/j.envres.2015.03.007]
24. Branco, P.T.B.S.; Nunes, R.A.O.; Alvim-Ferraz, M.C.M.; Martins, F.G.; Sousa, S.I.V. Children’s Exposure to Indoor Air in Urban Nurseries—Part II: Gaseous Pollutants’ Assessment. Environ. Res.; 2015; 142, pp. 662-670. [DOI: https://dx.doi.org/10.1016/j.envres.2015.08.026]
25. Csobod, É.; Annesi-Maesano, I.; Carrer, P.; Kephalopoulos, S.; Madureira, J.; Rudnai, P.; de Oliveira Fernandes, E. Schools Indoor Pollution & Health Observatory Network in Europe SINPHONIE; Publications Office of the European Union: Luxembourg, 2014; [DOI: https://dx.doi.org/10.2788/99220]
26. Baloch, R.M.; Maesano, C.N.; Christoffersen, J.; Banerjee, S.; Gabriel, M.; Csobod, É.; de Oliveira Fernandes, E.; Annesi-Maesano, I.; Szuppinger, P.; Prokai, R. et al. Indoor Air Pollution, Physical and Comfort Parameters Related to Schoolchildren’s Health: Data from the European SINPHONIE Study. Sci. Total Environ.; 2020; 739, 139870. [DOI: https://dx.doi.org/10.1016/j.scitotenv.2020.139870]
27. Vilcekova, S.; Meciarova, L.; Burdova, E.K.; Katunska, J.; Kosicanova, D.; Doroudiani, S. Indoor Environmental Quality of Classrooms and Occupants’ Comfort in a Special Education School in Slovak Republic. Build. Environ.; 2017; 120, pp. 29-40. [DOI: https://dx.doi.org/10.1016/j.buildenv.2017.05.001]
28. Harčárová, K. Indoor Air Quality in Classrooms of a Newly Built School. IOP Conf. Ser. Mater. Sci. Eng.; 2020; 867, 012008. [DOI: https://dx.doi.org/10.1088/1757-899X/867/1/012008]
29. De la Hoz-Torres, M.L.; Aguilar, A.J.; Costa, N.; Arezes, P.; Ruiz, D.P.; Martínez-Aires, M.D. Reopening Higher Education Buildings in Post-Epidemic COVID-19 Scenario: Monitoring and Assessment of Indoor Environmental Quality after Implementing Ventilation Protocols in Spain and Portugal. Indoor Air; 2022; 32, e13040. [DOI: https://dx.doi.org/10.1111/ina.13040]
30. Loreti, L.; Barbaresi, L.; De Cesaris, S.; Garai, M. Overall Indoor Quality of a Non-Renewed Secondary-School Building. Build. Acoust.; 2016; 23, pp. 47-58. [DOI: https://dx.doi.org/10.1177/1351010X16637533]
31. Leccese, F.; Salvadori, G.; Rocca, M.; Buratti, C.; Belloni, E. A Method to Assess Lighting Quality in Educational Rooms Using Analytic Hierarchy Process. Build. Environ.; 2020; 168, 106501. [DOI: https://dx.doi.org/10.1016/j.buildenv.2019.106501]
32. Russo, D.; Ruggiero, A. Choice of the Optimal Acoustic Design of a School Classroom and Experimental Verification. Appl. Acoust.; 2019; 146, pp. 280-287. [DOI: https://dx.doi.org/10.1016/j.apacoust.2018.11.019]
33. Rucińska, J.; Trzaski, A. Measurements and Simulation Study of Daylight Availability and Its Impact on the Heating, Cooling and Lighting Energy Demand in an Educational Building. Energies; 2020; 13, 2555. [DOI: https://dx.doi.org/10.3390/en13102555]
34. Aguilar, A.J.; de la Hoz-Torres, M.L.; Martínez-Aires, M.D.; Ruiz, D.P. Thermal Perception in Naturally Ventilated University Buildings in Spain during the Cold Season. Buildings; 2022; 12, 890. [DOI: https://dx.doi.org/10.3390/buildings12070890]
35. Ahmed, K.; Kuusk, K.; Heininen, H.; Arumägi, E.; Kalamees, T.; Hasu, T.; Lolli, N.; Kurnitski, J. Indoor Climate and Energy Performance in Nearly Zero Energy Day Care Centers and School Buildings. E3S Web Conf.; 2019; 111, 02003. [DOI: https://dx.doi.org/10.1051/e3sconf/201911102003]
36. Alves, C.; Nunes, T.; Silva, J.; Duarte, M. Comfort Parameters and Particulate Matter (PM10 and PM2.5) in School Classrooms and Outdoor Air. Aerosol Air Qual. Res.; 2013; 13, pp. 1521-1535. [DOI: https://dx.doi.org/10.4209/aaqr.2012.11.0321]
37. Annesi-Maesano, I.; Hulin, M.; Lavaud, F.; Raherison, C.; Kopferschmitt, C.; De Blay, F.; Charpin, D.A.; Denis, C. Poor Air Quality in Classrooms Related to Asthma and Rhinitis in Primary Schoolchildren of the French 6 Cities Study. Thorax; 2012; 67, pp. 682-688. [DOI: https://dx.doi.org/10.1136/thoraxjnl-2011-200391]
38. Baloch, R.M.; Maesano, C.N.; Christoffersen, J.; Mandin, C.; Csobod, E.; De, E.; Fernandes, O.; Annesi-Maesano, I. Daylight and School Performance in European Schoolchildren. Public Health; 2021; 18, 258. [DOI: https://dx.doi.org/10.3390/ijerph18010258]
39. Barmparesos, N.; Assimakopoulos, M.N.; Assimakopoulos, V.D.; Loumos, N.; Sotiriou, M.A.; Koukoumtzis, A. Indoor Air Quality and Thermal Conditions in a Primary School with a Green Roof System. Atmosphere; 2018; 9, 75. [DOI: https://dx.doi.org/10.3390/atmos9020075]
40. Becerra, J.A.; Lizana, J.; Gil, M.; Barrios-Padura, A.; Blondeau, P.; Chacartegui, R. Identification of Potential Indoor Air Pollutants in Schools. J. Clean. Prod.; 2020; 242, 118420. [DOI: https://dx.doi.org/10.1016/j.jclepro.2019.118420]
41. Branco, P.T.B.S.; Nunes, R.A.O.; Alvim-Ferraz, M.C.M.; Martins, F.G.; Sousa, S.I.V. Children’s Exposure to Radon in Nursery and Primary Schools. Int. J. Environ. Res. Public Health; 2016; 13, 386. [DOI: https://dx.doi.org/10.3390/ijerph13040386]
42. Brdarić, D.; Capak, K.; Gvozdić, V.; Barišin, A.; Jelinić, J.D.; Egorov, A.; Šapina, M.; Kalambura, S.; Kramarić, K. Indoor Carbon Dioxide Concentrations in Croatian Elementary School Classrooms during the Heating Season. Arh. Hig. Rada Toksikol.; 2019; 70, pp. 296-302. [DOI: https://dx.doi.org/10.2478/aiht-2019-70-3343]
43. Buratti, C.; Belloni, E.; Merli, F.; Ricciardi, P. A New Index Combining Thermal, Acoustic, and Visual Comfort of Moderate Environments in Temperate Climates. Build. Environ.; 2018; 139, pp. 27-37. [DOI: https://dx.doi.org/10.1016/j.buildenv.2018.04.038]
44. Canha, N.; Mandin, C.; Ramalho, O.; Wyart, G.; Ribéron, J.; Dassonville, C.; Hänninen, O.; Almeida, S.M.; Derbez, M. Assessment of Ventilation and Indoor Air Pollutants in Nursery and Elementary Schools in France. Indoor Air; 2016; 26, pp. 350-365. [DOI: https://dx.doi.org/10.1111/ina.12222]
45. Cequier, E.; Ionas, A.C.; Covaci, A.; Marcé, R.M.; Becher, G.; Thomsen, C. Occurrence of a Broad Range of Legacy and Emerging Flame Retardants in Indoor Environments in Norway. Environ. Sci. Technol.; 2014; 48, pp. 6827-6835. [DOI: https://dx.doi.org/10.1021/es500516u]
46. Chetoni, M.; Ascari, E.; Bianco, F.; Fredianelli, L.; Licitra, G.; Cori, L. Global Noise Score Indicator for Classroom Evaluation of Acoustic Performances in LIFE GIOCONDA Project. Noise Mapp.; 2016; 3, pp. 157-171. [DOI: https://dx.doi.org/10.1515/noise-2016-0012]
47. De Gennaro, G.; Farella, G.; Marzocca, A.; Mazzone, A.; Tutino, M. Indoor and Outdoor Monitoring of Volatile Organic Compounds in School Buildings: Indicators Based on Health Risk Assessment to Single out Critical Issues. Int. J. Environ. Res. Public Health; 2013; 10, pp. 6273-6291. [DOI: https://dx.doi.org/10.3390/ijerph10126273]
48. De Giuli, V.; Da Pos, O.; De Carli, M. Indoor Environmental Quality and Pupil Perception in Italian Primary Schools. Build. Environ.; 2012; 56, pp. 335-345. [DOI: https://dx.doi.org/10.1016/j.buildenv.2012.03.024]
49. De Giuli, V.; Zecchin, R.; Corain, L.; Salmaso, L. Measured and Perceived Environmental Comfort: Field Monitoring in an Italian School. Appl. Ergon.; 2014; 45, pp. 1035-1047. [DOI: https://dx.doi.org/10.1016/j.apergo.2014.01.004]
50. De Giuli, V.; Zecchin, R.; Corain, L.; Salmaso, L. Measurements of Indoor Environmental Conditions in Italian Classrooms and Their Impact on Childrens Comfort. Indoor Built Environ.; 2015; 24, pp. 689-712. [DOI: https://dx.doi.org/10.1177/1420326X14530586]
51. Dhoqina, P.; Tushe, K.; Xhixha, G.; Daci, B.; Bylyku, E. Measurements of Indoor Radon Concentrations in Schools in Some Cities of North Albania. AIP Conf. Proc.; 2019; 2075, 170003.
52. Erlandson, G.; Magzamen, S.; Carter, E.; Sharp, J.L.; Reynolds, S.J.; Schaeffer, J.W. Characterization of Indoor Air Quality on a College Campus: A Pilot Study. Int. J. Environ. Res. Public Health; 2019; 16, pp. 17-26. [DOI: https://dx.doi.org/10.3390/ijerph16152721]
53. Fabbri, K. Thermal Comfort Evaluation in Kindergarten: PMV and PPD Measurement through Datalogger and Questionnaire. Build. Environ.; 2013; 68, pp. 202-214. [DOI: https://dx.doi.org/10.1016/j.buildenv.2013.07.002]
54. Franci, D.; Aureli, T. Long- and Short-Term Indoor Radon Survey in the Ardea Municipality, South Rome. Radiat. Prot. Dosimetry; 2014; 162, pp. 625-629. [DOI: https://dx.doi.org/10.1093/rpd/ncu025]
55. Heracleous, C.; Michael, A. Experimental Assessment of the Impact of Natural Ventilation on Indoor Air Quality and Thermal Comfort Conditions of Educational Buildings in the Eastern Mediterranean Region during the Heating Period. J. Build. Eng.; 2019; 26, 100917. [DOI: https://dx.doi.org/10.1016/j.jobe.2019.100917]
56. Irulegi, O.; Serra, A.; Hernández, R. Data on Records of Indoor Temperature and Relative Humidity in a University Building. Data Br.; 2017; 13, pp. 248-252. [DOI: https://dx.doi.org/10.1016/j.dib.2017.05.029] [PubMed: https://www.ncbi.nlm.nih.gov/pubmed/28626790]
57. Istrate, M.A.; Catalina, T.; Cucos, A.; Dicu, T. Experimental Measurements of VOC and Radon in Two Romanian Classrooms. Energy Procedia; 2016; 85, pp. 288-294. [DOI: https://dx.doi.org/10.1016/j.egypro.2015.12.254]
58. Ivanova, K.; Stojanovska, Z.; Tsenova, M.; Badulin, V.; Kunovska, B. Measurement of Indoor Radon Concentration in Kindergartens in Sofia, Bulgaria. Radiat. Prot. Dosim.; 2014; 162, pp. 163-166. [DOI: https://dx.doi.org/10.1093/rpd/ncu251]
59. Ivanova, K.; Stojanovska, Z.; Djunakova, D.; Djounova, J. Analysis of the Spatial Distribution of the Indoor Radon Concentration in School’s Buildings in Plovdiv Province, Bulgaria. Build. Environ.; 2021; 204, 108122. [DOI: https://dx.doi.org/10.1016/j.buildenv.2021.108122]
60. Jovanović, M.; Vučićević, B.; Turanjanin, V.; Živković, M.; Spasojević, V. Investigation of Indoor and Outdoor Air Quality of the Classrooms at a School in Serbia. Energy; 2014; 77, pp. 42-48. [DOI: https://dx.doi.org/10.1016/j.energy.2014.03.080]
61. Klatte, M.; Hellbroock, J. Effects of Classroom Acoustics on Performance and Wellbeing in Elementary School Children: A Field Study. Environ. Behav.; 2010; 42, pp. 659-692. [DOI: https://dx.doi.org/10.1177/0013916509336813]
62. Kojo, K.; Kurttio, P. Indoor Radon Measurements in Finnish Daycare Centers and Schools-Enforcement of the Radiation Act. Int. J. Environ. Res. Public Health; 2020; 17, 2877. [DOI: https://dx.doi.org/10.3390/ijerph17082877]
63. Korsavi, S.S.; Montazami, A. Developing a Valid Method to Study Adaptive Behaviours with Regard to IEQ in Primary Schools. Build. Environ.; 2019; 153, pp. 1-16. [DOI: https://dx.doi.org/10.1016/j.buildenv.2019.02.018]
64. Kristiansen, J.; Lund, S.P.; Nielsen, P.M.; Persson, R.; Shibuya, H. Determinants of Noise Annoyance in Teachers from Schools with Different Classroom Reverberation Times. J. Environ. Psychol.; 2011; 31, pp. 383-392. [DOI: https://dx.doi.org/10.1016/j.jenvp.2011.08.005]
65. Krugly, E.; Martuzevicius, D.; Sidaraviciute, R.; Ciuzas, D.; Prasauskas, T.; Kauneliene, V.; Stasiulaitiene, I.; Kliucininkas, L. Characterization of Particulate and Vapor Phase Polycyclic Aromatic Hydrocarbons in Indoor and Outdoor Air of Primary Schools. Atmos. Environ.; 2014; 82, pp. 298-306. [DOI: https://dx.doi.org/10.1016/j.atmosenv.2013.10.042]
66. Campano-Laborda, M.Á.; Domínguez-Amarillo, S.; Fernández-Agüera, J.; Acosta, I. Indoor Comfort and Symptomatology in Non-University Educational Buildings: Occupants’ Perception. Atmosphere; 2020; 11, 357. [DOI: https://dx.doi.org/10.3390/atmos11040357]
67. Larsson, K.; Lindh, C.H.; Jönsson, B.A.; Giovanoulis, G.; Bibi, M.; Bottai, M.; Bergström, A.; Berglund, M. Phthalates, Non-Phthalate Plasticizers and Bisphenols in Swedish Preschool Dust in Relation to Children’s Exposure. Environ. Int.; 2017; 102, pp. 114-124. [DOI: https://dx.doi.org/10.1016/j.envint.2017.02.006]
68. Liaud, C.; Chouvenc, S.; Le Calvé, S. Simultaneous Monitoring of Particle-Bound PAHs inside a Low-Energy School Building and Outdoors over Two Weeks in France. Atmosphere; 2021; 12, 108. [DOI: https://dx.doi.org/10.3390/atmos12010108]
69. Madureira, J.; Paciência, I.; Rufo, J.; Ramos, E.; Barros, H.; Teixeira, J.P.; de Oliveira Fernandes, E. Indoor Air Quality in Schools and Its Relationship with Children’s Respiratory Symptoms. Atmos. Environ.; 2015; 118, pp. 145-156. [DOI: https://dx.doi.org/10.1016/j.atmosenv.2015.07.028]
70. Mainka, A.; Zajusz-Zubek, E. Indoor Air Quality in Urban and Rural Preschools in Upper Silesia, Poland: Particulate Matter and Carbon Dioxide. Int. J. Environ. Res. Public Health; 2015; 12, pp. 7697-7711. [DOI: https://dx.doi.org/10.3390/ijerph120707697]
71. Mikulski, W.; Radosz, J. Acoustics of Classrooms in Primary Schools—Results of the Reverberation Time and the Speech Transmission Index Assessments in Selected Buildings. Arch. Acoust.; 2011; 36, pp. 777-793. [DOI: https://dx.doi.org/10.2478/v10168-011-0052-6]
72. Müllerová, M.; Mazur, J.; Csordás, A.; Grzadziel, D.; Holý, K.; Kovács, T.; Kozak, K.; Kureková, P.; Nagy, E.; Neznal, M. et al. Preliminary Results of Radon Survey in the Kindergartens of V4 Countries. Radiat. Prot. Dosim.; 2017; 177, pp. 95-98. [DOI: https://dx.doi.org/10.1093/rpd/ncx155]
73. Nunes, R.A.O.; Branco, P.T.B.S.; Alvim-Ferraz, M.C.M.; Martins, F.G.; Sousa, S.I.V. Gaseous Pollutants on Rural and Urban Nursery Schools in Northern Portugal. Environ. Pollut.; 2016; 208, pp. 2-15. [DOI: https://dx.doi.org/10.1016/j.envpol.2015.07.018]
74. Oldham, E.; Kim, H. IEQ Field Investigation in High-Performance, Urban Elementary Schools. Atmosphere; 2020; 11, 81. [DOI: https://dx.doi.org/10.3390/atmos11010081]
75. Oliveira, M.; Slezakova, K.; Delerue-Matos, C.; Pereira, M.D.C.; Morais, S. Assessment of Polycyclic Aromatic Hydrocarbons in Indoor and Outdoor Air of Preschool Environments (3-5 Years Old Children). Environ. Pollut.; 2016; 208, pp. 382-394. [DOI: https://dx.doi.org/10.1016/j.envpol.2015.10.004] [PubMed: https://www.ncbi.nlm.nih.gov/pubmed/26552524]
76. Oliveira, M.; Slezakova, K.; Madureira, J.; de Oliveira Fernandes, E.; Delerue-Matos, C.; Morais, S.; do Carmo Pereira, M. Polycyclic Aromatic Hydrocarbons in Primary School Environments: Levels and Potential Risks. Sci. Total Environ.; 2017; 575, pp. 1156-1167. [DOI: https://dx.doi.org/10.1016/j.scitotenv.2016.09.195] [PubMed: https://www.ncbi.nlm.nih.gov/pubmed/27693148]
77. Oliveira, M.; Slezakova, K.; Delerue-Matos, C.; do Pereira, M.C.; Morais, S. Indoor Air Quality in Preschools (3- to 5-Year-Old Children) in the Northeast of Portugal during Spring–Summer Season: Pollutants and Comfort Parameters. J. Toxicol. Environ. Health-Part A Curr. Issues; 2017; 80, pp. 740-755. [DOI: https://dx.doi.org/10.1080/15287394.2017.1286932] [PubMed: https://www.ncbi.nlm.nih.gov/pubmed/28569620]
78. Onishchenko, A.; Malinovsky, G.; Vasilyev, A.; Zhukovsky, M. Radon Measurements in Kindergartens in Ural Region (Russia). Radiat. Prot. Dosim.; 2017; 177, pp. 112-115. [DOI: https://dx.doi.org/10.1093/rpd/ncx156] [PubMed: https://www.ncbi.nlm.nih.gov/pubmed/29036708]
79. Papadopoulos, G.; Panaras, G.; Tolis, E. Thermal Comfort and Indoor Air Quality Assessment in University Classrooms. IOP Conf. Ser. Earth Environ. Sci.; 2020; 410, 012095. [DOI: https://dx.doi.org/10.1088/1755-1315/410/1/012095]
80. Papazoglou, E.; Moustris, K.P.; Nikas, K.S.P.; Nastos, P.T.; Statharas, J.C. Assessment of Human Thermal Comfort Perception in a Non-Air-Conditioned School Building in Athens, Greece. Energy Procedia; 2019; 157, pp. 1343-1352. [DOI: https://dx.doi.org/10.1016/j.egypro.2018.11.299]
81. Dias Pereira, L.; Raimondo, D.; Corgnati, S.P.; Gameiro da Silva, M. Assessment of Indoor Air Quality and Thermal Comfort in Portuguese Secondary Classrooms: Methodology and Results. Build. Environ.; 2014; 81, pp. 69-80. [DOI: https://dx.doi.org/10.1016/j.buildenv.2014.06.008]
82. Pereira, L.D.; Cardoso, E.; Da Silva, M.G. Indoor Air Quality Audit and Evaluation on Thermal Comfort in a School in Portugal. Indoor Built Environ.; 2015; 24, pp. 256-268. [DOI: https://dx.doi.org/10.1177/1420326X13508966]
83. Persson, J.; Wang, T.; Hagberg, J. Organophosphate Flame Retardants and Plasticizers in Indoor Dust, Air and Window Wipes in Newly Built Low-Energy Preschools. Sci. Total Environ.; 2018; 628–629, pp. 159-168. [DOI: https://dx.doi.org/10.1016/j.scitotenv.2018.02.053]
84. Poulin, P.; Leclerc, J.M.; Dessau, J.C.; Deck, W.; Gagnon, F. Radon Measurement in Schools Located in Three Priority Investigation Areas in the Province of Quebec, Canada. Radiat. Prot. Dosim.; 2012; 151, pp. 278-289. [DOI: https://dx.doi.org/10.1093/rpd/ncr483]
85. Raffy, G.; Mercier, F.; Blanchard, O.; Derbez, M.; Dassonville, C.; Bonvallot, N.; Glorennec, P.; Le Bot, B. Semi-Volatile Organic Compounds in the Air and Dust of 30 French Schools: A Pilot Study. Indoor Air; 2017; 27, pp. 114-127. [DOI: https://dx.doi.org/10.1111/ina.12288]
86. Ramalho, O.; Wyart, G.; Mandin, C.; Blondeau, P.; Cabanes, P.A.; Leclerc, N.; Mullot, J.U.; Boulanger, G.; Redaelli, M. Association of Carbon Dioxide with Indoor Air Pollutants and Exceedance of Health Guideline Values. Build. Environ.; 2015; 93, pp. 115-124. [DOI: https://dx.doi.org/10.1016/j.buildenv.2015.03.018]
87. Rivas, I.; Viana, M.; Moreno, T.; Pandolfi, M.; Amato, F.; Reche, C.; Bouso, L.; Àlvarez-Pedrerol, M.; Alastuey, A.; Sunyer, J. et al. Child Exposure to Indoor and Outdoor Air Pollutants in Schools in Barcelona, Spain. Environ. Int.; 2014; 69, pp. 200-212. [DOI: https://dx.doi.org/10.1016/j.envint.2014.04.009]
88. Romagnoli, P.; Balducci, C.; Perilli, M.; Gherardi, M.; Gordiani, A.; Gariazzo, C.; Gatto, M.P.; Cecinato, A. Indoor PAHs at Schools, Homes and Offices in Rome, Italy. Atmos. Environ.; 2014; 92, pp. 51-59. [DOI: https://dx.doi.org/10.1016/j.atmosenv.2014.03.063]
89. Rovelli, S.; Cattaneo, A.; Nuzzi, C.P.; Spinazzè, A.; Piazza, S.; Carrer, P.; Cavallo, D.M. Airborne Particulate Matter in School Classrooms of Northern Italy. Int. J. Environ. Res. Public Health; 2014; 11, pp. 1398-1421. [DOI: https://dx.doi.org/10.3390/ijerph110201398]
90. Sarantopoulos, G.; Lykoudis, S.; Kassomenos, P. Noise Levels in Primary Schools of Medium Sized City in Greece. Sci. Total Environ.; 2014; 482–483, pp. 493-500. [DOI: https://dx.doi.org/10.1016/j.scitotenv.2013.09.010]
91. Langer, S.; Ekberg, L.; Teli, D.; Cabovska, B.; Bekö, G.; Wargocki, P. Study of the Measured and Perceived Indoor Air Quality in Swedish School Classrooms. IOP Conf. Ser. Earth Environ. Sci.; 2020; 588, 032070. [DOI: https://dx.doi.org/10.1088/1755-1315/588/3/032070]
92. Senitkova, I.J. Occurrence of Indoor VOCs in Nursery School—Case Study. IOP Conf. Ser. Mater. Sci. Eng.; 2017; 245, 082027.
93. Shield, B.; Conetta, R.; Dockrell, J.; Connolly, D.; Cox, T.; Mydlarz, C. A Survey of Acoustic Conditions and Noise Levels in Secondary School Classrooms in England. J. Acoust. Soc. Am.; 2015; 137, pp. 177-188. [DOI: https://dx.doi.org/10.1121/1.4904528]
94. Simanic, B.; Nordquist, B.; Bagge, H.; Johansson, D. Indoor Air Temperatures, CO2 Concentrations and Ventilation Rates: Long-Term Measurements in Newly Built Low-Energy Schools in Sweden. J. Build. Eng.; 2019; 25, 100827. [DOI: https://dx.doi.org/10.1016/j.jobe.2019.100827]
95. Sivanantham, S.; Dassonville, C.; Grégoire, A.; Malingre, L.; Ramalho, O.; Mandin, C. Coexposure to Indoor Pollutants in French Schools and Associations with Building Characteristics. Energy Build.; 2021; 252, 111424. [DOI: https://dx.doi.org/10.1016/j.enbuild.2021.111424]
96. Slezakova, K.; de Oliveira Fernandes, E.; do Pereira, M.C. Assessment of Ultrafine Particles in Primary Schools: Emphasis on Different Indoor Microenvironments. Environ. Pollut.; 2019; 246, pp. 885-895. [DOI: https://dx.doi.org/10.1016/j.envpol.2018.12.073] [PubMed: https://www.ncbi.nlm.nih.gov/pubmed/31159138]
97. Smith, K. Explorations of Acoustic Trends in Data Logged in K-12 Classrooms; Architetural Engineering and Construction, Durham School. 2019; Available online: https://digitalcommons.unl.edu/cgi/viewcontent.cgi?article=1058&context=archengdiss (accessed on 30 January 2023).
98. Stamp, S.; Burman, E.; Shrubsole, C.; Chatzidiakou, L.; Mumovic, D.; Davies, M. Long-Term, Continuous Air Quality Monitoring in a Cross-Sectional Study of Three UK Non-Domestic Buildings. Build. Environ.; 2020; 180, 107071. [DOI: https://dx.doi.org/10.1016/j.buildenv.2020.107071]
99. Toftum, J.; Kjeldsen, B.U.; Wargocki, P.; Menå, H.R.; Hansen, E.M.N.; Clausen, G. Association between Classroom Ventilation Mode and Learning Outcome in Danish Schools. Build. Environ.; 2015; 92, pp. 494-503. [DOI: https://dx.doi.org/10.1016/j.buildenv.2015.05.017]
100. Trevisi, R.; Leonardi, F.; Simeoni, C.; Tonnarini, S.; Veschetti, M. Indoor Radon Levels in Schools of South-East Italy. J. Environ. Radioact.; 2012; 112, pp. 160-164. [DOI: https://dx.doi.org/10.1016/j.jenvrad.2012.05.030]
101. Haverinen-Shaughnessy, U.; Shaughnessy, R.J.; Cole, E.C.; Toyinbo, O.; Moschandreas, D.J. An Assessment of Indoor Environmental Quality in Schools and Its Association with Health and Performance. Build. Environ.; 2015; 93, pp. 35-40. [DOI: https://dx.doi.org/10.1016/j.buildenv.2015.03.006]
102. Verriele, M.; Schoemaecker, C.; Hanoune, B.; Leclerc, N.; Germain, S.; Gaudion, V.; Locoge, N. The MERMAID Study: Indoor and Outdoor Average Pollutant Concentrations in 10 Low-Energy School Buildings in France. Indoor Air; 2016; 26, pp. 702-713. [DOI: https://dx.doi.org/10.1111/ina.12258]
103. Villanueva, F.; Tapia, A.; Lara, S.; Amo-Salas, M. Indoor and Outdoor Air Concentrations of Volatile Organic Compounds and NO2 in Schools of Urban, Industrial and Rural Areas in Central-Southern Spain. Sci. Total Environ.; 2018; 622–623, pp. 222-235. [DOI: https://dx.doi.org/10.1016/j.scitotenv.2017.11.274]
104. Vornanen-Winqvist, C.; Salonen, H.; Järvi, K.; Andersson, M.A.; Mikkola, R.; Marik, T.; Kredics, L.; Kurnitski, J. Effects of Ventilation Improvement on Measured and Perceived Indoor Air Quality in a School Building with a Hybrid Ventilation System. Int. J. Environ. Res. Public Health; 2018; 15, 1414. [DOI: https://dx.doi.org/10.3390/ijerph15071414]
105. Vornanen-Winqvist, C.; Järvi, K.; Andersson, M.A.; Duchaine, C.; Létourneau, V.; Kedves, O.; Kredics, L.; Mikkola, R.; Kurnitski, J.; Salonen, H. Exposure to Indoor Air Contaminants in School Buildings with and without Reported Indoor Air Quality Problems. Environ. Int.; 2020; 141, 105781. [DOI: https://dx.doi.org/10.1016/j.envint.2020.105781]
106. Curguz, Z.; Venoso, G.; Zunic, Z.S.; Mirjanic, D.; Ampollini, M.; Carpentieri, C.; Di Carlo, C.; Caprio, M.; Alavantic, D.; Kolarz, P. et al. Spatial Variability of Indoor Radon Concentration in Schools: Implications on Radon Measurement Protocols. Radiat. Prot. Dosim.; 2020; 191, pp. 133-137. [DOI: https://dx.doi.org/10.1093/rpd/ncaa137]
107. Zečević, N.; Husika, A.; Džaferović, E. Impact of Energy Efficiency Measures on Indoor Air Quality in Building of Mechanical Engineering Faculty Sarajevo. Ann. DAAAM Proc. Int. DAAAM Symp.; 2018; 29, pp. 0197-0201. [DOI: https://dx.doi.org/10.2507/29th.daaam.proceedings.028]
108. Zhong, L.; Su, F.C.; Batterman, S. Volatile Organic Compounds (VOCs) in Conventional and High Performance School Buildings in the U.S. Int. J. Environ. Res. Public Health; 2017; 14, 100. [DOI: https://dx.doi.org/10.3390/ijerph14010100]
109. Živković, M.; Jovašević-Stojanović, M.; Cvetković, A.; Lazović, I.; Tasić, V.; Stevanović, Ž.; Gržetić, I. Pahs Levels in Gas and Particle-Bound Phase in Schools at Different Locations in Serbia. Chem. Ind. Chem. Eng. Q.; 2015; 21, pp. 159-167. [DOI: https://dx.doi.org/10.2298/CICEQ140206016Z]
110. Fanger, P.O. Thermal Comfort. Analysis and Applications in Environmental Engineering; Danish Technical Press: Copenhagen, Denmark, 1970.
111. Basner, M.; Babisch, W.; Davis, A.; Brink, M.; Clark, C.; Janssen, S.; Stansfeld, S. Auditory and Non-Auditory Effects of Noise on Health. Lancet; 2014; 383, pp. 1325-1332. [DOI: https://dx.doi.org/10.1016/S0140-6736(13)61613-X]
112.
113. Bradley, J.S.; Sato, H. The Intelligibility of Speech in Elementary School Classrooms. J. Acoust. Soc. Am.; 2008; 123, pp. 2078-2086. [DOI: https://dx.doi.org/10.1121/1.2839285]
114. Subramaniam, N.; Ramachandraiah, A. Speech Intelligibility Issues in Classroom Acoustics- A Review. J. Inst. Eng. Archit. Eng. Div.; 2006; 87, pp. 29-33.
115.
116.
117. Ragazzi, M.; Albatici, R.; Schiavon, M.; Ferronato, N.; Torretta, V. CO2 Measurements for Unconventional Management of Indoor Air Quality. WIT Trans. Ecol. Environ.; 2019; 236, pp. 277-286. [DOI: https://dx.doi.org/10.2495/AIR190271]
118. Trocquet, C.; Bernhardt, P.; Guglielmino, M.; Malandain, I.; Liaud, C.; Englaro, S.; Le Calvé, S. Near Real-Time Monitoring of Formaldehyde in a Low-Energy School Building. Atmosphere; 2019; 10, 763. [DOI: https://dx.doi.org/10.3390/atmos10120763]
119. Madureira, J.; Paciência, I.; Rufo, J.; Severo, M.; Ramos, E.; Barros, H.; de Oliveira Fernandes, E. Source Apportionment of CO2, PM10 and VOCs Levels and Health Risk Assessment in Naturally Ventilated Primary Schools in Porto, Portugal. Build. Environ.; 2016; 96, pp. 198-205. [DOI: https://dx.doi.org/10.1016/j.buildenv.2015.11.031]
120. Arlian, L.G.; Neal, J.S.; Morgan, M.S.; Vyszenski-Moher, D.A.L.; Rapp, C.M.; Alexander, A.K. Reducing Relative Humidity Is a Practical Way to Control Dust Mites and Their Allergens in Homes Temperate Climates. J. Allergy Clin. Immunol.; 2001; 107, pp. 99-104. [DOI: https://dx.doi.org/10.1067/mai.2001.112119]
121. Lamberti, G.; Salvadori, G.; Leccese, F.; Fantozzi, F.; Bluyssen, P.M. Advancement on Thermal Comfort in Educational Buildings: Current Issues and Way Forward. Sustainability; 2021; 13, 10315. [DOI: https://dx.doi.org/10.3390/su131810315]
122. Shield, B.M.; Dockrell, J.E. The Effects of Noise on Children at School: A Review. Build. Acoust.; 2003; 10, pp. 97-116. [DOI: https://dx.doi.org/10.1260/135101003768965960]
123. ASHRAE Board of Directors. ASHRAE Position Document on Indoor Carbon Dioxide; 2022; Volume 21. Available online: https://www.ashrae.org/file%20library/about/position%20documents/pd_indoorcarbondioxide_2022.pdf (accessed on 30 January 2023).
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.
Abstract
As attention to indoor environmental quality (IEQ) grows, a systematic strategy for assessing IEQ in schools needs to be developed. For this purpose, this paper presents a summary of parameters measured in school classrooms to characterize the quality of thermal, acoustic, and visual environments and indoor air quality (IAQ). The summary is based on a review of published literature reporting measurements in schools in Europe and North America in the past ten years. It also summarizes the measurement protocols and measured concentrations. Eighty-eight papers describing measurements in schools were identified and analyzed. No unique standardized measuring method was used in the reviewed studies and different parameters were measured. The most often measured parameters were those describing the thermal environment and IAQ. The former mainly comprised air temperature and relative humidity. The latter mainly comprised concentrations of carbon dioxide, particulate matter, radon, formaldehyde, and some volatile organic compounds. The measured parameters describing acoustic and visual environments mainly comprised noise level, reverberation time, and illuminance. A few studies reported additional measurements of radiant temperature, operative temperature, and speech intelligibility. Measurement protocols from different studies show inconsistency in sampling duration and location and expressed results. Measured concentrations also show high variation between studies, with some pollutants exceeding the threshold values proposed by local and/or international organizations such as the World Health Organization (WHO). This review provides the reference for developing a rating scheme and protocols for uniform characterization of classroom IEQ.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
Details







1 Scientific and Technical Center for Building (CSTB), Health and Comfort Department, French Indoor Air Quality Observatory (OQAI), 77420 Champs sur Marne, France; IMT Atlantique, CNRS, GEPEA, UMR 6144, CEDEX 3, 44307 Nantes, France
2 Scientific and Technical Center for Building (CSTB), Health and Comfort Department, French Indoor Air Quality Observatory (OQAI), 77420 Champs sur Marne, France
3 IMT Atlantique, CNRS, GEPEA, UMR 6144, CEDEX 3, 44307 Nantes, France
4 International Centre for Indoor Environment and Energy, Department of Environmental and Resource Engineering (DTU SUSTAIN), Technical University of Denmark (DTU), 2800 Lyngby, Denmark