Full text

Turn on search term navigation

© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.

Abstract

The paper presents a cause-and-effect analysis of the failure of a 130 MWt gas-fired water boiler. The fault was a rupture of the helically finned tubes in the first rows of the second-stage water heater (ECO2). The high frequency of failures forced the boiler user to investigate their causes. The rapid drop in water flow in the ECO2 and the tightly finned pipes suggested that the permissible operating temperature of the steel used was exceeded. The only possible way to assess the working conditions was through a CFD simulation of the operation of the ECO2. Validated with the data acquisition system, the results show that the main reason for the failure was the overheating of the first rows of finned water heater pipes, regardless of the boiler load. The high heat flux value, exceeding 500,000 W/m2, and the increased flue gas temperature in front of the ECO2, almost reaching 900 °C, affected the appearance of the boiling film, limiting the cooling of the tube wall. Heat radiation and eddies behind the tubes significantly impacted the non-uniform temperature distribution, resulting in high pipe wall stress. By analyzing the service life of the first row of pipes based on the Larson–Miller parameter, it was concluded that the pipes would fail after only a few tens of hours.

Details

Title
Analysis of the Causes of the Emergency Shutdown of Natural Gas-Fired Water Peak Boilers at the Large Municipal Combined Heat and Power Plant
Author
Trojan, Marcin 1   VIAFID ORCID Logo  ; Dzierwa, Piotr 1   VIAFID ORCID Logo  ; Taler, Jan 2   VIAFID ORCID Logo  ; Granda, Mariusz 1   VIAFID ORCID Logo  ; Kaczmarski, Karol 1   VIAFID ORCID Logo  ; Taler, Dawid 1 ; Sobota, Tomasz 1   VIAFID ORCID Logo 

 Department of Thermal Engineering and Air Protection, Faculty of Environmental Engineering and Energy, Cracow University of Technology, 31-155 Cracow, Poland[email protected] (K.K.); [email protected] (D.T.); [email protected] (T.S.) 
 Department of Energy, Cracow University of Technology, 31-155 Cracow, Poland; [email protected] 
First page
6278
Publication year
2023
Publication date
2023
Publisher
MDPI AG
e-ISSN
19961073
Source type
Scholarly Journal
Language of publication
English
ProQuest document ID
2862335055
Copyright
© 2023 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.