Abstract
This paper presents the design of earthing system for 132 KV substation and simulation for calculation of required parameters. This paper is to provide information pertinent to safe earthing practices in ac substation design and to establish the safe limits of potential difference under normal and fault conditions. The grounding grid system of a practical 220 kV substation is calculated by MATLAB program. The supporting data has been obtained from actual field tested at the substation. Standard equations are used in the design of earthing system to get desired parameters such as touch and step voltage criteria for safety, earth resistance, grid resistance, maximum grid current, minimum conductor size and electrode size, maximum fault current level and resistivity of soil. By selection the proper horizontal conductor size, vertical electrode size and soil resistivity, the best choice of the project for safety is performed. This paper mentions the calculation of the desired parameters which are simulated by MATLAB program. Some simulated results are evaluated.
Keywords
component; Safe earthing system, Grounding, resistivity , AC substation, MATLAB program, Flowchart
(ProQuest: ... denotes formulae omitted.)
1. Introduction
In substation earthing system is essential not only to provide the protection of people working in the vicinity of earthed facilities and equipments against danger of electric shock but to maintain proper function of electrical system. Reliability and security are to be taken in considerations as well as adherence to statutory obligations (IEEE and Indian standards on electrical safety [1-2] and environmental aspects). Earthing system thus design must be easily maintained and future expansion must be taken into account while designing the dimensions of earth mat.
This paper is concerned with earthing practices and design for outdoor AC substation for power frequency in the range of 50 Hz. DC substation GIS and lightening effects are not covered in this paper. With proper caution, the method described here is also applicable to indoor portion of such substation. By using proper conductor and electrode size, earthing system may be able to overcome lightening effects.
2. Earthing system for a substation
A. Components of earthing system
An effective substation earthing system typically consists of earth rods, connecting cables from buried earthing grid to metallic parts of structures and equipments, connections to earthed system neutrals, and the earth surface insulating covering material briefly discussed in [1,3]. Current flowing into the earthing grid from lightening arrester operation impulse or switching surge flashover of insulators and line to ground fault current from the bus or connected transmission lines all cause potential differences between earthed points in the substation. Without a properly designed earthing system, large potential differences can exist between different points within the substation itself. Under normal circumstances, it is the current constitutes the main threat to personal.
B. Data needed for design of earthing
* Substation grid area
* Soil resistivity at the site
* Fault clearing time
* Maximum grid current
* Resistivity of soil at surface
C. Factors on which design of earthmat depends
* Materials used for earth electrodes and conductors must be chosen carefully taking into account physical, chemical and economical constraints. Ground conductor must be adequate for fault current (considering corrosion). Basic requirements are thoroughly studied in paper [4].
* Conductor sizing depends on fault current and conductivity as well as mechanical strength of material used.
* Resistivity of soil and surface layer determines the STEP and TOUCH potentials, which determine safe values of operation as described in reference [1, 5-9]. Also the multilayer resistivity has been a subject of continuous attention by the researchers [10-13].
* A good grounding system provides a low resistance in order to minimize GPR (ground potential rise)[14].
* Grid geometry is a major factor in determining the step, touch and mesh potential contours and current distribution in grid. The limitations on the physical parameters of a ground grid are based on economics and the physical limitations of the installation of the grid.
D. Fault Clearing Time
The faults clearing time is governed by system stability consideration and depend on protection and switchgear equipment. Generally a value of 0.5 seconds is assumed.
The size of the conductor is based on a time of 1 second.
E. Determination of Maximum Grid Current
A single line to ground fault is more common and causes more fault current as compared to a double line to ground fault. Therefore , the design is based on single line to
ground fault current. For calculation of this current grid resistance and fault resistance are assumed to be zero. Then Ig=SfIf
Where
Ig= symmetrical grid current , Amp
If= rms value of symmetrical ground fault current, Amp
Sf= current division factor relating the magnitude of fault current to that of its portion flowing in the earthing grid.
Only a part of the total fault current flows through the grid. The remaining current flows through the overhead ground wires and other ground return paths. The factor Sf gives this current division and can be calculated, if the system data is known, from the value of Ig the design value of grid current is found as
...
Where
I= maximum grid current
Gf= A factor to account for increase in fault current due to system growth during life span of grid.
Df= Decrement factor to account for asymmetry of the fault current wave.
Typical values of Gf assumed in design, lie in the range of 1.2 to 1.5 depending on the rate of growth of the system.
F. Selection of Electrode material
The material for grounding grid should have good conductivity, be mechanically rugged and resist fusing and deterioration of joints.
Copper was very commonly used in the past. It has high conductivity and is resistant to underground corrosion.
However, a grid of copper forms a galvanic cell with other buried structure and pipes and is likely to hasten the corrosion of the latter. Aluminium is not used because of corrosion problem.
3. Mathematical Description
G. Safe limits and values of potentials
The safety of a person depends on preventing the critical amount of shock energy from being absorbed. The maximum driving voltage of any accidental circuit should not exceed the limits defined as follows.
The tolerable step voltage criteria is
... (1)
The tolerable touch voltage criteria is
... (2)
Where
Cs = 1 for no protective surface layer
ρs= the resistivity of the surface material in A-m
ts = duration of shock circuit in seconds
The minimum conductor size formula is mentioned below-
... (3)
Where
...
tc = time of current flow in sec
TCAP = thermal capacity factor
For grounding resistance, the following formula is used
... (4)
Where
ρ = soil resistivity
Lt = total length of grid conductor
A = total area enclosed by earth grid
h = depth of earth grid conductor
For calculation of grid current, equation (5) is used
... (5)
Where
Ig = maximum grid current
3Io = symmetrical fault current in substation for Conductor sizing in A
Sf = current diversity factor
Equation (6) is expressed for grid potential rise (GPR)
... (6)
Maximum attainable step and touch voltages are given by: Formula for c-alculation of mesh and step voltage are
... (7)
... (8)
Where
ρ = soil resistivity, ohms-m
Em = mesh voltage at the center of corner mesh
Es = step voltage between point
Km = spacing factor for mesh voltage
Ks = spacing factor of step voltage
Ki = correct factor for grid geometry
... (9)
Where
D = spacing between conductor of the grid
d = diameter of grid conductor
Km = spacing factor for mesh voltage
Kii = 1 for grids with rods along perimeter
Kh = Corrective weighting factor for grid depth
... (10)
Where
D = spacing between conductor of the grid
h = depth of burial grid conductor
n = number of parallel conductor in one direction
The length required to keep mesh voltage within safe limits, can be calculated by
... (11)
If the length of conductor in the Preliminary design is less than that given eqn. (11) a revision in design is necessary.
H. Design procedure
Values of maximum attainable touch voltages are calculated. If the GPR of the preliminary design is below the tolerable touch voltage, no further analysis is necessary. Only additional conductor required to provide access to equipment grounds is necessary.
If the computed mesh voltage is below the tolerable touch voltage, the design may be complete. If the computed mesh voltage is greater than the tolerable touch voltage, the preliminary design should be revised. If both the computed touch and step voltages are below the tolerable voltages, the design needs only the refinements required to provide access to equipment grounds. If not, the preliminary design must be revised.
Further for the safe design we need to compare the length of the electrode in the preliminary design to the length of the electrode required to keep mesh voltage within safe limits
If either the step or touch tolerable limits are exceeded, revision of the grid design is required. These revisions may include smaller conductor spacing, additional ground rods, and use of closer spacing of conductor. In case the length given by eqn. (11) is too small to allow for connections to all equipments, more conductor may be required even though it is not necessary for safety ,etc as discussed in reference [1].
If the length of the conductor in the preliminary design is less than the length required to keep mesh voltage within safe limits. , then the design needs to be revised by entering more number of electrodes or by decreasing spacing between the conductors, otherwise the design is accurate. Further, if the Ground Potential Rise (R*Ig) is less than the tolerable value of touch potential then the design of the electrical grid is considered to be safe otherwise we need to guard personnel and other communication equipment against transferred potential.
Checking of step Potential:-
The tolerable step potential and actual step potential can be calculated from eqn (1) and eqn (8). If actual step potential is more than tolerable, a revision in design is necessary. The final step in design includes provision of closer meshes in the area frequently visited by operating personnel, additional ground rods for surge arrester leads, etc., and provision of risers for connection to equipments.
Impulse behaviour of earthing system:
The degree of protection provided by an earthing system under lightning discharge conditions depends on its impulse impedance (i.e.,impedance under impulse conditions) and not the power frequency resistance. The impulse impedance is different from the power frequency resistance due to effect of 1st soil ionization 2nd electrode inductance.
When the magnitude of impulse current is high, the soil in the vicinity of electrode may break-down causing a decrease in resistance. When the length of electrode is large, its inductance may cause only a part of the earthing system to be effective in dissipating current and, thus result in an increase in impedance.
The relative contributions of these two factors depend on the type of earthing system. The effect of soil ionization is very predominant in driven rods so that the impulse resistance of a driven rod is always less than its power frequency resistance.
The whole procedure can be shown by this flowchart:
4. Result
These results are obtained by a MATLAB program.
5. Significance and Touch Voltage
The step and touch voltages are dangerous for human body. Human body may get electric shocks from step and touch voltages. From the safety point of view it is necessary to calculate step and touch voltage. When high voltage substations are designed step and touch voltages should be calculated and must be in specified standard. The expected shock current caused by touch voltage can be effectively limited by applying inexpensive insulating layers on the earth's surface .The limits of step and touch potentials varies in different seasons because the resistivity of the soil layer is affected by different seasons .The step and touch voltage calculations are very significant while designing substation.
6. Conclusion
This paper has a focus on designing of an AC substation.The results for earthing system design are obtained by MATLAB program for earthing conductor and vertical earth electrode mild steel is used.
ACKNOWLEDGEMENT
The author wish to thank Er. O. P. Rahi for his guidance and moral support provided during this research effort, and Dr. M.G.Sharma for helping with substation data.
References
[1] N.M. Tabatabaei, S.R. Mortezaeei; -Design of Grounding System in Substation by ETAP Intelligent Softwere,IJTPE Journal, March 2010, Page(s):45-49
[2] Chae-Kyun Jung; Jong-kee choi; Ji-won Kang, -A study on effect of grounding system on transient voltage in 154kV Substation, IEEE Conference Publications, 2009, Page(s): 1-6
[3] Ladanyi, J. -Survey of the equivalent Substation earth current and earth impedance for transformer Station, IEEE Conference Publications, 2011, Page(s): 1-5
[4] Lee, C.H; Lin, S. D., -Safety assesment of AC earthing system in a DC traction-supply Substation, IEEE Journals, 2005, Page(s): 885-893
[5] IEEE Std. 80-2000, -IEEE Guide for Safety in AC Substation Grounding, IEEE: Institute of Electrical and Electronic Engineers, Inc., New York, 2000, Page(s) 1- 192
[6] F. Gatta, S. Lauria, G. Parise, - Common grounding system in urban areas (in italian), Conference on -Safety in complex system-Bari (Italy) 16-17 October 2003.
[7] K. M. Bhatia and B. K. Jain, -Standardization in the Field of Electrical Safety.
[8] IEEE Std. 142-2007, -IEEE Recommended Practice for Grounding of Industrial and Commercial Power System, IEEE: Institute of Electrical and Electronic Engineers, Inc., New York, 2007. Page(s): 1-215
[9] Brian Allport, -Practical considerations (substation earthing), VA TECH Reyrolle Transmission.
[10] H.B. Dwight, "Calculations of Resistances to Ground", AIEE Transactions, December 1936, pp.1319-1328.
[11] J. Nohman and S. Skuletich, "Irregularity Correction Factors for Mesh and Step Voltages of Grounding Grids", IEEE Transactions on Power Apparatus and Systems, vol. PAS-99, No. 1, 1980,pp 174-180.
[12] Thapar, B., Gerez, V., Balakrishnan, A., and Blank, D., Simplified equations for mesh and step voltages in an AC substation, IEEE Trans. Power Delivery, 6, 601-607, 1991
[13] R. J. Heppe, -Computation of potential at surface above an energized grid or other electrode, allowing for nonuniform current distribution, IEEE Trans. on PAS, vol. 98, no. 6, pp. 1978-1989, Nov.-Dec. 1979.
[14] Marlar Thein oo, Ei Ei Cho,Design of earthing system for new substation project , Myanmar.
[15] S. J. Schwartz, "Analytical Expression for Resistance of Grounding Systems", AIEE Transactions, vol. 73, Part 111-B, 1954, pp. 1011-1016.
[16] F. P. Dawalibi and D. Mukhedkar, -Optimum design of substation grounding in two-layer earth structure-Part I, Analytical study, IEEE Trans. on PAS, vol. 94, no. 2, pp. 252-261, Mar.-Apr. 1975.
[17] Xun Long; Ming Dung; Wilsun Xu ; Yun Weili, -Omline Monitoring of Substation Grounding Grid Conditions Using Touch and Step Voltage Sensors, IEEE Journals, 2012, Page(s):761-769
[18] Hernandez Martinez.G.; Venegas Rehollar, V., -Design and Simulation of a grounding grid for GIS Substation IEEE Journals, 2008, Page(s): 137-143
[19] Dwarka Prasad, H.C. Sharma; -Significance of Step and Touch voltages, (IJSCE) Volume-1, Issue-5, November 2011
O.P. Rahi1, Abhas Kumar Singh2, Shashi Kant Gupta3, Shilpa Goyal4
Electrical Engineering Department, National Institute of Technology, Hamirpur, India1,2,3,4
[email protected], [email protected], [email protected], [email protected]
Om Prakash Rahi was born in Kullu (H.P.), India. He received the B.Tech. degree from REC Hamirpur (HP), India, in 1992, and the M.E. degree in Electrical Power Systems from Punjab Engineering College, Chandigarh, in 1997. He joined Government Polytechnic, Sundernagar (HP) as Lecturer in 1997. Since 2000, he has been working as Lecturer in the Electrical Engineering Department, National Institute of Technology, Hamirpur, H.P., and India. He has published a number of research papers. His research interests are in the area of Condition Monitoring of Power Transformers, Deregulation of Power and Hydro Power Development.
Abhas Kumar Singh was born in Ambikapur (Surguja) C.G., India. He received the 3 year Diploma in Electrical Engg. from Govt. Polytechnic College Ambikapur India, in 2007 and the B.Tech. degree in Electrical and Electronics Engineering from Shri Shankaracharya College of Engg. & Tech. Bhilai, India, in 2010.He is currently pursuing the M.Tech. degree in Power System from National Institute of Technology, Hamirpur.
Shashi Kant Gupta was born in Obra (Uttar Pradesh), India. He received the B.Tech. degree in Electrical and Electronics Engineering from S.R.M.S.C.E.T. Bareilly (UP), India, in 2010. He is currently pursuing the M.Tech. degree in Power System from National Institute of Technology, Hamirpur.
Shilpa goyal was born in Chandigarh . She received the B.Tech. degree in Electrical and Electronics Engineering from NIT Hamirpur in 2010. She is currently working in Infosys.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
Copyright International Journal of Advanced Computer Research Dec 2012