Full text

Turn on search term navigation

© 2019. This work is licensed under http://creativecommons.org/licenses/by/3.0/ (the “License”). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.

Abstract

A DC circuit breaker is piece of core equipment for DC grid construction and can achieve fast isolation of DC faults in the grid. In this paper, based on the fault characteristics and protection requirements of an AC/DC hybrid distribution network, the technical parameters and topology structure of an inductance and capacitance (LC) resonant commutation-type mechanical DC breaker are proposed. Furthermore, an engineering prototype of the mechanical DC circuit breaker is developed, then a small current breaking test and a large current breaking test are carried out. The test results show that a 10 kA fault current can be interrupted within 10 ms by the engineering prototype. Finally, the engineering prototype of the mechanical DC circuit breaker is installed in the AC/DC hybrid distribution network project, and a current breaking test is carried out. The test results show that the mechanical DC circuit breaker has good running conditions, and the function and performance meet the engineering design and operation requirements.

Details

Title
Development and Application of a 10 kV Mechanical DC Circuit Breaker
Author
Qu, Lu  VIAFID ORCID Logo  ; Yu, Zhanqing; Xiao, Xiang; Zhao, Wei; Huang, Yulong; Zeng, Rong
First page
3615
Publication year
2019
Publication date
2019
Publisher
MDPI AG
e-ISSN
19961073
Source type
Scholarly Journal
Language of publication
English
ProQuest document ID
2317021229
Copyright
© 2019. This work is licensed under http://creativecommons.org/licenses/by/3.0/ (the “License”). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.