This is an open access article distributed under the Creative Commons Attribution License, which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
1. Introduction
Power transmission line is the only medium of power transmission in the power system and an important part of the power system. High voltage transmission lines have the characteristics of a long paths, mostly in the field or beside the urban road, so line faults often occur. In case of fault of high-voltage transmission line, if the reclosing cannot be completed successfully, the power system will stop the power supply. Frequent power outages will affect the reliability of power supply, fail to serve power customers well, affect the power supply income of power companies, and may affect the safe and stable operation of regional power systems [1]. Therefore, in the case of a power line fault, if the fault location can be determined quickly and accurately, it can improve the maintenance efficiency and significantly reduce various economic losses caused by power failure caused by line fault. Therefore, improving the fault location accuracy of transmission lines has important practical significance for power supply enterprises and power customers. It is a key research topic for power enterprises and scientific research institutes at home and abroad. Due to the development of the urban economy and the shortage of land resources, the total length of cable transmission lines increases year by year, and the operation time of cable lines continues to increase. At the same time, due to the influence of construction level, municipal construction, service conditions, and other factors, the faults of cable lines continue to increase and the types of faults are diverse. However, since the cable is laid below the ground, in the cable tunnel, channel, and pipe row, when the fault occurs, the maintenance personnel cannot directly observe the fault point. The fault location needs to be carried out in advance, and then the covering on the cable fault point can be removed for maintenance [2]. Therefore, the accuracy of cable positioning will directly determine the time of troubleshooting. If the fault point can be located quickly and accurately, the fault can be repaired in time and the power supply can be restored as soon as possible, which can effectively improve the reliability of the power supply, improve the power consumption satisfaction of users, and provide a strong guarantee for building a strong smart grid.
2. Literature Review
Salehimehr et al. use an expert system method to detect the fault of high-voltage power cable, can regard the knowledge base as the basic database, effectively update the knowledge base based on rules in the analysis, and complete the comprehensive extraction of key fault information. The expert system designed in the research, it has a man-machine interface to judge and make decisions, and the system also realizes the three components of fault diagnosis, rough measurement, and precise measurement. Combined with the actual situation of wavelet transform and fault diagnosis, it can achieve a more accurate effect of power cable fault measurement [3]. Rakesh et al. advocated using the impedance method to solve the problem of line fault in the research, which means that when there is an obvious fault difference, the interval between fault points can be determined by using impedance method to analyze the measurement points and fault points and analyzing the impedance value and the impedance ratio. However, it is necessary to set a uniform line in the analysis, and the use of impedance method can effectively reduce the cost. This fault detection method is more applicable to simple circuits, but not too complex circuits [4]. Kim et al. pointed out that the problem of cable fault location can be realized by a wavelet algorithm. In the research, the pulse current test method wavelet transform method is proposed. After processing and decomposing the recorded wavelet data, it is reconstructed, and the signal distance of the pulse is determined based on the premise of data analysis. During the analysis, it is determined that the impedance method can be used for single terminal ranging. Combined with the actual measurement results of current and voltage, it is found that this method can achieve 2.4% of the average measurement accuracy, but 4% of the measurement error. Therefore, the measurement accuracy still needs to be further developed [5]. Yang et al. analyzed the theoretical model of the s injection method and proposed that by connecting the connection points of signal current value, it can be seen that the fundamental frequency between bus and grounding wire exceeds n but is lower than N + 1, and then the existing fault points can be found by signal detector equipment. After the power transmission is stopped, the power detection instrument is matched with the signal injection method, which can obtain a more accurate fault point search, but it should not be used when the signal is too weak and the distance is too long. When there are branches, it is still necessary to ensure that the detection branch line used reaches 6 m [6].
The high-voltage power grid is not easy for people to touch, while the low-voltage power grid has a large coverage, much electrical equipments, and more opportunities for people to touch. Electric leakage accidents of low-voltage power supply lines will occur due to factors such as damp electrical lines, overload power consumption in peak power consumption, aging or damage of household line and outgoing line insulation, rupture of rubber insulated line sheath, flexible cable sheath and insulation layer, improper selection or loose falling off of flexible cable joint insulation binding, etc., resulting in electric shock, fire and other disasters. Therefore, the goal and key point of this research are to realize the alarm before the threshold value or cut off the line power supply in time when the threshold value is reached through the electrical line leakage fault detection and alarm system [7]. Abnormal current or voltage signals will appear when there is a leakage somewhere in the low-voltage electrical line. By detecting and processing these trigger signals, we can judge which section of the electrical line has a leakage fault and the approximate location of leakage, to give an alarm prompt and start the corresponding leakage protection actuator.
3. Research Methods
3.1. System Composition and Principle
3.1.1. System Composition
Part of the residual current, or zero-phase current, occurs when a drop occurs in a low voltage line. The detector is designed with zero phase current, which is a signal to indicate leakage. The detected material is a zero-one phase current transformer. After the fault of the line, the equilibrium of the current vectors of the phase line and the center line is not equal to zero, thus generating the electric field. After amplifying, comparing, and converting to analog-to-digital, the signal is transmitted by sending it to a microcomputer. With the help of loss detection, many tests and diagnostics have been completed of the digital signal, including fault lines and similarities, displaying this information with LEDs, and making sound and seeing the alarm. safety warning [8, 9]. Figure 1 shows the structure of the electrical protection circuit breaker.
[figure(s) omitted; refer to PDF]
3.1.2. Electric Leakage Fault Detection Principle of Electrical Circuit
Electrical protection devices shall be placed in the electrical meter on the grid or at a distance. When the low-sequence circuit currents are constant and there is no damage, the zero-sequence circuit of the current coming and going through one end of the circuit must be zero and the vacuum pump should be ready; When a leakage current occurs in one of the electric fields, a portion of the electric current flows from the atmosphere to the Earth, causing the difference between electrical and electronic equipment. After completing the signal occur several times, depending on the size of the leakage current signal, we can filter the distance of the leakage material to see with the help of different algorithms correct. In addition, depending on the number of leaks, we can identify the area near the leak where the leak occurs.
3.2. System Hardware Implementation
A visual pump is installed in the low-voltage line to identify the zero-phase section of the line. When there is no damage to the line, no power supply, and no line loss, the sum of the values of the line current of the line is zero; When the line fails, a single-phase grounding fault current
The signal to support the shock during operation is also an analog signal. An analog-to-digital converter must send this to the MCU for calculation. Analog-to-digital conversion is the process of converting analog input to digital values, and the converter circuit to analog-to-digital is an integral part of the entire data collection section. A-10 bit A/D conversion chip TLC1543 is used to follow the system operating index and signal characteristics, and its analog input voltage corresponds to the value of 0∼1024 and is 0∼ + 5 V [11]. In-circuit connections, pin A0 is the end of the signal input drop. Changing the CS end edge will restart the internal gauge and control the activation. ADDRESS (pin 17) is a 4-bit serial address used to select the next analog signal input or signal conversion experiment. The output file is the final 3-state serial output after conversion A/D. It can be connected to a microprocessor or peripheral serial port, and the length and type of data are output. optional modification.
When the signal is converted to a digital signal, it is sent to the MCU for operation. MCU is an important part of data management in all control circuits. The most recent update features the 8051 series MCU STC15F2K60S2, which has two independent ports; The built-in crystal oscillator and resets circuit greatly improve the interference resistance; It has multiple input/output ports, high speed, low power consumption, and most importantly low cost. This makes the system suitable for many applications and changes.
If the whole electrical circuit works normally and there is no leakage fault, the working state indicator is in the green flashing state, and its working state is controlled by the single-chip microcomputer I/O port P1.1 [12]. In case of leakage fault, the single-chip microcomputer program will set port P1.3 high, the triode
3.3. Software Design
3.3.1. Software Workflow
The operation of the software system is shown in Figure 2. The system is in low power standby mode when the electrical circuit is normal and no damage; The signal loss model is installed into an electronic circuit, upgraded to hardware, and then converted to analog-to-digital and sent to a single microcomputer for counting and analyzing check. Depending on the groundwater availability, the location of the fault is determined and the results are transmitted to the equipment by serial connection. If the electric current passes through the hard circuit, the protection device must be controlled and operated by the microcomputer alone to ensure the safety of the electronic device and prevent interference intersection of electrical equipment and staff [15].
[figure(s) omitted; refer to PDF]
3.3.2. Leakage Current Fault Detection Algorithm
In the event of a fault in the circuit, it is necessary to calculate the leakage current in the circuit to determine the location of the circuit leak, and to determine the voltage between the average point MQ and the load average point ml. In the low-voltage electrical circuit, there are three-phase voltages (
The conventional setup consists of a three-phase filter connecting three X capacitors to the neutral medium and conducting them through a Y capacitor or filter cover. In the case of a balanced capacitor circuit, the leakage current must be neglected. On the other hand, when the maximum phase difference is reached, the mains reach the maximum value of the current range [16, 17]. The reason for the discrepancy is the tolerance of the capacitor values and the inconsistency of the capacitance in the power supply. Therefore, the key element of leakage current is the voltage
Then, the digital return value
3.3.3. Software Anti-Interference Design
Because the operation of the pump is usually outdoor, there is a lot of signal interference, and the interference of electromagnetic pressure by the electric field can cause signal analog input distortion, signal control confusion, control failure, and operation failure. accident, address or bus information confusion, etc. Therefore, the design of the anti-interference system is associated with a high degree of reliability in the immune system. In addition to strengthening interference hardware, interference software must be specially designed [18]. If the system program is running and entering a dead loop, the support program can be run by 0000H. The reset circuit is connected to the reset terminal of a single-chip microcomputer, and the capacitor and grounding resistors provide power to the reset circuit, so the program is run by the 0000H unit. Reset Circuit and Manual Reset Circuit can provide a reset signal higher than 10 mA for the reset chip. The MAX813L reset chip offers real-time monitoring and power control. When the system program is caught in a dead cycle or when the power changes suddenly, it does not cause a crash, read data, write errors, or malfunction, so restart the system to the faulty state [19, 20].
4. Result Analysis
The environment for experiment and debugging, in which
[figure(s) omitted; refer to PDF]
According to the comparative analysis of leakage fault simulation test data and referring to the requirements of in the national standard “Leakage Current Operated Protector (residual current operated protector)” GB 6829-86, the indirect contact leakage test results are shown in Table 1 and Figure 4, and the direct contact leakage test results are shown in Table 2 [23].
Table 1
Test results of indirect contact leakage fault.
Leakage currentdetection value (mA) | Operatingcurrent (mA) | Faultlocation (m) | Actiontime (ms) |
6.4 | 30 | 19 | 68 |
6.6 | 30 | 17 | 70 |
6.2 | 30 | 21 | 60 |
[figure(s) omitted; refer to PDF]
Table 2
Test results of direct contact leakage fault.
Leakage currentdetection value (mA) | Operatingcurrent (mA) | Faultlocation (m) | Actiontime (ms) |
26 | Any | 16 | 35 |
33 | Any | 13 | 36 |
38 | Any | 11 | 33 |
Through the test of analog leakage signal and the test results, it can be concluded that the whole system operates stably, the fault detection is accurate, and there is no crash. According to the comparison between the indirect leakage detection and direct leakage detection results and the actual leakage position distance, the error is within 10%, which can meet the detection and positioning requirements of an electrical circuit leakage fault [24–26].
5. Conclusion
Taking the single-chip microcomputer as the control core, the system proposes to detect the leakage fault based on the zero-sequence circuit as the trigger signal, which can detect and locate the faults in time after the leakage fault occurs in the low-voltage power supply line. It plays a preventive role in the evolution of small fault into a large fault, to reduce the scope of fault power failure, facilitate the search for leakage fault, shorten the time of leakage power failure and improve the reliability of power supply.
[1] S. Wang, P. Dehghanian, "On the use of artificial intelligence for high impedance fault detection and electrical safety," IEEE Transactions on Industry Applications, vol. 56 no. 6, pp. 7208-7216, DOI: 10.1109/tia.2020.3017698, 2020.
[2] G. Kim, S. H. Min, Y. Won, K. Lee, S. I. Youn, B. C. Tan, Y. S. Park, S. H. Ahn, D. J. Park, H. H. Kim, "Frailty in elderly gastric cancer patients undergoing gastrectomy," Digestive Surgery, vol. 12,DOI: 10.1159/000511895, 2020.
[3] S. Salehimehr, B. Taheri, M. Faghihlou, "Detection of power swing and blocking the distance relay using the variance calculation of the current sampled data," Electrical Engineering, vol. 104 no. 2, pp. 913-927, DOI: 10.1007/s00202-021-01350-1, 2021.
[4] N. Rakesh, S. Banerjee, S. Subramaniam, N. Babu, "A simplified method for fault detection and identification of mismatch modules and strings in a grid-tied solar photovoltaic system," International Journal of Emerging Electric Power Systems, vol. 21 no. 4, pp. 1066-1073, DOI: 10.1515/ijeeps-2020-0001, 2020.
[5] J. W. Kim, S. J. Yang, Y. I. Son, "Performance improvement of a pi observer for line fault detection of a single machine infinite bus system under model uncertainty," Transactions of the Korean Institute of Electrical Engineers, vol. 70 no. 2, pp. 387-394, DOI: 10.5370/kiee.2021.70.2.387, 2021.
[6] S. J. Yang, S. Y. Jang, Y. I. Son, "Design of a dqn-based dob for line fault detection of a single machine infinite bus system against measurement noise," Transactions of the Korean Institute of Electrical Engineers, vol. 69 no. 7, pp. 1095-1101, DOI: 10.5370/kiee.2020.69.7.1095, 2020.
[7] D. Balladka, "Unmanned fault detection in distribution lines," European Journal of Engineering Education, vol. 23 no. 1, pp. 37-43, DOI: 10.18280/ejee.230105, 2021.
[8] K. Jnaneswar, B. Mallikarjuna, S. Devaraj, D. S. Roy, M. J. B. Reddy, D. K. Mohanta, "A real-time dwt and traveling waves-based multi-functional scheme for transmission line protection reinforcement," Electrical Engineering, vol. 103 no. 2, pp. 965-981, DOI: 10.1007/s00202-020-01117-0, 2020.
[9] M. H. Rezaeian Koochi, P. Dehghanian, S. Esmaeili, "Pmu placement with channel limitation for faulty line detection in transmission systems," IEEE Transactions on Power Delivery, vol. 35 no. 2, pp. 819-827, DOI: 10.1109/tpwrd.2019.2929097, 2020.
[10] Z. Zhang, S. Bai, G. S. Xu, X. Liu, J. Jia, Z. Feng, F. Wang, "Knitting needle fault detection system for hosiery machine based on laser detection and machine vision," Textile Research Journal, vol. 91, pp. 143-151, DOI: 10.1177/0040517520935210, 2020.
[11] B. K. Karmakar, A. K. Pradhan, "Detection and classification of faults in solar pv array using thevenin equivalent resistance," IEEE Journal of Photovoltaics, vol. 10 no. 2, pp. 644-654, DOI: 10.1109/jphotov.2019.2959951, 2020.
[12] J. Sun, J. B. Tan, T. Chen, "Investigation of electrical noise signal triggered resistive switching and its implications," IEEE Transactions on Electron Devices, vol. 67 no. 10, pp. 4178-4184, DOI: 10.1109/ted.2020.3014841, 2020.
[13] D. Valsecchi, "Ecal trigger performance in run 2 and improvements for run 3," Journal of Instrumentation, vol. 15 no. 6,DOI: 10.1088/1748-0221/15/06/c06037, 2020.
[14] A. Wiranata, E. Winata, "The implementation of fast fourier transform and coherence function to detect the millimetric hole on strip iron plate," Key Engineering Materials, vol. 840, pp. 430-437, DOI: 10.4028/www.scientific.net/kem.840.430, 2020.
[15] B. Wca, A. Wl, A. Hs, A. Sc, A. Pl, C. Yla, "Molecular and logic gate for multiple single-nucleotide mutations detection based on crispr/cas9n system-trigged signal amplification—sciencedirect," Analytica Chimica Acta, vol. 1112, pp. 46-53, 2020.
[16] Y. Zhao, P. Lang, "Optimal method of load signal control of power based on state difference clustering," Advanced Hybrid Information Processing, 2019.
[17] R. Huang, R. Zhou, Q. Li, "Mid-infrared supercontinuum generation in chalcogenide photonic crystal fibers with a weak cw trigger," Journal of Lightwave Technology, vol. 38 no. 6, pp. 1522-1528, DOI: 10.1109/jlt.2019.2957170, 2020.
[18] Y. K. Shogenov, A. K. Shogenov, "Drying induction motor windings with zero-sequence current," Russian Electrical Engineering, vol. 92 no. 4, pp. 217-220, DOI: 10.3103/s1068371221040064, 2021.
[19] Q. Lu, Y. Zuo, T. Zhang, L. Mo, "Zero-sequence current suppression for open-winding permanent magnet brushless motor driving system based on second order generalized integrator," IEEE Access, vol. 8, pp. 37465-37473, DOI: 10.1109/access.2020.2975126, 2020.
[20] Z. Zeng, Z. Li, S. M. Goetz, "Line current ripple minimization pwm strategy with reduced zero-sequence circulating current for two parallel interleaved three-phase converters," IEEE Transactions on Power Electronics, vol. 35 no. 7, pp. 6931-6943, DOI: 10.1109/tpel.2019.2958878, 2020.
[21] A. G. Shcherbinin, M. D. Naumov, E. V. Subbotin, "Determination of positive-negative-and zero-sequence impedances for power cables using mathematical modeling of electromagnetic processes," Russian Electrical Engineering, vol. 92 no. 11, pp. 659-662, DOI: 10.3103/s1068371221110134, 2022.
[22] J. Dogra, S. Jain, A. Sharma, R. Kumar, M. Sood, "Brain tumor detection from MR images employing fuzzy graph cut technique," Recent Advances in Computer Science and Communications, vol. 13 no. 3, pp. 362-369, DOI: 10.2174/2213275912666181207152633, 2020.
[23] P. Ajay, J. Jaya, "Bi-level energy optimization model in smart integrated engineering systems using WSN," Energy Reports, vol. 8, pp. 2490-2495, DOI: 10.1016/j.egyr.2022.01.183, 2022.
[24] L. Li, Y. Diao, X. Liu, "Ce-Mn mixed oxides supported on glass-fiber for low-temperature selective catalytic reduction of NO with NH 3," Journal of Rare Earths, vol. 32 no. 5, pp. 409-415, DOI: 10.1016/s1002-0721(14)60086-7, 2014.
[25] R. Huang, "Framework for a smart adult education environment," World Transactions on Engineering and Technology Education, vol. 13 no. 4, pp. 637-641, 2015.
[26] L. Yan, K. Cengiz, A. Sharma, "An improved image processing algorithm for automatic defect inspection in TFT-LCD TCON," Nonlinear Engineering, vol. 10 no. 1, pp. 293-303, DOI: 10.1515/nleng-2021-0023, 2021.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer
Copyright © 2022 Yakun Fu. This is an open access article distributed under the Creative Commons Attribution License (the “License”), which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited. Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License. https://creativecommons.org/licenses/by/4.0/
Abstract
In order to locate the leakage fault location of low-voltage electrical lines, cut off the power supply of electrical lines, and ensure the safety and reliability of the power supply network, this paper proposes an electrical line leakage fault detection system based on a signal trigger. Based on the research on the current leakage protection system of low-voltage electrical lines, the author puts forward that the leakage current of the selected test analog trigger signal is not less than twice the maximum value of the normal leakage current of electrical lines and equipment with STC15F2K60S2 single-chip microcomputer as the control core. The experimental results show that 30 mA is preferred for the sensitivity of the leakage fault test signal. When the rated leakage action current is equal to or less than 30 mA, the protection action time is required to be less than 0.1 s, and when the rated leakage action current is greater than 30 mA, it is required to be less than 0.2 S. The device is a supplement to the traditional leakage protection device. According to the comparison between the indirect leakage detection and direct leakage detection results and the actual leakage position distance, the error is within 10%. It is proved that the system meets the actual needs and improves the protection performance of the leakage protection system of low-voltage electrical lines.
You have requested "on-the-fly" machine translation of selected content from our databases. This functionality is provided solely for your convenience and is in no way intended to replace human translation. Show full disclaimer
Neither ProQuest nor its licensors make any representations or warranties with respect to the translations. The translations are automatically generated "AS IS" and "AS AVAILABLE" and are not retained in our systems. PROQUEST AND ITS LICENSORS SPECIFICALLY DISCLAIM ANY AND ALL EXPRESS OR IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, ANY WARRANTIES FOR AVAILABILITY, ACCURACY, TIMELINESS, COMPLETENESS, NON-INFRINGMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Your use of the translations is subject to all use restrictions contained in your Electronic Products License Agreement and by using the translation functionality you agree to forgo any and all claims against ProQuest or its licensors for your use of the translation functionality and any output derived there from. Hide full disclaimer