© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.

Abstract

Precision ventilation is developed to achieve thermal comfort for occupants in an office by creating micro-climate zones. The present study aims to achieve individual thermal comfort for occupants with different metabolic rates by using higher airspeeds for enhancing heat transfer. The variable jet interaction between two ACBs with JetCone adjustments cause higher velocity jets to reach different regions of the occupied zone. The colliding jets from the center of a thermal isolated room were moved towards different zones in an office configuration with a constant room temperature of 23 °C. This study was conducted for five different cases in a room divided into four zones according to occupants’ metabolic rates. The experimental and CFD results show that occupants facing symmetrical airflow distribution and with a constant 1.2 metabolic rate (Case 1) had a similar predicted mean vote (PMV) index. The zones with higher-metabolic-rate occupants, i.e., 1.4 met and 1.6 met in cases 2 and 3 were exposed to air velocities up to 0.4 and 0.5 m/s, respectively. In case 4, the air velocity in the single zone with 1.6 met occupants was raised to 0.6 m/s by targeted airflow distribution achieved by adjusting JetCones. These occupants with higher metabolic rates were kept thermally neutral, in the −0.5 to +0.5 PMV range, by pushing the high velocity colliding jets from the center towards them. In case 5, the results showed that precision ventilation can maintain the individual thermal comfort of up to three different zones (in the same office space) by exposing the occupants with metabolic rates of 1.2, 1.4, and 1.6 met to airspeeds of 0.15, 0.45, and 0.55 m/s, respectively.

Details

Title
Precision Ventilation for an Open-Plan Office: A Study of Variable Jet Interaction between Two Active Chilled Beams
Author
Haider Latif 1 ; Rahnama, Samira 1 ; Maccarini, Alessandro 1 ; Bradshaw, Craig R 2   VIAFID ORCID Logo  ; Hultmark, Goran 3 ; Nielsen, Peter V 1 ; Afshari, Alireza 1 

 The Department of the Built Environment, Aalborg University, 2450 Copenhagen, Denmark 
 The Center for Integrated Building Systems, School of Mechanical and Aerospace Engineering, Oklahoma State University, Stillwater, OK 74078-5016, USA 
 Indoor Climate Solutions, Lindab A/S, 3520 Haderslev, Denmark 
First page
11466
Publication year
2022
Publication date
2022
Publisher
MDPI AG
e-ISSN
20711050
Source type
Scholarly Journal
Language of publication
English
ProQuest document ID
2716585270
Copyright
© 2022 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/). Notwithstanding the ProQuest Terms and Conditions, you may use this content in accordance with the terms of the License.